Foam Fire System
A fixed foam system smothers flammable-liquid fires by starving them of oxygen under an expanding foam blanket, rather than cooling them the way water does, which is why it is the standard defence for cargo pump rooms, machinery space bilges and helidecks rather than accommodation.
Read more — Foam Fire System explained ▾
What sets a foam system apart from other fixed suppression
Water and water mist fight fire mainly by cooling; CO2 fights fire by displacing oxygen from an enclosed space and cannot be used where people might be present. Foam does something different again: it forms a blanket of bubbles over a burning or spilled flammable liquid, cutting off the oxygen supply at the surface and suppressing vapour release, which makes it the preferred system wherever oil, fuel or other liquid hydrocarbons are the main fire risk, cargo pump rooms on tankers, engine room bilges and fuel-handling areas, and helidecks where aviation fuel spills are the design case. It is generally unsuitable for fires deep in solid combustibles or in energised electrical equipment, where CO2 or water mist do a better job.
Main components
Foam concentrate tank
Stores the concentrate, commonly a synthetic or protein-based foam, or an aqueous film-forming foam (AFFF), which is proportioned into the water stream rather than used neat.
Proportioning system
A fixed ratio or balanced-pressure proportioner meters concentrate into the firemain flow, typically at 1-6% concentration depending on the foam type, to produce the correct foam solution.
Foam generators or monitors
Fixed foam monitors on deck or helidecks, or foam generators (branch pipes with an air-aspirating nozzle) in machinery spaces, expand the solution into finished foam at the point of application.
Distribution piping and valves
Dedicated piping runs from the proportioning system to each protected space or deck monitor, with remote-operated valves allowing activation from outside the space itself, essential where the fire may have already made the space inaccessible.
Selection and sizing
- Foam type matched to the fuel risk; AFFF performs well on hydrocarbon spills, but its environmental persistence has pushed many operators toward fluorine-free alternatives.
- Application rate and concentrate quantity sized to cover the largest single protected area for the required discharge duration, not an average across all spaces.
- Helideck systems sized specifically to IMO and offshore-industry helideck firefighting standards rather than generic machinery space rules.
- Compatibility of the foam concentrate with the firemain's seawater supply, since some formulations degrade with saltwater dilution.
Regulations and class
SOLAS Chapter II-2 sets fixed fire-fighting system requirements for machinery spaces and cargo pump rooms on tankers, with specific regulations covering fixed foam systems as an alternative or addition to fixed gas systems. The IMO Fire Safety Systems (FSS) Code, Chapter 6, sets detailed performance requirements for fixed foam extinguishing systems, including discharge rate and duration. Helideck foam provision follows IMO helicopter facility guidance alongside class notation requirements where applicable. Class surveys the system periodically, and foam concentrate itself is shelf-life limited and must be sampled or replaced within the manufacturer's stated interval.
Typical faults
| Fault | Cause | Consequence |
|---|---|---|
| Foam concentrate degraded | Storage past shelf life or contamination | System discharges but foam blanket fails to form correctly |
| Incorrect proportioning ratio | Proportioner valve fouled or maladjusted | Weak foam solution, reduced suppression effectiveness |
| Blocked foam generator screen | Debris or corrosion in piping | Reduced or no foam expansion at the point of application |
| Remote valve fails to operate | Actuator corrosion from a rarely-tested system | System cannot be activated from outside the affected space |
What to look for in a supplier
- Foam concentrate with a documented shelf life and a testing regime the crew can actually perform on board.
- Clear guidance on fluorine-free foam options given tightening environmental restrictions on AFFF in several jurisdictions.
- Availability of concentrate replenishment in the vessel's normal trading ports, since a discharged or degraded system with no local resupply leaves a real gap in fire protection.
Sample and test foam concentrate at the manufacturer's stated interval rather than assuming an unopened tank stays good indefinitely; degraded concentrate is invisible until the one time the system is actually needed, and by then it is too late to find out.
10 manufacturers · 120 models
Skum/Tyco
36 ✓ 36 verified- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Proportioner foam ratio accuracy deviation beyond tolerance (target: 0 to +30% or +1 percentage point maximum)Check: Annual foam solution sampling and laboratory ratio analysis; proportioner functional test at maximum and minimum design flow rates per EN 13565-1
- Area: Bladder tank integrity compromise (pressure loss, corrosion, elastomer degradation)Check: Visual inspection of tank exterior for rust, corrosion, or damage; pressure test of tank shell at 1.5x design pressure; bladder elastomer condition assessment; check relief valve operation
- Area: Foam concentrate deterioration, sludging, or chemical stratification in storageCheck: Annual tank inspection for sludge accumulation; foam concentrate sampling and laboratory quality testing; check for separation or discoloration; verify storage temperature maintained within -2 to +60°C limits
- Area: Monitor nozzle blockage or fouling preventing proper fog/jet pattern adjustmentCheck: Manual nozzle actuation test through full fog-to-jet range; visual inspection of nozzle orifice for debris or crystallization; flush test with clean water; verify elevation and rotation movement smoothness
- Area: System piping corrosion or blockage reducing flow and pressure deliveryCheck: Hydrostatic pressure test of main and branch piping at 1.5x operating pressure; measure water pressure at proportioner inlet, monitor connection, and deluge valve; flush entire piping system annually; inspect for rust or mineral deposits
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
Survitec
25 ✓ 16 verified
- Area: Foam Concentrate Content & Condition - Verify correct foam concentrate level, check for sludging, separation, or chemical deterioration indicating degradation oCheck: Visual inspection of foam tank/container appearance, density measurement, pH testing, microscopic examination for sludge/particulates per IMO MSC.1/Circ.1312 standards
- Area: System Pressure & Safety Valve Function - Verify pressurization levels meet specification and safety relief valves open/close at correct setpoints without leakaCheck: Pressure gauge reading verification, manual safety valve actuation test, hydrostatic test of all pressure vessels per ASME standards, pressure relief accuracy testing
- Area: Foam Proportioning & Discharge Accuracy - Confirm proportioner delivers correct mixing ratio (1%, 3%, 6% per system design) without variation exceeding tolerancCheck: Annual proportioner flow test with calibrated mixing verification, foam generation test at actual discharge nozzles, comparison against baseline performance data
- Area: Hose, Fittings & Connection Integrity - Inspect all foam supply hoses, quick-couplings, BSP threads, and flexible lines for leaks, corrosion, kinking, wear, orCheck: Visual examination under pressure (dry and wet tests), hydrostatic pressure testing of hoses per EN 854-1SC or equivalent, coupling engagement/disengagement cycle testing
- Area: Nozzle & Foam Generator Discharge Quality - Verify nozzles produce specified foam pattern (small droplets vs. jets), foam stack height testing, expansion ratioCheck: Visual pattern observation during discharge test, foam stack height measurement (minimum 20m for HiFoam systems), expansion ratio calculation, blockage removal, nozzle spray uniformity assessment
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Content & Condition - Verify correct foam concentrate level, check for sludging, separation, or chemical deterioration indicating degradation oCheck: Visual inspection of foam tank/container appearance, density measurement, pH testing, microscopic examination for sludge/particulates per IMO MSC.1/Circ.1312 standards
- Area: System Pressure & Safety Valve Function - Verify pressurization levels meet specification and safety relief valves open/close at correct setpoints without leakaCheck: Pressure gauge reading verification, manual safety valve actuation test, hydrostatic test of all pressure vessels per ASME standards, pressure relief accuracy testing
- Area: Foam Proportioning & Discharge Accuracy - Confirm proportioner delivers correct mixing ratio (1%, 3%, 6% per system design) without variation exceeding tolerancCheck: Annual proportioner flow test with calibrated mixing verification, foam generation test at actual discharge nozzles, comparison against baseline performance data
- Area: Hose, Fittings & Connection Integrity - Inspect all foam supply hoses, quick-couplings, BSP threads, and flexible lines for leaks, corrosion, kinking, wear, orCheck: Visual examination under pressure (dry and wet tests), hydrostatic pressure testing of hoses per EN 854-1SC or equivalent, coupling engagement/disengagement cycle testing
- Area: Nozzle & Foam Generator Discharge Quality - Verify nozzles produce specified foam pattern (small droplets vs. jets), foam stack height testing, expansion ratioCheck: Visual pattern observation during discharge test, foam stack height measurement (minimum 20m for HiFoam systems), expansion ratio calculation, blockage removal, nozzle spray uniformity assessment
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Content & Condition - Verify correct foam concentrate level, check for sludging, separation, or chemical deterioration indicating degradation oCheck: Visual inspection of foam tank/container appearance, density measurement, pH testing, microscopic examination for sludge/particulates per IMO MSC.1/Circ.1312 standards
- Area: System Pressure & Safety Valve Function - Verify pressurization levels meet specification and safety relief valves open/close at correct setpoints without leakaCheck: Pressure gauge reading verification, manual safety valve actuation test, hydrostatic test of all pressure vessels per ASME standards, pressure relief accuracy testing
- Area: Foam Proportioning & Discharge Accuracy - Confirm proportioner delivers correct mixing ratio (1%, 3%, 6% per system design) without variation exceeding tolerancCheck: Annual proportioner flow test with calibrated mixing verification, foam generation test at actual discharge nozzles, comparison against baseline performance data
- Area: Hose, Fittings & Connection Integrity - Inspect all foam supply hoses, quick-couplings, BSP threads, and flexible lines for leaks, corrosion, kinking, wear, orCheck: Visual examination under pressure (dry and wet tests), hydrostatic pressure testing of hoses per EN 854-1SC or equivalent, coupling engagement/disengagement cycle testing
- Area: Nozzle & Foam Generator Discharge Quality - Verify nozzles produce specified foam pattern (small droplets vs. jets), foam stack height testing, expansion ratioCheck: Visual pattern observation during discharge test, foam stack height measurement (minimum 20m for HiFoam systems), expansion ratio calculation, blockage removal, nozzle spray uniformity assessment
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Content & Condition - Verify correct foam concentrate level, check for sludging, separation, or chemical deterioration indicating degradation oCheck: Visual inspection of foam tank/container appearance, density measurement, pH testing, microscopic examination for sludge/particulates per IMO MSC.1/Circ.1312 standards
- Area: System Pressure & Safety Valve Function - Verify pressurization levels meet specification and safety relief valves open/close at correct setpoints without leakaCheck: Pressure gauge reading verification, manual safety valve actuation test, hydrostatic test of all pressure vessels per ASME standards, pressure relief accuracy testing
- Area: Foam Proportioning & Discharge Accuracy - Confirm proportioner delivers correct mixing ratio (1%, 3%, 6% per system design) without variation exceeding tolerancCheck: Annual proportioner flow test with calibrated mixing verification, foam generation test at actual discharge nozzles, comparison against baseline performance data
- Area: Hose, Fittings & Connection Integrity - Inspect all foam supply hoses, quick-couplings, BSP threads, and flexible lines for leaks, corrosion, kinking, wear, orCheck: Visual examination under pressure (dry and wet tests), hydrostatic pressure testing of hoses per EN 854-1SC or equivalent, coupling engagement/disengagement cycle testing
- Area: Nozzle & Foam Generator Discharge Quality - Verify nozzles produce specified foam pattern (small droplets vs. jets), foam stack height testing, expansion ratioCheck: Visual pattern observation during discharge test, foam stack height measurement (minimum 20m for HiFoam systems), expansion ratio calculation, blockage removal, nozzle spray uniformity assessment
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Content & Condition - Verify correct foam concentrate level, check for sludging, separation, or chemical deterioration indicating degradation oCheck: Visual inspection of foam tank/container appearance, density measurement, pH testing, microscopic examination for sludge/particulates per IMO MSC.1/Circ.1312 standards
- Area: System Pressure & Safety Valve Function - Verify pressurization levels meet specification and safety relief valves open/close at correct setpoints without leakaCheck: Pressure gauge reading verification, manual safety valve actuation test, hydrostatic test of all pressure vessels per ASME standards, pressure relief accuracy testing
- Area: Foam Proportioning & Discharge Accuracy - Confirm proportioner delivers correct mixing ratio (1%, 3%, 6% per system design) without variation exceeding tolerancCheck: Annual proportioner flow test with calibrated mixing verification, foam generation test at actual discharge nozzles, comparison against baseline performance data
- Area: Hose, Fittings & Connection Integrity - Inspect all foam supply hoses, quick-couplings, BSP threads, and flexible lines for leaks, corrosion, kinking, wear, orCheck: Visual examination under pressure (dry and wet tests), hydrostatic pressure testing of hoses per EN 854-1SC or equivalent, coupling engagement/disengagement cycle testing
- Area: Nozzle & Foam Generator Discharge Quality - Verify nozzles produce specified foam pattern (small droplets vs. jets), foam stack height testing, expansion ratioCheck: Visual pattern observation during discharge test, foam stack height measurement (minimum 20m for HiFoam systems), expansion ratio calculation, blockage removal, nozzle spray uniformity assessment
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Content & Condition - Verify correct foam concentrate level, check for sludging, separation, or chemical deterioration indicating degradation oCheck: Visual inspection of foam tank/container appearance, density measurement, pH testing, microscopic examination for sludge/particulates per IMO MSC.1/Circ.1312 standards
- Area: System Pressure & Safety Valve Function - Verify pressurization levels meet specification and safety relief valves open/close at correct setpoints without leakaCheck: Pressure gauge reading verification, manual safety valve actuation test, hydrostatic test of all pressure vessels per ASME standards, pressure relief accuracy testing
- Area: Foam Proportioning & Discharge Accuracy - Confirm proportioner delivers correct mixing ratio (1%, 3%, 6% per system design) without variation exceeding tolerancCheck: Annual proportioner flow test with calibrated mixing verification, foam generation test at actual discharge nozzles, comparison against baseline performance data
- Area: Hose, Fittings & Connection Integrity - Inspect all foam supply hoses, quick-couplings, BSP threads, and flexible lines for leaks, corrosion, kinking, wear, orCheck: Visual examination under pressure (dry and wet tests), hydrostatic pressure testing of hoses per EN 854-1SC or equivalent, coupling engagement/disengagement cycle testing
- Area: Nozzle & Foam Generator Discharge Quality - Verify nozzles produce specified foam pattern (small droplets vs. jets), foam stack height testing, expansion ratioCheck: Visual pattern observation during discharge test, foam stack height measurement (minimum 20m for HiFoam systems), expansion ratio calculation, blockage removal, nozzle spray uniformity assessment
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Content & Condition - Verify correct foam concentrate level, check for sludging, separation, or chemical deterioration indicating degradation oCheck: Visual inspection of foam tank/container appearance, density measurement, pH testing, microscopic examination for sludge/particulates per IMO MSC.1/Circ.1312 standards
- Area: System Pressure & Safety Valve Function - Verify pressurization levels meet specification and safety relief valves open/close at correct setpoints without leakaCheck: Pressure gauge reading verification, manual safety valve actuation test, hydrostatic test of all pressure vessels per ASME standards, pressure relief accuracy testing
- Area: Foam Proportioning & Discharge Accuracy - Confirm proportioner delivers correct mixing ratio (1%, 3%, 6% per system design) without variation exceeding tolerancCheck: Annual proportioner flow test with calibrated mixing verification, foam generation test at actual discharge nozzles, comparison against baseline performance data
- Area: Hose, Fittings & Connection Integrity - Inspect all foam supply hoses, quick-couplings, BSP threads, and flexible lines for leaks, corrosion, kinking, wear, orCheck: Visual examination under pressure (dry and wet tests), hydrostatic pressure testing of hoses per EN 854-1SC or equivalent, coupling engagement/disengagement cycle testing
- Area: Nozzle & Foam Generator Discharge Quality - Verify nozzles produce specified foam pattern (small droplets vs. jets), foam stack height testing, expansion ratioCheck: Visual pattern observation during discharge test, foam stack height measurement (minimum 20m for HiFoam systems), expansion ratio calculation, blockage removal, nozzle spray uniformity assessment
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Content & Condition - Verify correct foam concentrate level, check for sludging, separation, or chemical deterioration indicating degradation oCheck: Visual inspection of foam tank/container appearance, density measurement, pH testing, microscopic examination for sludge/particulates per IMO MSC.1/Circ.1312 standards
- Area: System Pressure & Safety Valve Function - Verify pressurization levels meet specification and safety relief valves open/close at correct setpoints without leakaCheck: Pressure gauge reading verification, manual safety valve actuation test, hydrostatic test of all pressure vessels per ASME standards, pressure relief accuracy testing
- Area: Foam Proportioning & Discharge Accuracy - Confirm proportioner delivers correct mixing ratio (1%, 3%, 6% per system design) without variation exceeding tolerancCheck: Annual proportioner flow test with calibrated mixing verification, foam generation test at actual discharge nozzles, comparison against baseline performance data
- Area: Hose, Fittings & Connection Integrity - Inspect all foam supply hoses, quick-couplings, BSP threads, and flexible lines for leaks, corrosion, kinking, wear, orCheck: Visual examination under pressure (dry and wet tests), hydrostatic pressure testing of hoses per EN 854-1SC or equivalent, coupling engagement/disengagement cycle testing
- Area: Nozzle & Foam Generator Discharge Quality - Verify nozzles produce specified foam pattern (small droplets vs. jets), foam stack height testing, expansion ratioCheck: Visual pattern observation during discharge test, foam stack height measurement (minimum 20m for HiFoam systems), expansion ratio calculation, blockage removal, nozzle spray uniformity assessment
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Content & Condition - Verify correct foam concentrate level, check for sludging, separation, or chemical deterioration indicating degradation oCheck: Visual inspection of foam tank/container appearance, density measurement, pH testing, microscopic examination for sludge/particulates per IMO MSC.1/Circ.1312 standards
- Area: System Pressure & Safety Valve Function - Verify pressurization levels meet specification and safety relief valves open/close at correct setpoints without leakaCheck: Pressure gauge reading verification, manual safety valve actuation test, hydrostatic test of all pressure vessels per ASME standards, pressure relief accuracy testing
- Area: Foam Proportioning & Discharge Accuracy - Confirm proportioner delivers correct mixing ratio (1%, 3%, 6% per system design) without variation exceeding tolerancCheck: Annual proportioner flow test with calibrated mixing verification, foam generation test at actual discharge nozzles, comparison against baseline performance data
- Area: Hose, Fittings & Connection Integrity - Inspect all foam supply hoses, quick-couplings, BSP threads, and flexible lines for leaks, corrosion, kinking, wear, orCheck: Visual examination under pressure (dry and wet tests), hydrostatic pressure testing of hoses per EN 854-1SC or equivalent, coupling engagement/disengagement cycle testing
- Area: Nozzle & Foam Generator Discharge Quality - Verify nozzles produce specified foam pattern (small droplets vs. jets), foam stack height testing, expansion ratioCheck: Visual pattern observation during discharge test, foam stack height measurement (minimum 20m for HiFoam systems), expansion ratio calculation, blockage removal, nozzle spray uniformity assessment
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Content & Condition - Verify correct foam concentrate level, check for sludging, separation, or chemical deterioration indicating degradation oCheck: Visual inspection of foam tank/container appearance, density measurement, pH testing, microscopic examination for sludge/particulates per IMO MSC.1/Circ.1312 standards
- Area: System Pressure & Safety Valve Function - Verify pressurization levels meet specification and safety relief valves open/close at correct setpoints without leakaCheck: Pressure gauge reading verification, manual safety valve actuation test, hydrostatic test of all pressure vessels per ASME standards, pressure relief accuracy testing
- Area: Foam Proportioning & Discharge Accuracy - Confirm proportioner delivers correct mixing ratio (1%, 3%, 6% per system design) without variation exceeding tolerancCheck: Annual proportioner flow test with calibrated mixing verification, foam generation test at actual discharge nozzles, comparison against baseline performance data
- Area: Hose, Fittings & Connection Integrity - Inspect all foam supply hoses, quick-couplings, BSP threads, and flexible lines for leaks, corrosion, kinking, wear, orCheck: Visual examination under pressure (dry and wet tests), hydrostatic pressure testing of hoses per EN 854-1SC or equivalent, coupling engagement/disengagement cycle testing
- Area: Nozzle & Foam Generator Discharge Quality - Verify nozzles produce specified foam pattern (small droplets vs. jets), foam stack height testing, expansion ratioCheck: Visual pattern observation during discharge test, foam stack height measurement (minimum 20m for HiFoam systems), expansion ratio calculation, blockage removal, nozzle spray uniformity assessment
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Content & Condition - Verify correct foam concentrate level, check for sludging, separation, or chemical deterioration indicating degradation oCheck: Visual inspection of foam tank/container appearance, density measurement, pH testing, microscopic examination for sludge/particulates per IMO MSC.1/Circ.1312 standards
- Area: System Pressure & Safety Valve Function - Verify pressurization levels meet specification and safety relief valves open/close at correct setpoints without leakaCheck: Pressure gauge reading verification, manual safety valve actuation test, hydrostatic test of all pressure vessels per ASME standards, pressure relief accuracy testing
- Area: Foam Proportioning & Discharge Accuracy - Confirm proportioner delivers correct mixing ratio (1%, 3%, 6% per system design) without variation exceeding tolerancCheck: Annual proportioner flow test with calibrated mixing verification, foam generation test at actual discharge nozzles, comparison against baseline performance data
- Area: Hose, Fittings & Connection Integrity - Inspect all foam supply hoses, quick-couplings, BSP threads, and flexible lines for leaks, corrosion, kinking, wear, orCheck: Visual examination under pressure (dry and wet tests), hydrostatic pressure testing of hoses per EN 854-1SC or equivalent, coupling engagement/disengagement cycle testing
- Area: Nozzle & Foam Generator Discharge Quality - Verify nozzles produce specified foam pattern (small droplets vs. jets), foam stack height testing, expansion ratioCheck: Visual pattern observation during discharge test, foam stack height measurement (minimum 20m for HiFoam systems), expansion ratio calculation, blockage removal, nozzle spray uniformity assessment
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Content & Condition - Verify correct foam concentrate level, check for sludging, separation, or chemical deterioration indicating degradation oCheck: Visual inspection of foam tank/container appearance, density measurement, pH testing, microscopic examination for sludge/particulates per IMO MSC.1/Circ.1312 standards
- Area: System Pressure & Safety Valve Function - Verify pressurization levels meet specification and safety relief valves open/close at correct setpoints without leakaCheck: Pressure gauge reading verification, manual safety valve actuation test, hydrostatic test of all pressure vessels per ASME standards, pressure relief accuracy testing
- Area: Foam Proportioning & Discharge Accuracy - Confirm proportioner delivers correct mixing ratio (1%, 3%, 6% per system design) without variation exceeding tolerancCheck: Annual proportioner flow test with calibrated mixing verification, foam generation test at actual discharge nozzles, comparison against baseline performance data
- Area: Hose, Fittings & Connection Integrity - Inspect all foam supply hoses, quick-couplings, BSP threads, and flexible lines for leaks, corrosion, kinking, wear, orCheck: Visual examination under pressure (dry and wet tests), hydrostatic pressure testing of hoses per EN 854-1SC or equivalent, coupling engagement/disengagement cycle testing
- Area: Nozzle & Foam Generator Discharge Quality - Verify nozzles produce specified foam pattern (small droplets vs. jets), foam stack height testing, expansion ratioCheck: Visual pattern observation during discharge test, foam stack height measurement (minimum 20m for HiFoam systems), expansion ratio calculation, blockage removal, nozzle spray uniformity assessment
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Content & Condition - Verify correct foam concentrate level, check for sludging, separation, or chemical deterioration indicating degradation oCheck: Visual inspection of foam tank/container appearance, density measurement, pH testing, microscopic examination for sludge/particulates per IMO MSC.1/Circ.1312 standards
- Area: System Pressure & Safety Valve Function - Verify pressurization levels meet specification and safety relief valves open/close at correct setpoints without leakaCheck: Pressure gauge reading verification, manual safety valve actuation test, hydrostatic test of all pressure vessels per ASME standards, pressure relief accuracy testing
- Area: Foam Proportioning & Discharge Accuracy - Confirm proportioner delivers correct mixing ratio (1%, 3%, 6% per system design) without variation exceeding tolerancCheck: Annual proportioner flow test with calibrated mixing verification, foam generation test at actual discharge nozzles, comparison against baseline performance data
- Area: Hose, Fittings & Connection Integrity - Inspect all foam supply hoses, quick-couplings, BSP threads, and flexible lines for leaks, corrosion, kinking, wear, orCheck: Visual examination under pressure (dry and wet tests), hydrostatic pressure testing of hoses per EN 854-1SC or equivalent, coupling engagement/disengagement cycle testing
- Area: Nozzle & Foam Generator Discharge Quality - Verify nozzles produce specified foam pattern (small droplets vs. jets), foam stack height testing, expansion ratioCheck: Visual pattern observation during discharge test, foam stack height measurement (minimum 20m for HiFoam systems), expansion ratio calculation, blockage removal, nozzle spray uniformity assessment
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Content & Condition - Verify correct foam concentrate level, check for sludging, separation, or chemical deterioration indicating degradation oCheck: Visual inspection of foam tank/container appearance, density measurement, pH testing, microscopic examination for sludge/particulates per IMO MSC.1/Circ.1312 standards
- Area: System Pressure & Safety Valve Function - Verify pressurization levels meet specification and safety relief valves open/close at correct setpoints without leakaCheck: Pressure gauge reading verification, manual safety valve actuation test, hydrostatic test of all pressure vessels per ASME standards, pressure relief accuracy testing
- Area: Foam Proportioning & Discharge Accuracy - Confirm proportioner delivers correct mixing ratio (1%, 3%, 6% per system design) without variation exceeding tolerancCheck: Annual proportioner flow test with calibrated mixing verification, foam generation test at actual discharge nozzles, comparison against baseline performance data
- Area: Hose, Fittings & Connection Integrity - Inspect all foam supply hoses, quick-couplings, BSP threads, and flexible lines for leaks, corrosion, kinking, wear, orCheck: Visual examination under pressure (dry and wet tests), hydrostatic pressure testing of hoses per EN 854-1SC or equivalent, coupling engagement/disengagement cycle testing
- Area: Nozzle & Foam Generator Discharge Quality - Verify nozzles produce specified foam pattern (small droplets vs. jets), foam stack height testing, expansion ratioCheck: Visual pattern observation during discharge test, foam stack height measurement (minimum 20m for HiFoam systems), expansion ratio calculation, blockage removal, nozzle spray uniformity assessment
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Content & Condition - Verify correct foam concentrate level, check for sludging, separation, or chemical deterioration indicating degradation oCheck: Visual inspection of foam tank/container appearance, density measurement, pH testing, microscopic examination for sludge/particulates per IMO MSC.1/Circ.1312 standards
- Area: System Pressure & Safety Valve Function - Verify pressurization levels meet specification and safety relief valves open/close at correct setpoints without leakaCheck: Pressure gauge reading verification, manual safety valve actuation test, hydrostatic test of all pressure vessels per ASME standards, pressure relief accuracy testing
- Area: Foam Proportioning & Discharge Accuracy - Confirm proportioner delivers correct mixing ratio (1%, 3%, 6% per system design) without variation exceeding tolerancCheck: Annual proportioner flow test with calibrated mixing verification, foam generation test at actual discharge nozzles, comparison against baseline performance data
- Area: Hose, Fittings & Connection Integrity - Inspect all foam supply hoses, quick-couplings, BSP threads, and flexible lines for leaks, corrosion, kinking, wear, orCheck: Visual examination under pressure (dry and wet tests), hydrostatic pressure testing of hoses per EN 854-1SC or equivalent, coupling engagement/disengagement cycle testing
- Area: Nozzle & Foam Generator Discharge Quality - Verify nozzles produce specified foam pattern (small droplets vs. jets), foam stack height testing, expansion ratioCheck: Visual pattern observation during discharge test, foam stack height measurement (minimum 20m for HiFoam systems), expansion ratio calculation, blockage removal, nozzle spray uniformity assessment
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Content & Condition - Verify correct foam concentrate level, check for sludging, separation, or chemical deterioration indicating degradation oCheck: Visual inspection of foam tank/container appearance, density measurement, pH testing, microscopic examination for sludge/particulates per IMO MSC.1/Circ.1312 standards
- Area: System Pressure & Safety Valve Function - Verify pressurization levels meet specification and safety relief valves open/close at correct setpoints without leakaCheck: Pressure gauge reading verification, manual safety valve actuation test, hydrostatic test of all pressure vessels per ASME standards, pressure relief accuracy testing
- Area: Foam Proportioning & Discharge Accuracy - Confirm proportioner delivers correct mixing ratio (1%, 3%, 6% per system design) without variation exceeding tolerancCheck: Annual proportioner flow test with calibrated mixing verification, foam generation test at actual discharge nozzles, comparison against baseline performance data
- Area: Hose, Fittings & Connection Integrity - Inspect all foam supply hoses, quick-couplings, BSP threads, and flexible lines for leaks, corrosion, kinking, wear, orCheck: Visual examination under pressure (dry and wet tests), hydrostatic pressure testing of hoses per EN 854-1SC or equivalent, coupling engagement/disengagement cycle testing
- Area: Nozzle & Foam Generator Discharge Quality - Verify nozzles produce specified foam pattern (small droplets vs. jets), foam stack height testing, expansion ratioCheck: Visual pattern observation during discharge test, foam stack height measurement (minimum 20m for HiFoam systems), expansion ratio calculation, blockage removal, nozzle spray uniformity assessment
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
Wilhelmsen Unitor
12 ✓ 12 verified- Area: Foam concentrate level verification and expiration date checkCheck: Verify adequate foam chemical levels in storage tanks; confirm concentrate has not exceeded shelf life (check product date codes); test foam mixing ratio accuracy with graduated measurement device
- Area: System pressure verification and pump operational statusCheck: Confirm fire/foam main isolating valves are in correct position; verify fire pump operation achieves minimum main pressure of 0.6 MPa; test pressure gauges on proportioners and generators
- Area: Foam generator and proportioner function testingCheck: Test foam generator production rate against nameplate specifications (UFG models: 20-60 m³/min nominal at 5-7 bar); verify proportioner delivers correct concentrate concentration (1%, 3%, or 6%); inspect for blockages in generator nozzles
- Area: Piping, valve, and component corrosion inspectionCheck: Inspect all foam piping, monitor valve connections, and proportioner components for visible corrosion, scale buildup, or physical damage; check for proper coating integrity on stainless steel components; verify no leaks at connection points
- Area: System discharge and alarm testingCheck: Test audible and visible alarm systems for functionality; verify discharge nozzles and monitors spray pattern and reach distance; inspect eductor valve operation; perform test discharge to confirm proper foam generation and mixing (follow operational procedures to avoid directing foam at ignition sources until foam appears at nozzle)
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam concentrate level verification and expiration date checkCheck: Verify adequate foam chemical levels in storage tanks; confirm concentrate has not exceeded shelf life (check product date codes); test foam mixing ratio accuracy with graduated measurement device
- Area: System pressure verification and pump operational statusCheck: Confirm fire/foam main isolating valves are in correct position; verify fire pump operation achieves minimum main pressure of 0.6 MPa; test pressure gauges on proportioners and generators
- Area: Foam generator and proportioner function testingCheck: Test foam generator production rate against nameplate specifications (UFG models: 20-60 m³/min nominal at 5-7 bar); verify proportioner delivers correct concentrate concentration (1%, 3%, or 6%); inspect for blockages in generator nozzles
- Area: Piping, valve, and component corrosion inspectionCheck: Inspect all foam piping, monitor valve connections, and proportioner components for visible corrosion, scale buildup, or physical damage; check for proper coating integrity on stainless steel components; verify no leaks at connection points
- Area: System discharge and alarm testingCheck: Test audible and visible alarm systems for functionality; verify discharge nozzles and monitors spray pattern and reach distance; inspect eductor valve operation; perform test discharge to confirm proper foam generation and mixing (follow operational procedures to avoid directing foam at ignition sources until foam appears at nozzle)
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam concentrate level verification and expiration date checkCheck: Verify adequate foam chemical levels in storage tanks; confirm concentrate has not exceeded shelf life (check product date codes); test foam mixing ratio accuracy with graduated measurement device
- Area: System pressure verification and pump operational statusCheck: Confirm fire/foam main isolating valves are in correct position; verify fire pump operation achieves minimum main pressure of 0.6 MPa; test pressure gauges on proportioners and generators
- Area: Foam generator and proportioner function testingCheck: Test foam generator production rate against nameplate specifications (UFG models: 20-60 m³/min nominal at 5-7 bar); verify proportioner delivers correct concentrate concentration (1%, 3%, or 6%); inspect for blockages in generator nozzles
- Area: Piping, valve, and component corrosion inspectionCheck: Inspect all foam piping, monitor valve connections, and proportioner components for visible corrosion, scale buildup, or physical damage; check for proper coating integrity on stainless steel components; verify no leaks at connection points
- Area: System discharge and alarm testingCheck: Test audible and visible alarm systems for functionality; verify discharge nozzles and monitors spray pattern and reach distance; inspect eductor valve operation; perform test discharge to confirm proper foam generation and mixing (follow operational procedures to avoid directing foam at ignition sources until foam appears at nozzle)
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam concentrate level verification and expiration date checkCheck: Verify adequate foam chemical levels in storage tanks; confirm concentrate has not exceeded shelf life (check product date codes); test foam mixing ratio accuracy with graduated measurement device
- Area: System pressure verification and pump operational statusCheck: Confirm fire/foam main isolating valves are in correct position; verify fire pump operation achieves minimum main pressure of 0.6 MPa; test pressure gauges on proportioners and generators
- Area: Foam generator and proportioner function testingCheck: Test foam generator production rate against nameplate specifications (UFG models: 20-60 m³/min nominal at 5-7 bar); verify proportioner delivers correct concentrate concentration (1%, 3%, or 6%); inspect for blockages in generator nozzles
- Area: Piping, valve, and component corrosion inspectionCheck: Inspect all foam piping, monitor valve connections, and proportioner components for visible corrosion, scale buildup, or physical damage; check for proper coating integrity on stainless steel components; verify no leaks at connection points
- Area: System discharge and alarm testingCheck: Test audible and visible alarm systems for functionality; verify discharge nozzles and monitors spray pattern and reach distance; inspect eductor valve operation; perform test discharge to confirm proper foam generation and mixing (follow operational procedures to avoid directing foam at ignition sources until foam appears at nozzle)
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam concentrate level verification and expiration date checkCheck: Verify adequate foam chemical levels in storage tanks; confirm concentrate has not exceeded shelf life (check product date codes); test foam mixing ratio accuracy with graduated measurement device
- Area: System pressure verification and pump operational statusCheck: Confirm fire/foam main isolating valves are in correct position; verify fire pump operation achieves minimum main pressure of 0.6 MPa; test pressure gauges on proportioners and generators
- Area: Foam generator and proportioner function testingCheck: Test foam generator production rate against nameplate specifications (UFG models: 20-60 m³/min nominal at 5-7 bar); verify proportioner delivers correct concentrate concentration (1%, 3%, or 6%); inspect for blockages in generator nozzles
- Area: Piping, valve, and component corrosion inspectionCheck: Inspect all foam piping, monitor valve connections, and proportioner components for visible corrosion, scale buildup, or physical damage; check for proper coating integrity on stainless steel components; verify no leaks at connection points
- Area: System discharge and alarm testingCheck: Test audible and visible alarm systems for functionality; verify discharge nozzles and monitors spray pattern and reach distance; inspect eductor valve operation; perform test discharge to confirm proper foam generation and mixing (follow operational procedures to avoid directing foam at ignition sources until foam appears at nozzle)
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam concentrate level verification and expiration date checkCheck: Verify adequate foam chemical levels in storage tanks; confirm concentrate has not exceeded shelf life (check product date codes); test foam mixing ratio accuracy with graduated measurement device
- Area: System pressure verification and pump operational statusCheck: Confirm fire/foam main isolating valves are in correct position; verify fire pump operation achieves minimum main pressure of 0.6 MPa; test pressure gauges on proportioners and generators
- Area: Foam generator and proportioner function testingCheck: Test foam generator production rate against nameplate specifications (UFG models: 20-60 m³/min nominal at 5-7 bar); verify proportioner delivers correct concentrate concentration (1%, 3%, or 6%); inspect for blockages in generator nozzles
- Area: Piping, valve, and component corrosion inspectionCheck: Inspect all foam piping, monitor valve connections, and proportioner components for visible corrosion, scale buildup, or physical damage; check for proper coating integrity on stainless steel components; verify no leaks at connection points
- Area: System discharge and alarm testingCheck: Test audible and visible alarm systems for functionality; verify discharge nozzles and monitors spray pattern and reach distance; inspect eductor valve operation; perform test discharge to confirm proper foam generation and mixing (follow operational procedures to avoid directing foam at ignition sources until foam appears at nozzle)
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam concentrate level verification and expiration date checkCheck: Verify adequate foam chemical levels in storage tanks; confirm concentrate has not exceeded shelf life (check product date codes); test foam mixing ratio accuracy with graduated measurement device
- Area: System pressure verification and pump operational statusCheck: Confirm fire/foam main isolating valves are in correct position; verify fire pump operation achieves minimum main pressure of 0.6 MPa; test pressure gauges on proportioners and generators
- Area: Foam generator and proportioner function testingCheck: Test foam generator production rate against nameplate specifications (UFG models: 20-60 m³/min nominal at 5-7 bar); verify proportioner delivers correct concentrate concentration (1%, 3%, or 6%); inspect for blockages in generator nozzles
- Area: Piping, valve, and component corrosion inspectionCheck: Inspect all foam piping, monitor valve connections, and proportioner components for visible corrosion, scale buildup, or physical damage; check for proper coating integrity on stainless steel components; verify no leaks at connection points
- Area: System discharge and alarm testingCheck: Test audible and visible alarm systems for functionality; verify discharge nozzles and monitors spray pattern and reach distance; inspect eductor valve operation; perform test discharge to confirm proper foam generation and mixing (follow operational procedures to avoid directing foam at ignition sources until foam appears at nozzle)
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam concentrate level verification and expiration date checkCheck: Verify adequate foam chemical levels in storage tanks; confirm concentrate has not exceeded shelf life (check product date codes); test foam mixing ratio accuracy with graduated measurement device
- Area: System pressure verification and pump operational statusCheck: Confirm fire/foam main isolating valves are in correct position; verify fire pump operation achieves minimum main pressure of 0.6 MPa; test pressure gauges on proportioners and generators
- Area: Foam generator and proportioner function testingCheck: Test foam generator production rate against nameplate specifications (UFG models: 20-60 m³/min nominal at 5-7 bar); verify proportioner delivers correct concentrate concentration (1%, 3%, or 6%); inspect for blockages in generator nozzles
- Area: Piping, valve, and component corrosion inspectionCheck: Inspect all foam piping, monitor valve connections, and proportioner components for visible corrosion, scale buildup, or physical damage; check for proper coating integrity on stainless steel components; verify no leaks at connection points
- Area: System discharge and alarm testingCheck: Test audible and visible alarm systems for functionality; verify discharge nozzles and monitors spray pattern and reach distance; inspect eductor valve operation; perform test discharge to confirm proper foam generation and mixing (follow operational procedures to avoid directing foam at ignition sources until foam appears at nozzle)
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam concentrate level verification and expiration date checkCheck: Verify adequate foam chemical levels in storage tanks; confirm concentrate has not exceeded shelf life (check product date codes); test foam mixing ratio accuracy with graduated measurement device
- Area: System pressure verification and pump operational statusCheck: Confirm fire/foam main isolating valves are in correct position; verify fire pump operation achieves minimum main pressure of 0.6 MPa; test pressure gauges on proportioners and generators
- Area: Foam generator and proportioner function testingCheck: Test foam generator production rate against nameplate specifications (UFG models: 20-60 m³/min nominal at 5-7 bar); verify proportioner delivers correct concentrate concentration (1%, 3%, or 6%); inspect for blockages in generator nozzles
- Area: Piping, valve, and component corrosion inspectionCheck: Inspect all foam piping, monitor valve connections, and proportioner components for visible corrosion, scale buildup, or physical damage; check for proper coating integrity on stainless steel components; verify no leaks at connection points
- Area: System discharge and alarm testingCheck: Test audible and visible alarm systems for functionality; verify discharge nozzles and monitors spray pattern and reach distance; inspect eductor valve operation; perform test discharge to confirm proper foam generation and mixing (follow operational procedures to avoid directing foam at ignition sources until foam appears at nozzle)
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam concentrate level verification and expiration date checkCheck: Verify adequate foam chemical levels in storage tanks; confirm concentrate has not exceeded shelf life (check product date codes); test foam mixing ratio accuracy with graduated measurement device
- Area: System pressure verification and pump operational statusCheck: Confirm fire/foam main isolating valves are in correct position; verify fire pump operation achieves minimum main pressure of 0.6 MPa; test pressure gauges on proportioners and generators
- Area: Foam generator and proportioner function testingCheck: Test foam generator production rate against nameplate specifications (UFG models: 20-60 m³/min nominal at 5-7 bar); verify proportioner delivers correct concentrate concentration (1%, 3%, or 6%); inspect for blockages in generator nozzles
- Area: Piping, valve, and component corrosion inspectionCheck: Inspect all foam piping, monitor valve connections, and proportioner components for visible corrosion, scale buildup, or physical damage; check for proper coating integrity on stainless steel components; verify no leaks at connection points
- Area: System discharge and alarm testingCheck: Test audible and visible alarm systems for functionality; verify discharge nozzles and monitors spray pattern and reach distance; inspect eductor valve operation; perform test discharge to confirm proper foam generation and mixing (follow operational procedures to avoid directing foam at ignition sources until foam appears at nozzle)
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam concentrate level verification and expiration date checkCheck: Verify adequate foam chemical levels in storage tanks; confirm concentrate has not exceeded shelf life (check product date codes); test foam mixing ratio accuracy with graduated measurement device
- Area: System pressure verification and pump operational statusCheck: Confirm fire/foam main isolating valves are in correct position; verify fire pump operation achieves minimum main pressure of 0.6 MPa; test pressure gauges on proportioners and generators
- Area: Foam generator and proportioner function testingCheck: Test foam generator production rate against nameplate specifications (UFG models: 20-60 m³/min nominal at 5-7 bar); verify proportioner delivers correct concentrate concentration (1%, 3%, or 6%); inspect for blockages in generator nozzles
- Area: Piping, valve, and component corrosion inspectionCheck: Inspect all foam piping, monitor valve connections, and proportioner components for visible corrosion, scale buildup, or physical damage; check for proper coating integrity on stainless steel components; verify no leaks at connection points
- Area: System discharge and alarm testingCheck: Test audible and visible alarm systems for functionality; verify discharge nozzles and monitors spray pattern and reach distance; inspect eductor valve operation; perform test discharge to confirm proper foam generation and mixing (follow operational procedures to avoid directing foam at ignition sources until foam appears at nozzle)
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam concentrate level verification and expiration date checkCheck: Verify adequate foam chemical levels in storage tanks; confirm concentrate has not exceeded shelf life (check product date codes); test foam mixing ratio accuracy with graduated measurement device
- Area: System pressure verification and pump operational statusCheck: Confirm fire/foam main isolating valves are in correct position; verify fire pump operation achieves minimum main pressure of 0.6 MPa; test pressure gauges on proportioners and generators
- Area: Foam generator and proportioner function testingCheck: Test foam generator production rate against nameplate specifications (UFG models: 20-60 m³/min nominal at 5-7 bar); verify proportioner delivers correct concentrate concentration (1%, 3%, or 6%); inspect for blockages in generator nozzles
- Area: Piping, valve, and component corrosion inspectionCheck: Inspect all foam piping, monitor valve connections, and proportioner components for visible corrosion, scale buildup, or physical damage; check for proper coating integrity on stainless steel components; verify no leaks at connection points
- Area: System discharge and alarm testingCheck: Test audible and visible alarm systems for functionality; verify discharge nozzles and monitors spray pattern and reach distance; inspect eductor valve operation; perform test discharge to confirm proper foam generation and mixing (follow operational procedures to avoid directing foam at ignition sources until foam appears at nozzle)
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
NK
6 ✓ 6 verified- Area: Foam Concentrate Deterioration and ContaminationCheck: Annual visual inspection of foam concentrate in storage tanks for excessive sludging, discoloration, or crystallization; laboratory quality testing of foam samples for viscosity, surface tension, and emulsion stability per ISO/IEC standards
- Area: Foam Generator Pressure and Flow Rate PerformanceCheck: Annual functional test of foam proportioning generators at rated operating pressure (4 bar); measure actual foam output capacity (m³/min) against nameplate specifications; verify proportioning ratio accuracy (1-3% injection)
- Area: System Piping and Component IntegrityCheck: Visual inspection of all piping, connections, and nozzles for corrosion, scaling, or blockage; pressure testing at 1.5x operating pressure; verify water connections (100A/150A) are clear and functional
- Area: Foam Expansion Ratio and Quality VerificationCheck: Test foam expansion ratio (target 1:670 for NK.D-101M, 960+ for system discharge) using standardized test nozzles; measure drainage time and foam stability per EN 1568-3 or equivalent maritime standards
- Area: SOLAS Compliance and Certification DocumentationCheck: Verify MED (Marine Equipment Directive) B+D and IMO Rules certifications are current; confirm PFAS restrictions compliance (PFOS <10 mg/kg effective from 1 January 2026); review maintenance log and maker's declarations for approved foam batch numbers
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Deterioration and ContaminationCheck: Annual visual inspection of foam concentrate in storage tanks for excessive sludging, discoloration, or crystallization; laboratory quality testing of foam samples for viscosity, surface tension, and emulsion stability per ISO/IEC standards
- Area: Foam Generator Pressure and Flow Rate PerformanceCheck: Annual functional test of foam proportioning generators at rated operating pressure (4 bar); measure actual foam output capacity (m³/min) against nameplate specifications; verify proportioning ratio accuracy (1-3% injection)
- Area: System Piping and Component IntegrityCheck: Visual inspection of all piping, connections, and nozzles for corrosion, scaling, or blockage; pressure testing at 1.5x operating pressure; verify water connections (100A/150A) are clear and functional
- Area: Foam Expansion Ratio and Quality VerificationCheck: Test foam expansion ratio (target 1:670 for NK.D-101M, 960+ for system discharge) using standardized test nozzles; measure drainage time and foam stability per EN 1568-3 or equivalent maritime standards
- Area: SOLAS Compliance and Certification DocumentationCheck: Verify MED (Marine Equipment Directive) B+D and IMO Rules certifications are current; confirm PFAS restrictions compliance (PFOS <10 mg/kg effective from 1 January 2026); review maintenance log and maker's declarations for approved foam batch numbers
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Deterioration and ContaminationCheck: Annual visual inspection of foam concentrate in storage tanks for excessive sludging, discoloration, or crystallization; laboratory quality testing of foam samples for viscosity, surface tension, and emulsion stability per ISO/IEC standards
- Area: Foam Generator Pressure and Flow Rate PerformanceCheck: Annual functional test of foam proportioning generators at rated operating pressure (4 bar); measure actual foam output capacity (m³/min) against nameplate specifications; verify proportioning ratio accuracy (1-3% injection)
- Area: System Piping and Component IntegrityCheck: Visual inspection of all piping, connections, and nozzles for corrosion, scaling, or blockage; pressure testing at 1.5x operating pressure; verify water connections (100A/150A) are clear and functional
- Area: Foam Expansion Ratio and Quality VerificationCheck: Test foam expansion ratio (target 1:670 for NK.D-101M, 960+ for system discharge) using standardized test nozzles; measure drainage time and foam stability per EN 1568-3 or equivalent maritime standards
- Area: SOLAS Compliance and Certification DocumentationCheck: Verify MED (Marine Equipment Directive) B+D and IMO Rules certifications are current; confirm PFAS restrictions compliance (PFOS <10 mg/kg effective from 1 January 2026); review maintenance log and maker's declarations for approved foam batch numbers
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Deterioration and ContaminationCheck: Annual visual inspection of foam concentrate in storage tanks for excessive sludging, discoloration, or crystallization; laboratory quality testing of foam samples for viscosity, surface tension, and emulsion stability per ISO/IEC standards
- Area: Foam Generator Pressure and Flow Rate PerformanceCheck: Annual functional test of foam proportioning generators at rated operating pressure (4 bar); measure actual foam output capacity (m³/min) against nameplate specifications; verify proportioning ratio accuracy (1-3% injection)
- Area: System Piping and Component IntegrityCheck: Visual inspection of all piping, connections, and nozzles for corrosion, scaling, or blockage; pressure testing at 1.5x operating pressure; verify water connections (100A/150A) are clear and functional
- Area: Foam Expansion Ratio and Quality VerificationCheck: Test foam expansion ratio (target 1:670 for NK.D-101M, 960+ for system discharge) using standardized test nozzles; measure drainage time and foam stability per EN 1568-3 or equivalent maritime standards
- Area: SOLAS Compliance and Certification DocumentationCheck: Verify MED (Marine Equipment Directive) B+D and IMO Rules certifications are current; confirm PFAS restrictions compliance (PFOS <10 mg/kg effective from 1 January 2026); review maintenance log and maker's declarations for approved foam batch numbers
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Deterioration and ContaminationCheck: Annual visual inspection of foam concentrate in storage tanks for excessive sludging, discoloration, or crystallization; laboratory quality testing of foam samples for viscosity, surface tension, and emulsion stability per ISO/IEC standards
- Area: Foam Generator Pressure and Flow Rate PerformanceCheck: Annual functional test of foam proportioning generators at rated operating pressure (4 bar); measure actual foam output capacity (m³/min) against nameplate specifications; verify proportioning ratio accuracy (1-3% injection)
- Area: System Piping and Component IntegrityCheck: Visual inspection of all piping, connections, and nozzles for corrosion, scaling, or blockage; pressure testing at 1.5x operating pressure; verify water connections (100A/150A) are clear and functional
- Area: Foam Expansion Ratio and Quality VerificationCheck: Test foam expansion ratio (target 1:670 for NK.D-101M, 960+ for system discharge) using standardized test nozzles; measure drainage time and foam stability per EN 1568-3 or equivalent maritime standards
- Area: SOLAS Compliance and Certification DocumentationCheck: Verify MED (Marine Equipment Directive) B+D and IMO Rules certifications are current; confirm PFAS restrictions compliance (PFOS <10 mg/kg effective from 1 January 2026); review maintenance log and maker's declarations for approved foam batch numbers
Typ-universelle Inspektionspunkte fuer Fixed Fire Suppression (verifiziert, 2026-06).
- Area: Foam Concentrate Deterioration and ContaminationCheck: Annual visual inspection of foam concentrate in storage tanks for excessive sludging, discoloration, or crystallization; laboratory quality testing of foam samples for viscosity, surface tension, and emulsion stability per ISO/IEC standards
- Area: Foam Generator Pressure and Flow Rate PerformanceCheck: Annual functional test of foam proportioning generators at rated operating pressure (4 bar); measure actual foam output capacity (m³/min) against nameplate specifications; verify proportioning ratio accuracy (1-3% injection)
- Area: System Piping and Component IntegrityCheck: Visual inspection of all piping, connections, and nozzles for corrosion, scaling, or blockage; pressure testing at 1.5x operating pressure; verify water connections (100A/150A) are clear and functional
- Area: Foam Expansion Ratio and Quality VerificationCheck: Test foam expansion ratio (target 1:670 for NK.D-101M, 960+ for system discharge) using standardized test nozzles; measure drainage time and foam stability per EN 1568-3 or equivalent maritime standards
- Area: SOLAS Compliance and Certification DocumentationCheck: Verify MED (Marine Equipment Directive) B+D and IMO Rules certifications are current; confirm PFAS restrictions compliance (PFOS <10 mg/kg effective from 1 January 2026); review maintenance log and maker's declarations for approved foam batch numbers