Library Safety & LSA Fixed Fire Suppression Deluge/Sprinkler System
Fixed Fire Suppression

Deluge/Sprinkler System

A deluge or sprinkler system floods a protected space with water through open or heat-activated nozzles, deluge systems dousing an entire area at once on manual or automatic release, sprinklers responding zone by zone as individual heads activate.

79models 13manufacturers
Models

Models in this type.

The 79 models with the most complete data of 79 in Deluge/Sprinkler System. Every row links to full specifications, documents and service notes.

TycoDP-1 Dry Pilot Actuator TycoDP-2 Dry Pilot Actuator TycoDPV-1 Preaction Type B Valve TycoDV-5 Deluge Valve TycoDV-5A Automatic Water Control Valve TycoDV-5A Deluge Red-E Cabinet TycoDV-5A Pre-trim Preaction Valve TycoDV-5A Preaction Red-E Cabinet TycoDuct Deluge System (DDS) TycoFTR-1 Fixed Temperature Release TycoMC-1 Manual Control Station TycoMRA-1 Manual Reset Actuator TycoModel B-1 Foam-Water Sprinklers TycoSeries MJC Multiple Jet Controls TycoSolenoid Valve TycoTN-17 Horizontal Spray Nozzle TycoTN-25 Horizontal Spray Nozzle TycoType D3 Protectospray Directional Spray Nozzles TycoType DN-5 Corrosion Resistant Duct Nozzle Tyco / Johnson ControlsDeluge DV-5 Tyco / Johnson ControlsDeluge DV-5S Tyco / Johnson ControlsSprinkler SW-12 Tyco / Johnson ControlsSprinkler SW-20 Tyco / Johnson ControlsTyco Sprinkler Accommodation-B Tyco / Johnson ControlsTyco Sprinkler Car Deck-B Tyco / Johnson ControlsTyco Sprinkler Helideck-B Tyco / Johnson ControlsTyco Sprinkler Machinery-B Tyco / Johnson ControlsTyco Sprinkler RoRo Space-B Tyco / Johnson ControlsTyco Sprinkler Storage-B MinimaxDeluge Systems (General) MinimaxMXOne (Firefighting Turbine) MinimaxMinifog EconAqua MinimaxMinifog Marine XP MinimaxMinifog ProCon MinimaxMinifog ProCon XP MinimaxPVProtect (Solar Panel Protection System) MinimaxSprinkler Systems (Undercover) MinimaxTraFoProtect (Transformer Protection System) NAFFCO MarineDeluge Marine NAFFCO MarineSprinkler Accommodation-B NAFFCO MarineSprinkler Car Deck-B NAFFCO MarineSprinkler Helideck-B NAFFCO MarineSprinkler Machinery-B NAFFCO MarineSprinkler RoRo Space-B NAFFCO MarineSprinkler Storage-B NAFFCO MarinePre-Action Marine NAFFCO MarineSprinkler Marine Viking Group (Fire)VK Marine Deluge Viking Group (Fire)VK Marine Pre-Action Viking Group (Fire)VK Marine Sprinkler Viking Group (Fire)Sprinkler Accommodation-B Viking Group (Fire)Sprinkler Car Deck-B Viking Group (Fire)Sprinkler Helideck-B Viking Group (Fire)Sprinkler Machinery-B Viking Group (Fire)Sprinkler RoRo Space-B Viking Group (Fire)Sprinkler Storage-B Minimax MarineMX Deluge Minimax MarineMX Sprinkler Minimax MarineSprinkler Accommodation-B Minimax MarineSprinkler Car Deck-B Minimax MarineSprinkler Helideck-B Minimax MarineSprinkler Machinery-B Minimax MarineSprinkler RoRo Space-B Minimax MarineSprinkler Storage-B ULTRAFOG S.p.A.Ultra Fog Accommodation Sprinkler System ULTRAFOG S.p.A.Ultra Fog Balcony Sprinkler System ULTRAFOG S.p.A.Ultra Fog High Pressure Water Mist System, Volume 3348 m3 ULTRAFOG S.p.A.Ultra Fog High Pressure Water Mist System, Volume 500 m3 ULTRAFOG S.p.A.Ultra Fog Ro-Ro Sprinkler System Marioff Corporation OyMarioff Hi-Fog 2000 water mist system. Marioff Corporation OyMarioff Hi-Fog 3000 water mist system. Marioff Corporation OyMarioff Hi-Fog 3000 water mist systems for ro-ro spaces and special category spaces. Marioff Corporation OyMarioff Hi-Fog water mist systems for ro-ro spaces and special category spaces. ULTRAFOG S.r.l.Ultra Fog Accommodation Sprinklers ULTRAFOG S.r.l.Ultra Fog High Pressure Water Mist System, Volume 3815 m3 Danfoss Fire Safety A/SSEM-SAFE High Pressure Water Mist System for Total flooding application Minimax Technologies GmbHDry Sprinkler VK Ningbo Yonghang Fire Equipment Co., Ltd.Sprinkler system Vid Fire-Kill ApSK7-Kattegat low pressure water mist system
By manufacturer

Manufacturers.

All 13 manufacturers with models of Deluge/Sprinkler System. Every name opens a search across the full library.

Related types

Also in Fixed Fire Suppression.

The other equipment types in this category.

CO2 Fire SuppressionCO2 Fixed Fire SystemClean Agent SystemDry Chemical SystemFM-200/Novec SystemFixed Gas Extinguishing SystemFoam Fire SuppressionFoam Fire SystemWater Mist SystemWater Mist System (Hi-Fog)
Knowledge

What to check on a Deluge/Sprinkler System.

Both systems distribute water through overhead piping and nozzles, but they release differently. A sprinkler system uses heat-sensitive heads that open individually as the temperature around them rises, so only the heads actually over the fire discharge, limiting water damage to the affected zone. A deluge system uses open nozzles on every branch of the protected section, held dry until a detection system or manual pull station opens a common deluge valve, flooding the whole section at once. Sprinklers suit accommodation and machinery spaces where a slow-developing fire is expected…

What Sets Deluge and Sprinkler Apart

Both systems distribute water through overhead piping and nozzles, but they release differently. A sprinkler system uses heat-sensitive heads that open individually as the temperature around them rises, so only the heads actually over the fire discharge, limiting water damage to the affected zone. A deluge system uses open nozzles on every branch of the protected section, held dry until a detection system or manual pull station opens a common deluge valve, flooding the whole section at once. Sprinklers suit accommodation and machinery spaces where a slow-developing fire is expected; deluge suits fast-flashover risks such as a paint locker or a helicopter deck fuel spill, where waiting for individual heads to react would be too slow.

Deluge / sprinkler system schematic
Flow schematic from the fire main through the deluge valve to open nozzles flooding a protected area, with the heat detection line and manual release station shown.

Main Components

Detection and Release

Automatic sprinkler heads detect and release themselves; deluge systems instead rely on a separate fire detection loop or manual pull stations to open the deluge valve for the whole section.

Deluge/Alarm Valve

The key control element on a deluge system, normally held shut against system pressure until a detection signal or manual release opens it, admitting water to all open nozzles downstream simultaneously.

Pressure Tank and Pump

Sprinkler systems keep the piping pressurized from a dedicated tank for instant discharge on the first head opening, backed by an automatic pump that starts on falling pressure to sustain flow.

Section Isolation Valves

Divide the ship into zones so one section can be tested, drained or isolated for maintenance without disabling protection elsewhere.

Selection and Sizing

  • Water density (litres per minute per square metre) required for the specific space, set by the applicable fire safety rules
  • Pump capacity sized for the largest single section likely to discharge at once, not the whole system total
  • Head or nozzle spacing matched to ceiling height and obstruction layout
  • Response time requirement, faster for deluge-protected high-risk spaces than for general sprinkler zones

Regulations and Class

SOLAS Ch. II-2 and the FSS Code set water application rates, coverage and pump capacity requirements for both sprinkler systems in accommodation spaces and deluge systems in high-risk areas. Passenger ships and many cargo ship types must fit an automatic sprinkler system in accommodation under SOLAS regulation II-2/10, and helicopter decks commonly require deluge protection as a specific carriage requirement.

Typical Faults

FaultConsequence
Deluge valve diaphragm perished or stuckValve fails to open on release signal, or opens without command, causing a false flood
Sprinkler pressure tank low on air chargeDelayed or reduced initial discharge before the pump takes over
Section isolation valve left shut after maintenanceAn entire zone silently loses protection with no visible alarm indication
Sprinkler heads painted over during accommodation refurbishmentHeads fail to activate at the design temperature

What to Look for in a Supplier

  • Application rate and pump duty calculations matched to the specific protected spaces, backed by class-approved drawings
  • Valve and head components compatible with existing zone wiring and detection loop, if retrofitting
  • Clear zone isolation labelling and testing procedures supplied with the system, not left to the yard

After any accommodation repaint, check every sprinkler head by hand for overspray - a painted-over head looks fine on inspection but will not activate at the fire's design temperature.

Search by manufacturer AFRISOWISKASwagelokAlfa Laval S.p.A.MAN Energy SolutionsSEIMIWärtsiläEndress+HauserABB MarineAlfa LavalMacGregorNovenco MarineCarrier MarineSiemens MarineHeinen & Hopman
Would you like to know more?

One request. A person answers within 24 hours on working days.

Tell us the manufacturer, the model and what you need — a part, a service call, a second opinion. Our desk asks the right suppliers from a network of over 114,000 companies and comes back with a quote or a sourcing plan, not a search page.

Frequently asked

Three things people ask first.

Is Deluge/Sprinkler System data free?

Yes. Every model page, every guide and every datasheet for this type is readable without an account. An account adds saved searches and requests, nothing is taken away.

My model is missing — what now?

Send us the nameplate. We identify it by hand, add it to the library, and if you need a part or a service, the request is already on our desk.

Can you source a Deluge/Sprinkler System part?

Yes. Tell us the manufacturer, the model and what you need — our desk asks the right suppliers from a network of over 114,000 companies and comes back with a quote or a sourcing plan.