"> LO Standby/Priming Pump - Equipment Database

LO Standby/Priming Pump

high 3 models total

This pump only earns its keep on standby, priming the lubricating oil system before a cold start and automatically taking over if the main LO pump trips; a monthly no-load start test can hide a pump that seizes the moment it is asked to deliver real flow against system pressure.

Read more — LO Standby/Priming Pump explained

What sets the LO standby/priming pump apart

This pump exists for the moments the main lubricating oil pump cannot cover: before the main engine starts, when the shaft-driven or electric main LO pump has not yet built pressure, and as an automatic backup if the main pump trips while the engine is running. It does not run continuously alongside the main pump under normal load — it is either idle, priming the system before start, or picking up the full duty automatically the instant low LO pressure is detected.

Lube oil standby/priming pump
The electric standby pump draws from the LO sump and delivers through its own non-return valve into the common line that the duty main LO pump also feeds, so it can prime the system before start and take over automatically on a pressure switch signal.

Main components

Pump and motor

Usually a smaller electric centrifugal or screw pump than the main LO pump, sized to deliver enough pressure and flow to protect bearings, not to match full running capacity — many are rated to sustain the engine at reduced load or dead slow only.

Automatic start relay

A pressure switch on the main LO line triggers the standby pump to start within a set delay, commonly a few seconds, if main LO pressure drops below the alarm setpoint. This automatic changeover is the core safety function of the whole unit.

Non-return valve

Prevents the main pump, once it recovers or restarts, from driving oil backward through the idle standby pump and its motor.

Suction strainer

A dedicated strainer, often finer than the main pump's, since a standby pump that starts automatically after months of idle standby is exactly the pump most likely to pick up settled sludge from the bottom of the sump.

Selection and sizing

  • Flow and pressure sufficient to maintain minimum bearing protection at the load the engine is permitted to run at on standby pump alone
  • Automatic start delay short enough to avoid bearing damage but long enough to ignore momentary pressure dips from rolling or manoeuvring
  • Motor supplied from the emergency switchboard or a source independent of the main pump's supply, so a single electrical fault cannot take out both pumps
  • Compatibility confirmed with priming duty — some standby pumps double as the priming pump used before every cold start, which adds self-priming capability to the specification

Regulations and class

Class rules for main propulsion machinery require a standby means of lubrication such that loss of the main LO pump does not immediately endanger the engine, and for unmanned machinery space notation the automatic changeover and its alarm must function without manual intervention. Surveyors test the automatic start function directly, simulating a main pump trip and timing the standby pump's pickup and the resulting pressure recovery.

Typical faults

  • Automatic start relay never tested in service — fails to trigger on the one occasion the main pump actually trips
  • Standby pump seized or seal-bound from long idle periods without a periodic run — discovered only during the automatic changeover test, or worse, during a real trip
  • Suction strainer clogged with settled sludge — pump starts but cannot draw sufficient flow, so LO pressure keeps falling despite the changeover
  • Priming function left disabled after a control system update — engine start attempted on an unprimed system, risking a dry start on the bearings

What to look for in a supplier

  • Documented automatic start and changeover time tested at the factory, not just claimed in a data sheet
  • Self-priming capability confirmed if the pump is also intended for pre-start priming duty
  • Motor and control gear compatible with the vessel's emergency power arrangement
  • Seal design suited to long idle periods without weeping or seizing, since this pump spends most of its life stationary

Run the standby LO pump on load, not just on a no-flow test bench check, at least once a month — a pump that starts on command but cannot deliver pressure against the real system resistance gives a false sense of security until the day the main pump actually fails.

4000h
Service Interval
25 yr
Typical Lifetime

Typical Manufacturers

IMO Naniwa Shinko

3 manufacturers · 3 models

IMO

1
ACE 025L3
30 m3/h · 7.5 kW · Lube Oil · Low-Speed Centrifugal Pump
Common Failures & Inspection Points
  • Screw wear
  • Seal leakage
  • Low discharge pressure
Service: Run weekly for 15 min to verify readiness.
Spare Parts: IMO: Ersatzteile per Hersteller-Ersatzteilliste. Mechanische Dichtungen und Laufräder an Bord vorhalten. Lead time: 2-6 Wochen je nach Hersteller.
Strengths
  • High discharge pressure to meet main engine requirements
  • Robust design for long service life and reduced maintenance
  • Efficient priming system for quick startup and minimal wear on engine components
Weaknesses
  • Potential for screw wear due to high-pressure operation
  • Seal leakage can occur if not properly maintained or replaced
  • Low discharge pressure may indicate worn-out pump components
Typical Vessels: Bulk CarrierContainer ShipTanker
Certifications: IMO Type ApprovalDNV GL Certification
Decision Guide: Choose if: You require a reliable LO standby/priming pump for main engine systems. Avoid if: You need a high-flow rate or low-maintenance solution.
Use Cases: Typically deployed on vessels with large main engines, such as bulk carriers and container ships, where a reliable source of lubrication oil is critical to smooth operation.

Naniwa

1
FG-200
25 m3/h · 5.5 kW · Lube Oil · Centrifugal Pump
Common Failures & Inspection Points
  • Gear wear
  • Relief valve sticking
  • Coupling failure
Service: Keep as warm standby; auto-start on LO pressure drop.
Spare Parts: Naniwa: Ersatzteile per Hersteller-Ersatzteilliste. Mechanische Dichtungen und Laufräder an Bord vorhalten. Lead time: 2-6 Wochen je nach Hersteller.
Strengths
  • Automatic start on low oil pressure
  • Compact design for space-saving installation
  • Reliable performance in warm standby mode
Weaknesses
  • Prone to gear wear and coupling failure
  • Relief valve sticking can cause operational issues
  • May require frequent maintenance checks
Typical Vessels: TankerContainerBulk Carrier
Decision Guide: Choose if you need a reliable standby pump for maintaining oil pressure in critical systems. Avoid if you have limited space for maintenance or prefer pumps with lower failure rates.
Use Cases: Typically deployed in the engine rooms of large vessels, such as tankers and container ships, where continuous oil flow is crucial for engine operation.

Shinko

1
Shinko GVK 150
GVK 150
20 m3/h · 5.5 kW · Lube Oil · self-priming centrifugal pump
Common Failures & Inspection Points
  • Rotor clearance increase
  • Seal deterioration
Service: Test auto-start weekly; check non-return valve.
Spare Parts: Shinko: Ersatzteile per Hersteller-Ersatzteilliste. Mechanische Dichtungen und Laufräder an Bord vorhalten. Lead time: 2-6 Wochen je nach Hersteller.
Strengths
  • Low oil consumption reduces maintenance intervals
  • Automatic start function provides rapid response in emergencies
  • High suction lift capability ensures reliable priming even when the inlet is flooded
  • Robust cast‑iron construction tolerates harsh marine environments
  • Compact footprint fits limited engine‑room spaces
Weaknesses
  • Rotor clearance wear can increase over time, leading to reduced efficiency
  • Mechanical seal deterioration is a known failure mode requiring periodic inspection
  • Flow capacity is modest compared with larger dedicated fire‑main pumps
  • Requires weekly auto‑start testing and non‑return valve checks to stay ready
Typical Vessels: TankerBulk CarrierContainer ShipOffshore Supply VesselCruise Ship
Decision Guide: Choose if: you need a reliable, low‑oil standby pump with automatic start for fire‑main or engine‑cooling priming on vessels where space and oil consumption are critical. Avoid if: the vessel requires very high flow rates or prefers an oil‑free (electric) backup system.
Use Cases: Commonly installed as the primary standby pump in fire‑fighting systems, as a priming pump for main engine cooling circuits, and as a backup bilge suction unit on various merchant ships.