"> Foam Fire Suppression - Equipment Database

Foam Fire Suppression

medium 5 models total

Fixed foam systems flood a compartment or blanket a deck with AFFF or protein foam concentrate mixed with water, smothering a flammable-liquid fire by cutting off the oxygen the flame needs rather than cooling it the way water alone does.

Read more — Foam Fire Suppression explained

What sets foam apart from CO2 and water mist

Foam earns its place specifically on flammable and combustible liquid fires — engine room bilges, cargo pump rooms on tankers, and helicopter decks — where a CO2 flood risks reflash once the gas disperses and plain water can spread a burning liquid rather than extinguish it. Foam works by forming a blanket over the liquid surface that separates fuel from air and, with aqueous film-forming foam (AFFF), also lays down a thin film of water under the foam that continues sealing the surface even if the foam blanket is disturbed. That reflash resistance is why foam remains the standard for tanker deck protection even where other fixed systems have been adopted elsewhere on the same ship.

Fixed foam fire suppression system
Flow scheme of a fixed foam system: fire main water and foam concentrate meet at the proportioner, the foam solution passes an isolation valve to a discharge outlet, and the resulting foam blanket smothers the protected space.

Main components

Foam concentrate tank

Stores the concentrate, typically 1%, 3% or 6% proportioning depending on the product, that gets mixed with seawater or fresh water at the point of application — concentrate does not work neat and has a shelf life that needs checking, not assuming.

Proportioner

Meters concentrate into the water stream at the correct ratio, either by a fixed orifice (balanced pressure) or an in-line eductor. Getting the ratio wrong in either direction produces a foam that either will not form a stable blanket or wastes concentrate without added benefit.

Foam monitors and pourers

Deck monitors on tankers throw foam at range onto the cargo deck or a specific tank fire; foam pourers on helidecks deliver foam locally and fast, since a helideck fire has to be knocked down within the response time built into the helideck's own approval.

Distribution piping and pump

A dedicated foam pump or the fire main, pressurised to the system's design pressure, delivers water to the proportioner and on to the monitors or pourers — foam system performance is only as good as the fire pump behind it.

Selection and sizing

  • Foam type matched to the cargo or fuel risk — AFFF for hydrocarbon fires, alcohol-resistant foam (AR-AFFF) where polar solvent cargoes are carried, since ordinary AFFF breaks down against alcohols and ketones
  • Application rate and duration required by the applicable code for the protected area, deck area, pump room volume, helideck size
  • Proportioning ratio matched to the concentrate product — mixing concentrate brands or ratios without re-calibrating the proportioner is a common yard error
  • Monitor throw range versus deck length, to confirm full coverage without dead zones between monitor positions

Regulations and class

Fixed foam fire-fighting systems for cargo deck protection on tankers are required under SOLAS Ch. II-2 Reg. 10 and detailed in the FSS Code, which sets minimum application rates, foam solution supply duration and monitor coverage. Helideck foam provision follows IMO MSC circulars on helicopter facilities in addition to the flag state's aviation authority requirements where applicable. Class surveys check concentrate quantity and condition, proportioner calibration and monitor function as part of the periodic fire safety survey, and concentrate that has degraded past its shelf life is a common survey finding rather than a rare one.

Typical faults

FaultConsequence
Foam concentrate past shelf life or improperly storedDegraded foam quality, blanket collapses faster than design duration
Proportioner miscalibrated for the concentrate in useWrong mix ratio, ineffective or wasted foam application
Standard AFFF used against a polar solvent cargo fireFoam blanket breaks down rapidly, fire re-ignites
Monitor or pourer nozzle blocked or corroded shutNo or reduced foam delivery exactly when the system is called on

What to look for in a supplier

  • Concentrate compatible with the specific cargoes or fuels the ship carries, including AR-AFFF where polar solvents are in the cargo list
  • Concentrate batch testing or a documented shelf-life and storage temperature range
  • Proportioner calibration service matched to the concentrate actually supplied
  • Monitor and pourer spares availability, since these are the parts most exposed to weather and corrosion on deck

Check the concentrate, not just the pump — a foam system that pressure-tests perfectly on water alone can still fail on the day if the concentrate in the tank has quietly gone past useful life.

5 manufacturers · 5 models

Dr. Sthamer

1
Dr. Sthamer Marine AFFF System
variable · Fire Suppression / Detection · Fixed AFFF fire suppression system
Agent
foam_afff
Solas
ja
Origin
Germany
Common Failures & Inspection Points
  • Loss of extinguishing medium, pressure or water supply reduces available firefighting capacity
  • Valve, hose, nozzle, release or pump faults prevent correct discharge
  • Corrosion, seal deterioration or mechanical damage causes leakage or unreliable operation
  • Detection, alarm, fan-stop or shutdown interlock faults create an incomplete or unsafe release sequence
  • Blocked nozzles, hoses or distribution piping reduce delivery to the fire area
Service: Inspect storage or pumps, valves, hoses, nozzles, piping, release controls, alarms and shutdown interfaces according to the system type. Verify accessibility, seals, markings and protected-space arrangements. Functional tests must follow the approved safety procedure without unintended discharge. Refer to manufacturer, class and statutory documentation for the exact figure for pressure, quantity and acceptance criteria.
Spare Parts: Carry approved valves, seals, hoses, nozzles, release components, pump service parts, alarms, fuses and manufacturer-supported extinguisher or system service items.
Strengths
  • SOLAS‑approved for mandatory maritime fire protection
  • German design heritage with over a century of foam expertise
  • PFAS‑free foam concentrate options available
  • Integrated proportioner provides automatic dosing
  • Robust tank construction suited to marine environments
Weaknesses
  • Foam concentrate can degrade if storage conditions are poor
  • Proportioner may drift and require periodic recalibration
  • Metal tanks are prone to corrosion in high‑humidity service
  • System complexity increases maintenance workload
Typical Vessels: Oil TankerChemical TankerBulk CarrierContainer ShipOffshore Supply Vessel
Certifications: SOLAS
Decision Guide: Choose if you need a SOLAS‑compliant fixed AFFF system with proven German engineering and the option of PFAS‑free foam. Avoid if your operation cannot support regular proportioner calibration or prefers a low‑maintenance, corrosion‑resistant solution.
Use Cases: Portable and fixed firefighting on machinery, cargo, accommodation and deck areas.

Kidde

1
Kidde Foam Fixed Suppression System unverified
Equipment Type
foam_fixed
Solas type
SOLAS
Common Failures & Inspection Points
  • Loss of extinguishing-agent inventory or pressure caused by leakage or poor maintenance, resulting in low-level or low-pressure indication and reduced system readiness
  • Nozzle, pipe or distribution blockage caused by corrosion, paint, deposits or mechanical damage, resulting in restricted discharge
  • Release-valve or actuator failure caused by corrosion, sticking or control faults, resulting in inability to discharge the system when commanded
  • Detection, interlock or alarm failure caused by wiring, sensor or control-panel faults, resulting in missing alarms or inhibited release sequence
  • Pump, cylinder or pressure-regulating equipment deterioration caused by wear, corrosion or electrical faults, resulting in inadequate discharge performance
Service: Inspect agent storage, pumps or cylinders, release controls, section valves, nozzles, piping and alarms in accordance with the approved maintenance plan. Keep nozzles and discharge openings clear of paint, cargo or modifications. Function-test release circuits and interlocks using the authorized non-discharge test method. Check cylinder or tank condition, pressure indication and securing arrangements and record any isolated section. Verify protected-space shutdowns and alarms where required by the approved design. Refer to the manufacturer documentation for the exact figure for test intervals, charge quantities, pressures and acceptance criteria.
Spare Parts: Keep approved valve service kits, nozzles, seals, actuators, detection or release components, fuses and manufacturer-recommended pump or pressure-regulating parts. Extinguishing agent and cylinder components must remain compatible with the certified system. Major pressure vessels or pumps are normally strategic spares.
Use Cases: Fixed fire protection for machinery spaces, cargo areas, accommodation or deck hazards on merchant ships, passenger vessels and offshore units.
AFFF foam fixed system

National Foam

1
National Foam Marine AFFF
variable · Fire Suppression / Detection · Fixed AFFF foam suppression
Agent
foam_afff
Solas
ja
Common Failures & Inspection Points
  • Loss of extinguishing medium, pressure or water supply reduces available firefighting capacity
  • Valve, hose, nozzle, release or pump faults prevent correct discharge
  • Corrosion, seal deterioration or mechanical damage causes leakage or unreliable operation
  • Detection, alarm, fan-stop or shutdown interlock faults create an incomplete or unsafe release sequence
  • Blocked nozzles, hoses or distribution piping reduce delivery to the fire area
Service: Inspect storage or pumps, valves, hoses, nozzles, piping, release controls, alarms and shutdown interfaces according to the system type. Verify accessibility, seals, markings and protected-space arrangements. Functional tests must follow the approved safety procedure without unintended discharge. Refer to manufacturer, class and statutory documentation for the exact figure for pressure, quantity and acceptance criteria.
Spare Parts: Carry approved valves, seals, hoses, nozzles, release components, pump service parts, alarms, fuses and manufacturer-supported extinguisher or system service items.
Strengths
  • Proven rapid knock‑down of fuel‑oil fires
  • Meets SOLAS fire‑extinguishing standards for oil‑carrying vessels
  • Low water usage compared with CO₂ or water mist systems
  • Can be integrated into existing fixed piping networks
  • Simple manual activation in emergencies
Weaknesses
  • Foam concentrate degrades over time, requiring strict age control
  • Proportioning valve failures can lead to incorrect foam‑to‑water ratios
  • Steel distribution pipes are prone to corrosion if not stainless or protected
  • Contains PFAS chemicals that face increasing regulatory restrictions
  • Annual foam‑quality testing and regular maintenance increase operational cost
Typical Vessels: Oil TankerChemical TankerBulk Carrier (fuel‑oil bunkering areas)Offshore Supply VesselPassenger Ferry (engine room protection)
Decision Guide: Choose if: the vessel transports or stores flammable liquids, SOLAS compliance with AFFF is required, and rapid fire knock‑down is a priority. Avoid if: PFAS‑related environmental regulations are strict, low‑maintenance systems are preferred, or the vessel operates in jurisdictions limiting AFFF use.
Use Cases: Portable and fixed firefighting on machinery, cargo, accommodation and deck areas.

Solberg

1
Solberg Marine Re-Healing Foam
variable · Fire Suppression / Detection · re‑healing foam system
Agent
foam
Solas
ja
Pfas free
ja
Common Failures & Inspection Points
  • Loss of extinguishing medium, pressure or water supply reduces available firefighting capacity
  • Valve, hose, nozzle, release or pump faults prevent correct discharge
  • Corrosion, seal deterioration or mechanical damage causes leakage or unreliable operation
  • Detection, alarm, fan-stop or shutdown interlock faults create an incomplete or unsafe release sequence
  • Blocked nozzles, hoses or distribution piping reduce delivery to the fire area
Service: Inspect storage or pumps, valves, hoses, nozzles, piping, release controls, alarms and shutdown interfaces according to the system type. Verify accessibility, seals, markings and protected-space arrangements. Functional tests must follow the approved safety procedure without unintended discharge. Refer to manufacturer, class and statutory documentation for the exact figure for pressure, quantity and acceptance criteria.
Spare Parts: Carry approved valves, seals, hoses, nozzles, release components, pump service parts, alarms, fuses and manufacturer-supported extinguisher or system service items.
Strengths
  • PFAS‑free formulation meets increasing environmental regulations
  • Re‑healing nozzle design self‑seals after activation, reducing post‑fire repair time
  • SOLAS‑approved for marine use on a wide range of vessel classes
  • Fast knock‑down capability on flammable liquid fires typical of tankers and bulk carriers
Weaknesses
  • Foam concentrate has a limited shelf life requiring regular replacement checks
  • Proportioner units have documented failure modes that demand frequent testing
  • Nozzle blockage can occur if the system is not kept clean or if water ingress happens
  • Higher maintenance interval compared with dry‑chemical systems
Typical Vessels: Oil tankerChemical tankerBulk carrierContainer shipPassenger ferry
Certifications: SOLAS
Decision Guide: Choose if: you need a marine‑approved foam system that complies with PFAS bans, operate vessels carrying flammable liquids, and value rapid post‑fire resealing. Avoid if: you cannot commit to the required concentrate replacement schedule or have limited maintenance resources for proportioner testing.
Use Cases: Portable and fixed firefighting on machinery, cargo, accommodation and deck areas.

VIKING Life-Saving

1
Viking TwinAgent Foam System
TwinAgent Foam System
variable · Fire Suppression / Detection · Fixed AFFF foam suppression
Agent
foam_afff
Type
fixed
Solas
ja
Common Failures & Inspection Points
  • Loss of extinguishing medium, pressure or water supply reduces available firefighting capacity
  • Valve, hose, nozzle, release or pump faults prevent correct discharge
  • Corrosion, seal deterioration or mechanical damage causes leakage or unreliable operation
  • Detection, alarm, fan-stop or shutdown interlock faults create an incomplete or unsafe release sequence
  • Blocked nozzles, hoses or distribution piping reduce delivery to the fire area
Service: Inspect storage or pumps, valves, hoses, nozzles, piping, release controls, alarms and shutdown interfaces according to the system type. Verify accessibility, seals, markings and protected-space arrangements. Functional tests must follow the approved safety procedure without unintended discharge. Refer to manufacturer, class and statutory documentation for the exact figure for pressure, quantity and acceptance criteria.
Spare Parts: Carry approved valves, seals, hoses, nozzles, release components, pump service parts, alarms, fuses and manufacturer-supported extinguisher or system service items.
Strengths
  • SOLAS‑compliant fixed system for mandatory safety standards
  • Integrated proportioner with annual test capability simplifies verification
  • Foam concentrate service interval of 10–15 years reduces long‑term consumable costs
  • Twin‑agent design minimizes pipe runs and provides quick discharge coverage
  • Viking brand reputation for reliability in marine fire protection
Weaknesses
  • Foam concentrate can degrade over time, requiring scheduled replacement
  • Proportioner malfunctions have been reported, necessitating regular testing
  • Pump seal failures and foam‑maker blockages can occur if maintenance is lax
  • Fixed installation lacks the flexibility of portable extinguishers for evolving fire scenarios
  • Annual proportioner test adds to routine maintenance workload
Typical Vessels: TankersBulk carriersContainer shipsRo‑Ro vesselsOffshore supply vessels
Certifications: SOLAS
Decision Guide: Choose if: you need a SOLAS‑approved, permanently installed foam system for machinery spaces with long concentrate service intervals and you can commit to annual proportioner testing. Avoid if: the vessel relies heavily on flexible, portable fire‑extinguishing solutions or cannot accommodate the regular maintenance schedule required for proportioners and pump seals.
Use Cases: Portable and fixed firefighting on machinery, cargo, accommodation and deck areas.