Deluge/Sprinkler System
6 manufacturers · 64 models
Tyco
19 ✓ 19 verified- Area: Diaphragm Integrity and LeakageCheck: Inspect for water or air leakage from bonnet cover and outlet drain; verify no external moisture on diaphragm chamber; perform annual full trip test to verify diaphragm response and proper valve opening
- Area: Strainer and Filter BlockageCheck: Clean strainer in diaphragm chamber supply control valve; inspect for sediment, corrosion debris, or mineral deposits; perform internal inspection of strainers every 5 years per NFPA 25; replace if significant blockage detected
- Area: Pilot Line Pressure and Air SupplyCheck: Verify dry pilot line air pressure maintained at design pressure (typically 40-50 psi); check for air leaks at connections; ensure air drier functioning and dew point below lowest ambient temperature; test pressure gauge reading weekly
- Area: Nozzle and Sprinkler ConditionCheck: Inspect all deluge nozzles/sprinklers for corrosion, mechanical damage, or buildup; verify proper orientation and alignment; check for blockage or paint over orifices; ensure DN-5 duct nozzles maintain HALAR coating integrity
- Area: Control Valve Assembly ConditionCheck: Check for external corrosion on valve body, actuators, and piping; verify bonnet bolts are tight; inspect manual reset actuator (MRA-1) for damage; ensure dry pilot actuators (DP-1/DP-2) have no water/air leakage at drain outlet
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Diaphragm Integrity and LeakageCheck: Inspect for water or air leakage from bonnet cover and outlet drain; verify no external moisture on diaphragm chamber; perform annual full trip test to verify diaphragm response and proper valve opening
- Area: Strainer and Filter BlockageCheck: Clean strainer in diaphragm chamber supply control valve; inspect for sediment, corrosion debris, or mineral deposits; perform internal inspection of strainers every 5 years per NFPA 25; replace if significant blockage detected
- Area: Pilot Line Pressure and Air SupplyCheck: Verify dry pilot line air pressure maintained at design pressure (typically 40-50 psi); check for air leaks at connections; ensure air drier functioning and dew point below lowest ambient temperature; test pressure gauge reading weekly
- Area: Nozzle and Sprinkler ConditionCheck: Inspect all deluge nozzles/sprinklers for corrosion, mechanical damage, or buildup; verify proper orientation and alignment; check for blockage or paint over orifices; ensure DN-5 duct nozzles maintain HALAR coating integrity
- Area: Control Valve Assembly ConditionCheck: Check for external corrosion on valve body, actuators, and piping; verify bonnet bolts are tight; inspect manual reset actuator (MRA-1) for damage; ensure dry pilot actuators (DP-1/DP-2) have no water/air leakage at drain outlet
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Diaphragm Integrity and LeakageCheck: Inspect for water or air leakage from bonnet cover and outlet drain; verify no external moisture on diaphragm chamber; perform annual full trip test to verify diaphragm response and proper valve opening
- Area: Strainer and Filter BlockageCheck: Clean strainer in diaphragm chamber supply control valve; inspect for sediment, corrosion debris, or mineral deposits; perform internal inspection of strainers every 5 years per NFPA 25; replace if significant blockage detected
- Area: Pilot Line Pressure and Air SupplyCheck: Verify dry pilot line air pressure maintained at design pressure (typically 40-50 psi); check for air leaks at connections; ensure air drier functioning and dew point below lowest ambient temperature; test pressure gauge reading weekly
- Area: Nozzle and Sprinkler ConditionCheck: Inspect all deluge nozzles/sprinklers for corrosion, mechanical damage, or buildup; verify proper orientation and alignment; check for blockage or paint over orifices; ensure DN-5 duct nozzles maintain HALAR coating integrity
- Area: Control Valve Assembly ConditionCheck: Check for external corrosion on valve body, actuators, and piping; verify bonnet bolts are tight; inspect manual reset actuator (MRA-1) for damage; ensure dry pilot actuators (DP-1/DP-2) have no water/air leakage at drain outlet
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Diaphragm Integrity and LeakageCheck: Inspect for water or air leakage from bonnet cover and outlet drain; verify no external moisture on diaphragm chamber; perform annual full trip test to verify diaphragm response and proper valve opening
- Area: Strainer and Filter BlockageCheck: Clean strainer in diaphragm chamber supply control valve; inspect for sediment, corrosion debris, or mineral deposits; perform internal inspection of strainers every 5 years per NFPA 25; replace if significant blockage detected
- Area: Pilot Line Pressure and Air SupplyCheck: Verify dry pilot line air pressure maintained at design pressure (typically 40-50 psi); check for air leaks at connections; ensure air drier functioning and dew point below lowest ambient temperature; test pressure gauge reading weekly
- Area: Nozzle and Sprinkler ConditionCheck: Inspect all deluge nozzles/sprinklers for corrosion, mechanical damage, or buildup; verify proper orientation and alignment; check for blockage or paint over orifices; ensure DN-5 duct nozzles maintain HALAR coating integrity
- Area: Control Valve Assembly ConditionCheck: Check for external corrosion on valve body, actuators, and piping; verify bonnet bolts are tight; inspect manual reset actuator (MRA-1) for damage; ensure dry pilot actuators (DP-1/DP-2) have no water/air leakage at drain outlet
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Diaphragm Integrity and LeakageCheck: Inspect for water or air leakage from bonnet cover and outlet drain; verify no external moisture on diaphragm chamber; perform annual full trip test to verify diaphragm response and proper valve opening
- Area: Strainer and Filter BlockageCheck: Clean strainer in diaphragm chamber supply control valve; inspect for sediment, corrosion debris, or mineral deposits; perform internal inspection of strainers every 5 years per NFPA 25; replace if significant blockage detected
- Area: Pilot Line Pressure and Air SupplyCheck: Verify dry pilot line air pressure maintained at design pressure (typically 40-50 psi); check for air leaks at connections; ensure air drier functioning and dew point below lowest ambient temperature; test pressure gauge reading weekly
- Area: Nozzle and Sprinkler ConditionCheck: Inspect all deluge nozzles/sprinklers for corrosion, mechanical damage, or buildup; verify proper orientation and alignment; check for blockage or paint over orifices; ensure DN-5 duct nozzles maintain HALAR coating integrity
- Area: Control Valve Assembly ConditionCheck: Check for external corrosion on valve body, actuators, and piping; verify bonnet bolts are tight; inspect manual reset actuator (MRA-1) for damage; ensure dry pilot actuators (DP-1/DP-2) have no water/air leakage at drain outlet
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Diaphragm Integrity and LeakageCheck: Inspect for water or air leakage from bonnet cover and outlet drain; verify no external moisture on diaphragm chamber; perform annual full trip test to verify diaphragm response and proper valve opening
- Area: Strainer and Filter BlockageCheck: Clean strainer in diaphragm chamber supply control valve; inspect for sediment, corrosion debris, or mineral deposits; perform internal inspection of strainers every 5 years per NFPA 25; replace if significant blockage detected
- Area: Pilot Line Pressure and Air SupplyCheck: Verify dry pilot line air pressure maintained at design pressure (typically 40-50 psi); check for air leaks at connections; ensure air drier functioning and dew point below lowest ambient temperature; test pressure gauge reading weekly
- Area: Nozzle and Sprinkler ConditionCheck: Inspect all deluge nozzles/sprinklers for corrosion, mechanical damage, or buildup; verify proper orientation and alignment; check for blockage or paint over orifices; ensure DN-5 duct nozzles maintain HALAR coating integrity
- Area: Control Valve Assembly ConditionCheck: Check for external corrosion on valve body, actuators, and piping; verify bonnet bolts are tight; inspect manual reset actuator (MRA-1) for damage; ensure dry pilot actuators (DP-1/DP-2) have no water/air leakage at drain outlet
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Diaphragm Integrity and LeakageCheck: Inspect for water or air leakage from bonnet cover and outlet drain; verify no external moisture on diaphragm chamber; perform annual full trip test to verify diaphragm response and proper valve opening
- Area: Strainer and Filter BlockageCheck: Clean strainer in diaphragm chamber supply control valve; inspect for sediment, corrosion debris, or mineral deposits; perform internal inspection of strainers every 5 years per NFPA 25; replace if significant blockage detected
- Area: Pilot Line Pressure and Air SupplyCheck: Verify dry pilot line air pressure maintained at design pressure (typically 40-50 psi); check for air leaks at connections; ensure air drier functioning and dew point below lowest ambient temperature; test pressure gauge reading weekly
- Area: Nozzle and Sprinkler ConditionCheck: Inspect all deluge nozzles/sprinklers for corrosion, mechanical damage, or buildup; verify proper orientation and alignment; check for blockage or paint over orifices; ensure DN-5 duct nozzles maintain HALAR coating integrity
- Area: Control Valve Assembly ConditionCheck: Check for external corrosion on valve body, actuators, and piping; verify bonnet bolts are tight; inspect manual reset actuator (MRA-1) for damage; ensure dry pilot actuators (DP-1/DP-2) have no water/air leakage at drain outlet
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Diaphragm Integrity and LeakageCheck: Inspect for water or air leakage from bonnet cover and outlet drain; verify no external moisture on diaphragm chamber; perform annual full trip test to verify diaphragm response and proper valve opening
- Area: Strainer and Filter BlockageCheck: Clean strainer in diaphragm chamber supply control valve; inspect for sediment, corrosion debris, or mineral deposits; perform internal inspection of strainers every 5 years per NFPA 25; replace if significant blockage detected
- Area: Pilot Line Pressure and Air SupplyCheck: Verify dry pilot line air pressure maintained at design pressure (typically 40-50 psi); check for air leaks at connections; ensure air drier functioning and dew point below lowest ambient temperature; test pressure gauge reading weekly
- Area: Nozzle and Sprinkler ConditionCheck: Inspect all deluge nozzles/sprinklers for corrosion, mechanical damage, or buildup; verify proper orientation and alignment; check for blockage or paint over orifices; ensure DN-5 duct nozzles maintain HALAR coating integrity
- Area: Control Valve Assembly ConditionCheck: Check for external corrosion on valve body, actuators, and piping; verify bonnet bolts are tight; inspect manual reset actuator (MRA-1) for damage; ensure dry pilot actuators (DP-1/DP-2) have no water/air leakage at drain outlet
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Diaphragm Integrity and LeakageCheck: Inspect for water or air leakage from bonnet cover and outlet drain; verify no external moisture on diaphragm chamber; perform annual full trip test to verify diaphragm response and proper valve opening
- Area: Strainer and Filter BlockageCheck: Clean strainer in diaphragm chamber supply control valve; inspect for sediment, corrosion debris, or mineral deposits; perform internal inspection of strainers every 5 years per NFPA 25; replace if significant blockage detected
- Area: Pilot Line Pressure and Air SupplyCheck: Verify dry pilot line air pressure maintained at design pressure (typically 40-50 psi); check for air leaks at connections; ensure air drier functioning and dew point below lowest ambient temperature; test pressure gauge reading weekly
- Area: Nozzle and Sprinkler ConditionCheck: Inspect all deluge nozzles/sprinklers for corrosion, mechanical damage, or buildup; verify proper orientation and alignment; check for blockage or paint over orifices; ensure DN-5 duct nozzles maintain HALAR coating integrity
- Area: Control Valve Assembly ConditionCheck: Check for external corrosion on valve body, actuators, and piping; verify bonnet bolts are tight; inspect manual reset actuator (MRA-1) for damage; ensure dry pilot actuators (DP-1/DP-2) have no water/air leakage at drain outlet
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Diaphragm Integrity and LeakageCheck: Inspect for water or air leakage from bonnet cover and outlet drain; verify no external moisture on diaphragm chamber; perform annual full trip test to verify diaphragm response and proper valve opening
- Area: Strainer and Filter BlockageCheck: Clean strainer in diaphragm chamber supply control valve; inspect for sediment, corrosion debris, or mineral deposits; perform internal inspection of strainers every 5 years per NFPA 25; replace if significant blockage detected
- Area: Pilot Line Pressure and Air SupplyCheck: Verify dry pilot line air pressure maintained at design pressure (typically 40-50 psi); check for air leaks at connections; ensure air drier functioning and dew point below lowest ambient temperature; test pressure gauge reading weekly
- Area: Nozzle and Sprinkler ConditionCheck: Inspect all deluge nozzles/sprinklers for corrosion, mechanical damage, or buildup; verify proper orientation and alignment; check for blockage or paint over orifices; ensure DN-5 duct nozzles maintain HALAR coating integrity
- Area: Control Valve Assembly ConditionCheck: Check for external corrosion on valve body, actuators, and piping; verify bonnet bolts are tight; inspect manual reset actuator (MRA-1) for damage; ensure dry pilot actuators (DP-1/DP-2) have no water/air leakage at drain outlet
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Diaphragm Integrity and LeakageCheck: Inspect for water or air leakage from bonnet cover and outlet drain; verify no external moisture on diaphragm chamber; perform annual full trip test to verify diaphragm response and proper valve opening
- Area: Strainer and Filter BlockageCheck: Clean strainer in diaphragm chamber supply control valve; inspect for sediment, corrosion debris, or mineral deposits; perform internal inspection of strainers every 5 years per NFPA 25; replace if significant blockage detected
- Area: Pilot Line Pressure and Air SupplyCheck: Verify dry pilot line air pressure maintained at design pressure (typically 40-50 psi); check for air leaks at connections; ensure air drier functioning and dew point below lowest ambient temperature; test pressure gauge reading weekly
- Area: Nozzle and Sprinkler ConditionCheck: Inspect all deluge nozzles/sprinklers for corrosion, mechanical damage, or buildup; verify proper orientation and alignment; check for blockage or paint over orifices; ensure DN-5 duct nozzles maintain HALAR coating integrity
- Area: Control Valve Assembly ConditionCheck: Check for external corrosion on valve body, actuators, and piping; verify bonnet bolts are tight; inspect manual reset actuator (MRA-1) for damage; ensure dry pilot actuators (DP-1/DP-2) have no water/air leakage at drain outlet
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Diaphragm Integrity and LeakageCheck: Inspect for water or air leakage from bonnet cover and outlet drain; verify no external moisture on diaphragm chamber; perform annual full trip test to verify diaphragm response and proper valve opening
- Area: Strainer and Filter BlockageCheck: Clean strainer in diaphragm chamber supply control valve; inspect for sediment, corrosion debris, or mineral deposits; perform internal inspection of strainers every 5 years per NFPA 25; replace if significant blockage detected
- Area: Pilot Line Pressure and Air SupplyCheck: Verify dry pilot line air pressure maintained at design pressure (typically 40-50 psi); check for air leaks at connections; ensure air drier functioning and dew point below lowest ambient temperature; test pressure gauge reading weekly
- Area: Nozzle and Sprinkler ConditionCheck: Inspect all deluge nozzles/sprinklers for corrosion, mechanical damage, or buildup; verify proper orientation and alignment; check for blockage or paint over orifices; ensure DN-5 duct nozzles maintain HALAR coating integrity
- Area: Control Valve Assembly ConditionCheck: Check for external corrosion on valve body, actuators, and piping; verify bonnet bolts are tight; inspect manual reset actuator (MRA-1) for damage; ensure dry pilot actuators (DP-1/DP-2) have no water/air leakage at drain outlet
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Diaphragm Integrity and LeakageCheck: Inspect for water or air leakage from bonnet cover and outlet drain; verify no external moisture on diaphragm chamber; perform annual full trip test to verify diaphragm response and proper valve opening
- Area: Strainer and Filter BlockageCheck: Clean strainer in diaphragm chamber supply control valve; inspect for sediment, corrosion debris, or mineral deposits; perform internal inspection of strainers every 5 years per NFPA 25; replace if significant blockage detected
- Area: Pilot Line Pressure and Air SupplyCheck: Verify dry pilot line air pressure maintained at design pressure (typically 40-50 psi); check for air leaks at connections; ensure air drier functioning and dew point below lowest ambient temperature; test pressure gauge reading weekly
- Area: Nozzle and Sprinkler ConditionCheck: Inspect all deluge nozzles/sprinklers for corrosion, mechanical damage, or buildup; verify proper orientation and alignment; check for blockage or paint over orifices; ensure DN-5 duct nozzles maintain HALAR coating integrity
- Area: Control Valve Assembly ConditionCheck: Check for external corrosion on valve body, actuators, and piping; verify bonnet bolts are tight; inspect manual reset actuator (MRA-1) for damage; ensure dry pilot actuators (DP-1/DP-2) have no water/air leakage at drain outlet
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Diaphragm Integrity and LeakageCheck: Inspect for water or air leakage from bonnet cover and outlet drain; verify no external moisture on diaphragm chamber; perform annual full trip test to verify diaphragm response and proper valve opening
- Area: Strainer and Filter BlockageCheck: Clean strainer in diaphragm chamber supply control valve; inspect for sediment, corrosion debris, or mineral deposits; perform internal inspection of strainers every 5 years per NFPA 25; replace if significant blockage detected
- Area: Pilot Line Pressure and Air SupplyCheck: Verify dry pilot line air pressure maintained at design pressure (typically 40-50 psi); check for air leaks at connections; ensure air drier functioning and dew point below lowest ambient temperature; test pressure gauge reading weekly
- Area: Nozzle and Sprinkler ConditionCheck: Inspect all deluge nozzles/sprinklers for corrosion, mechanical damage, or buildup; verify proper orientation and alignment; check for blockage or paint over orifices; ensure DN-5 duct nozzles maintain HALAR coating integrity
- Area: Control Valve Assembly ConditionCheck: Check for external corrosion on valve body, actuators, and piping; verify bonnet bolts are tight; inspect manual reset actuator (MRA-1) for damage; ensure dry pilot actuators (DP-1/DP-2) have no water/air leakage at drain outlet
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Diaphragm Integrity and LeakageCheck: Inspect for water or air leakage from bonnet cover and outlet drain; verify no external moisture on diaphragm chamber; perform annual full trip test to verify diaphragm response and proper valve opening
- Area: Strainer and Filter BlockageCheck: Clean strainer in diaphragm chamber supply control valve; inspect for sediment, corrosion debris, or mineral deposits; perform internal inspection of strainers every 5 years per NFPA 25; replace if significant blockage detected
- Area: Pilot Line Pressure and Air SupplyCheck: Verify dry pilot line air pressure maintained at design pressure (typically 40-50 psi); check for air leaks at connections; ensure air drier functioning and dew point below lowest ambient temperature; test pressure gauge reading weekly
- Area: Nozzle and Sprinkler ConditionCheck: Inspect all deluge nozzles/sprinklers for corrosion, mechanical damage, or buildup; verify proper orientation and alignment; check for blockage or paint over orifices; ensure DN-5 duct nozzles maintain HALAR coating integrity
- Area: Control Valve Assembly ConditionCheck: Check for external corrosion on valve body, actuators, and piping; verify bonnet bolts are tight; inspect manual reset actuator (MRA-1) for damage; ensure dry pilot actuators (DP-1/DP-2) have no water/air leakage at drain outlet
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Diaphragm Integrity and LeakageCheck: Inspect for water or air leakage from bonnet cover and outlet drain; verify no external moisture on diaphragm chamber; perform annual full trip test to verify diaphragm response and proper valve opening
- Area: Strainer and Filter BlockageCheck: Clean strainer in diaphragm chamber supply control valve; inspect for sediment, corrosion debris, or mineral deposits; perform internal inspection of strainers every 5 years per NFPA 25; replace if significant blockage detected
- Area: Pilot Line Pressure and Air SupplyCheck: Verify dry pilot line air pressure maintained at design pressure (typically 40-50 psi); check for air leaks at connections; ensure air drier functioning and dew point below lowest ambient temperature; test pressure gauge reading weekly
- Area: Nozzle and Sprinkler ConditionCheck: Inspect all deluge nozzles/sprinklers for corrosion, mechanical damage, or buildup; verify proper orientation and alignment; check for blockage or paint over orifices; ensure DN-5 duct nozzles maintain HALAR coating integrity
- Area: Control Valve Assembly ConditionCheck: Check for external corrosion on valve body, actuators, and piping; verify bonnet bolts are tight; inspect manual reset actuator (MRA-1) for damage; ensure dry pilot actuators (DP-1/DP-2) have no water/air leakage at drain outlet
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Diaphragm Integrity and LeakageCheck: Inspect for water or air leakage from bonnet cover and outlet drain; verify no external moisture on diaphragm chamber; perform annual full trip test to verify diaphragm response and proper valve opening
- Area: Strainer and Filter BlockageCheck: Clean strainer in diaphragm chamber supply control valve; inspect for sediment, corrosion debris, or mineral deposits; perform internal inspection of strainers every 5 years per NFPA 25; replace if significant blockage detected
- Area: Pilot Line Pressure and Air SupplyCheck: Verify dry pilot line air pressure maintained at design pressure (typically 40-50 psi); check for air leaks at connections; ensure air drier functioning and dew point below lowest ambient temperature; test pressure gauge reading weekly
- Area: Nozzle and Sprinkler ConditionCheck: Inspect all deluge nozzles/sprinklers for corrosion, mechanical damage, or buildup; verify proper orientation and alignment; check for blockage or paint over orifices; ensure DN-5 duct nozzles maintain HALAR coating integrity
- Area: Control Valve Assembly ConditionCheck: Check for external corrosion on valve body, actuators, and piping; verify bonnet bolts are tight; inspect manual reset actuator (MRA-1) for damage; ensure dry pilot actuators (DP-1/DP-2) have no water/air leakage at drain outlet
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Diaphragm Integrity and LeakageCheck: Inspect for water or air leakage from bonnet cover and outlet drain; verify no external moisture on diaphragm chamber; perform annual full trip test to verify diaphragm response and proper valve opening
- Area: Strainer and Filter BlockageCheck: Clean strainer in diaphragm chamber supply control valve; inspect for sediment, corrosion debris, or mineral deposits; perform internal inspection of strainers every 5 years per NFPA 25; replace if significant blockage detected
- Area: Pilot Line Pressure and Air SupplyCheck: Verify dry pilot line air pressure maintained at design pressure (typically 40-50 psi); check for air leaks at connections; ensure air drier functioning and dew point below lowest ambient temperature; test pressure gauge reading weekly
- Area: Nozzle and Sprinkler ConditionCheck: Inspect all deluge nozzles/sprinklers for corrosion, mechanical damage, or buildup; verify proper orientation and alignment; check for blockage or paint over orifices; ensure DN-5 duct nozzles maintain HALAR coating integrity
- Area: Control Valve Assembly ConditionCheck: Check for external corrosion on valve body, actuators, and piping; verify bonnet bolts are tight; inspect manual reset actuator (MRA-1) for damage; ensure dry pilot actuators (DP-1/DP-2) have no water/air leakage at drain outlet
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Diaphragm Integrity and LeakageCheck: Inspect for water or air leakage from bonnet cover and outlet drain; verify no external moisture on diaphragm chamber; perform annual full trip test to verify diaphragm response and proper valve opening
- Area: Strainer and Filter BlockageCheck: Clean strainer in diaphragm chamber supply control valve; inspect for sediment, corrosion debris, or mineral deposits; perform internal inspection of strainers every 5 years per NFPA 25; replace if significant blockage detected
- Area: Pilot Line Pressure and Air SupplyCheck: Verify dry pilot line air pressure maintained at design pressure (typically 40-50 psi); check for air leaks at connections; ensure air drier functioning and dew point below lowest ambient temperature; test pressure gauge reading weekly
- Area: Nozzle and Sprinkler ConditionCheck: Inspect all deluge nozzles/sprinklers for corrosion, mechanical damage, or buildup; verify proper orientation and alignment; check for blockage or paint over orifices; ensure DN-5 duct nozzles maintain HALAR coating integrity
- Area: Control Valve Assembly ConditionCheck: Check for external corrosion on valve body, actuators, and piping; verify bonnet bolts are tight; inspect manual reset actuator (MRA-1) for damage; ensure dry pilot actuators (DP-1/DP-2) have no water/air leakage at drain outlet
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
Minimax
9 ✓ 9 verified- Area: Valve Actuation and System Response TimeCheck: Conduct annual full trip test of deluge valves; record time from detector activation to water discharge through all nozzles; verify compliance with maximum 3-year interval requirement for full trip tests
- Area: Pressure Gauge Calibration and System Pressure MaintenanceCheck: Visually inspect pressure gauges quarterly; verify water pressure at hydraulically remote sprinkler and deluge valve inlet; confirm jockey pump maintains correct pressure (9 bar for ProCon systems, 40-90 bar for ProCon XP)
- Area: Nozzle and Sprinkler Obstruction, Corrosion, and Physical DamageCheck: Visually inspect all open nozzles (Viking Model A, C-1, ProCon, Marine XP) for paint coverage, debris accumulation, corrosion, bent deflectors, or mechanical damage; remove random sample of sprinklers for laboratory endoscopic examination of pipe network deposits; assess residual wall thicknesses
- Area: Pipe System Internal Condition and DepositsCheck: Perform endoscopic examination of main pipe network for internal corrosion, mineral deposits, and rust; assess hydraulic impact and remaining pipe wall thickness; conduct main drain tests to verify control valve operation; inspect all trim valves in correct open/closed positions
- Area: Fire Detection System Integration and Signal IntegrityCheck: For systems with electric or pneumatic release (TraFoProtect with UniVario/FMZ 5000, PVProtect with heat detectors, EconAqua systems): verify all detector signal paths; test short circuit detection in monitoring circuits; confirm automatic activation signal transmission under simulated fire conditions; check for line interruptions or water supply status indicator function
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Valve Actuation and System Response TimeCheck: Conduct annual full trip test of deluge valves; record time from detector activation to water discharge through all nozzles; verify compliance with maximum 3-year interval requirement for full trip tests
- Area: Pressure Gauge Calibration and System Pressure MaintenanceCheck: Visually inspect pressure gauges quarterly; verify water pressure at hydraulically remote sprinkler and deluge valve inlet; confirm jockey pump maintains correct pressure (9 bar for ProCon systems, 40-90 bar for ProCon XP)
- Area: Nozzle and Sprinkler Obstruction, Corrosion, and Physical DamageCheck: Visually inspect all open nozzles (Viking Model A, C-1, ProCon, Marine XP) for paint coverage, debris accumulation, corrosion, bent deflectors, or mechanical damage; remove random sample of sprinklers for laboratory endoscopic examination of pipe network deposits; assess residual wall thicknesses
- Area: Pipe System Internal Condition and DepositsCheck: Perform endoscopic examination of main pipe network for internal corrosion, mineral deposits, and rust; assess hydraulic impact and remaining pipe wall thickness; conduct main drain tests to verify control valve operation; inspect all trim valves in correct open/closed positions
- Area: Fire Detection System Integration and Signal IntegrityCheck: For systems with electric or pneumatic release (TraFoProtect with UniVario/FMZ 5000, PVProtect with heat detectors, EconAqua systems): verify all detector signal paths; test short circuit detection in monitoring circuits; confirm automatic activation signal transmission under simulated fire conditions; check for line interruptions or water supply status indicator function
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Valve Actuation and System Response TimeCheck: Conduct annual full trip test of deluge valves; record time from detector activation to water discharge through all nozzles; verify compliance with maximum 3-year interval requirement for full trip tests
- Area: Pressure Gauge Calibration and System Pressure MaintenanceCheck: Visually inspect pressure gauges quarterly; verify water pressure at hydraulically remote sprinkler and deluge valve inlet; confirm jockey pump maintains correct pressure (9 bar for ProCon systems, 40-90 bar for ProCon XP)
- Area: Nozzle and Sprinkler Obstruction, Corrosion, and Physical DamageCheck: Visually inspect all open nozzles (Viking Model A, C-1, ProCon, Marine XP) for paint coverage, debris accumulation, corrosion, bent deflectors, or mechanical damage; remove random sample of sprinklers for laboratory endoscopic examination of pipe network deposits; assess residual wall thicknesses
- Area: Pipe System Internal Condition and DepositsCheck: Perform endoscopic examination of main pipe network for internal corrosion, mineral deposits, and rust; assess hydraulic impact and remaining pipe wall thickness; conduct main drain tests to verify control valve operation; inspect all trim valves in correct open/closed positions
- Area: Fire Detection System Integration and Signal IntegrityCheck: For systems with electric or pneumatic release (TraFoProtect with UniVario/FMZ 5000, PVProtect with heat detectors, EconAqua systems): verify all detector signal paths; test short circuit detection in monitoring circuits; confirm automatic activation signal transmission under simulated fire conditions; check for line interruptions or water supply status indicator function
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Valve Actuation and System Response TimeCheck: Conduct annual full trip test of deluge valves; record time from detector activation to water discharge through all nozzles; verify compliance with maximum 3-year interval requirement for full trip tests
- Area: Pressure Gauge Calibration and System Pressure MaintenanceCheck: Visually inspect pressure gauges quarterly; verify water pressure at hydraulically remote sprinkler and deluge valve inlet; confirm jockey pump maintains correct pressure (9 bar for ProCon systems, 40-90 bar for ProCon XP)
- Area: Nozzle and Sprinkler Obstruction, Corrosion, and Physical DamageCheck: Visually inspect all open nozzles (Viking Model A, C-1, ProCon, Marine XP) for paint coverage, debris accumulation, corrosion, bent deflectors, or mechanical damage; remove random sample of sprinklers for laboratory endoscopic examination of pipe network deposits; assess residual wall thicknesses
- Area: Pipe System Internal Condition and DepositsCheck: Perform endoscopic examination of main pipe network for internal corrosion, mineral deposits, and rust; assess hydraulic impact and remaining pipe wall thickness; conduct main drain tests to verify control valve operation; inspect all trim valves in correct open/closed positions
- Area: Fire Detection System Integration and Signal IntegrityCheck: For systems with electric or pneumatic release (TraFoProtect with UniVario/FMZ 5000, PVProtect with heat detectors, EconAqua systems): verify all detector signal paths; test short circuit detection in monitoring circuits; confirm automatic activation signal transmission under simulated fire conditions; check for line interruptions or water supply status indicator function
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Valve Actuation and System Response TimeCheck: Conduct annual full trip test of deluge valves; record time from detector activation to water discharge through all nozzles; verify compliance with maximum 3-year interval requirement for full trip tests
- Area: Pressure Gauge Calibration and System Pressure MaintenanceCheck: Visually inspect pressure gauges quarterly; verify water pressure at hydraulically remote sprinkler and deluge valve inlet; confirm jockey pump maintains correct pressure (9 bar for ProCon systems, 40-90 bar for ProCon XP)
- Area: Nozzle and Sprinkler Obstruction, Corrosion, and Physical DamageCheck: Visually inspect all open nozzles (Viking Model A, C-1, ProCon, Marine XP) for paint coverage, debris accumulation, corrosion, bent deflectors, or mechanical damage; remove random sample of sprinklers for laboratory endoscopic examination of pipe network deposits; assess residual wall thicknesses
- Area: Pipe System Internal Condition and DepositsCheck: Perform endoscopic examination of main pipe network for internal corrosion, mineral deposits, and rust; assess hydraulic impact and remaining pipe wall thickness; conduct main drain tests to verify control valve operation; inspect all trim valves in correct open/closed positions
- Area: Fire Detection System Integration and Signal IntegrityCheck: For systems with electric or pneumatic release (TraFoProtect with UniVario/FMZ 5000, PVProtect with heat detectors, EconAqua systems): verify all detector signal paths; test short circuit detection in monitoring circuits; confirm automatic activation signal transmission under simulated fire conditions; check for line interruptions or water supply status indicator function
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Valve Actuation and System Response TimeCheck: Conduct annual full trip test of deluge valves; record time from detector activation to water discharge through all nozzles; verify compliance with maximum 3-year interval requirement for full trip tests
- Area: Pressure Gauge Calibration and System Pressure MaintenanceCheck: Visually inspect pressure gauges quarterly; verify water pressure at hydraulically remote sprinkler and deluge valve inlet; confirm jockey pump maintains correct pressure (9 bar for ProCon systems, 40-90 bar for ProCon XP)
- Area: Nozzle and Sprinkler Obstruction, Corrosion, and Physical DamageCheck: Visually inspect all open nozzles (Viking Model A, C-1, ProCon, Marine XP) for paint coverage, debris accumulation, corrosion, bent deflectors, or mechanical damage; remove random sample of sprinklers for laboratory endoscopic examination of pipe network deposits; assess residual wall thicknesses
- Area: Pipe System Internal Condition and DepositsCheck: Perform endoscopic examination of main pipe network for internal corrosion, mineral deposits, and rust; assess hydraulic impact and remaining pipe wall thickness; conduct main drain tests to verify control valve operation; inspect all trim valves in correct open/closed positions
- Area: Fire Detection System Integration and Signal IntegrityCheck: For systems with electric or pneumatic release (TraFoProtect with UniVario/FMZ 5000, PVProtect with heat detectors, EconAqua systems): verify all detector signal paths; test short circuit detection in monitoring circuits; confirm automatic activation signal transmission under simulated fire conditions; check for line interruptions or water supply status indicator function
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Valve Actuation and System Response TimeCheck: Conduct annual full trip test of deluge valves; record time from detector activation to water discharge through all nozzles; verify compliance with maximum 3-year interval requirement for full trip tests
- Area: Pressure Gauge Calibration and System Pressure MaintenanceCheck: Visually inspect pressure gauges quarterly; verify water pressure at hydraulically remote sprinkler and deluge valve inlet; confirm jockey pump maintains correct pressure (9 bar for ProCon systems, 40-90 bar for ProCon XP)
- Area: Nozzle and Sprinkler Obstruction, Corrosion, and Physical DamageCheck: Visually inspect all open nozzles (Viking Model A, C-1, ProCon, Marine XP) for paint coverage, debris accumulation, corrosion, bent deflectors, or mechanical damage; remove random sample of sprinklers for laboratory endoscopic examination of pipe network deposits; assess residual wall thicknesses
- Area: Pipe System Internal Condition and DepositsCheck: Perform endoscopic examination of main pipe network for internal corrosion, mineral deposits, and rust; assess hydraulic impact and remaining pipe wall thickness; conduct main drain tests to verify control valve operation; inspect all trim valves in correct open/closed positions
- Area: Fire Detection System Integration and Signal IntegrityCheck: For systems with electric or pneumatic release (TraFoProtect with UniVario/FMZ 5000, PVProtect with heat detectors, EconAqua systems): verify all detector signal paths; test short circuit detection in monitoring circuits; confirm automatic activation signal transmission under simulated fire conditions; check for line interruptions or water supply status indicator function
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Valve Actuation and System Response TimeCheck: Conduct annual full trip test of deluge valves; record time from detector activation to water discharge through all nozzles; verify compliance with maximum 3-year interval requirement for full trip tests
- Area: Pressure Gauge Calibration and System Pressure MaintenanceCheck: Visually inspect pressure gauges quarterly; verify water pressure at hydraulically remote sprinkler and deluge valve inlet; confirm jockey pump maintains correct pressure (9 bar for ProCon systems, 40-90 bar for ProCon XP)
- Area: Nozzle and Sprinkler Obstruction, Corrosion, and Physical DamageCheck: Visually inspect all open nozzles (Viking Model A, C-1, ProCon, Marine XP) for paint coverage, debris accumulation, corrosion, bent deflectors, or mechanical damage; remove random sample of sprinklers for laboratory endoscopic examination of pipe network deposits; assess residual wall thicknesses
- Area: Pipe System Internal Condition and DepositsCheck: Perform endoscopic examination of main pipe network for internal corrosion, mineral deposits, and rust; assess hydraulic impact and remaining pipe wall thickness; conduct main drain tests to verify control valve operation; inspect all trim valves in correct open/closed positions
- Area: Fire Detection System Integration and Signal IntegrityCheck: For systems with electric or pneumatic release (TraFoProtect with UniVario/FMZ 5000, PVProtect with heat detectors, EconAqua systems): verify all detector signal paths; test short circuit detection in monitoring circuits; confirm automatic activation signal transmission under simulated fire conditions; check for line interruptions or water supply status indicator function
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Valve Actuation and System Response TimeCheck: Conduct annual full trip test of deluge valves; record time from detector activation to water discharge through all nozzles; verify compliance with maximum 3-year interval requirement for full trip tests
- Area: Pressure Gauge Calibration and System Pressure MaintenanceCheck: Visually inspect pressure gauges quarterly; verify water pressure at hydraulically remote sprinkler and deluge valve inlet; confirm jockey pump maintains correct pressure (9 bar for ProCon systems, 40-90 bar for ProCon XP)
- Area: Nozzle and Sprinkler Obstruction, Corrosion, and Physical DamageCheck: Visually inspect all open nozzles (Viking Model A, C-1, ProCon, Marine XP) for paint coverage, debris accumulation, corrosion, bent deflectors, or mechanical damage; remove random sample of sprinklers for laboratory endoscopic examination of pipe network deposits; assess residual wall thicknesses
- Area: Pipe System Internal Condition and DepositsCheck: Perform endoscopic examination of main pipe network for internal corrosion, mineral deposits, and rust; assess hydraulic impact and remaining pipe wall thickness; conduct main drain tests to verify control valve operation; inspect all trim valves in correct open/closed positions
- Area: Fire Detection System Integration and Signal IntegrityCheck: For systems with electric or pneumatic release (TraFoProtect with UniVario/FMZ 5000, PVProtect with heat detectors, EconAqua systems): verify all detector signal paths; test short circuit detection in monitoring circuits; confirm automatic activation signal transmission under simulated fire conditions; check for line interruptions or water supply status indicator function
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
Tyco / Johnson Controls
10NAFFCO Marine
9