Library› Safety & LSA› Fire Detection Systems› Manual Call Point
Fire Detection Systems

Manual Call Point

A manual call point is the deliberately low-tech override in an otherwise automatic fire detection system: a break-glass or push-button unit that lets any crew member raise the alarm the instant they see or smell fire, without waiting for a detector to react.

45models
Apollo Fire Detectors
Knowledge

What to check on a Manual Call Point.

45 models from Apollo Fire Detectors in Manual Call Point. Below: the full model list.

What a manual call point does that automatic detectors cannot

Smoke and heat detectors react to a physical change in the air; a manual call point (MCP) reacts to a person. It exists for the case where someone spots flame, smells smoke, or sees an electrical fault sparking well before any detector head crosses its alarm threshold, and for spaces where automatic detection is impractical or where a false start needs a human override. Every MCP on the loop reports its own address to the fire panel, exactly like an automatic detector, so the location shows immediately on the mimic display.

Manual call point construction
Front view of a manual call point showing the frangible element, push button, indicator LED and casing, alongside a detail of the backbox terminals and the cable wired to the fire detection loop.

Legend

  1. frangible element (glass)
  2. indicator LED
  3. push button
  4. call point casing
  5. backbox and terminals
  6. cable to fire detection loop

Main components

Break-glass / frangible element units

The traditional design uses a small glass or plastic element that must be broken to depress the operating element underneath. This deliberately makes activation a conscious, two-stage act — reducing accidental trips from a bumped enclosure — while still needing no key or tool.

Resettable (non-frangible) units

Increasingly common, these use a hinged or push-in element that can be reset with a key after a false alarm or drill, avoiding the cost and delay of replacing a glass element every time. Many yards now specify resettable units as standard on newbuilds precisely because drills happen often.

Read the full guide

Addressable interface / base

On an addressable loop, the MCP body sits on a base that carries its own loop address, identical in principle to a smoke detector base, so the panel can distinguish an MCP activated in the engine room from a general zone alarm.

Selection considerations

  • Compatibility with the existing loop protocol — MCPs are protocol-specific and cannot be freely mixed between panel manufacturers on an addressable system.
  • Frangible versus resettable element, weighed against how often the space runs fire drills.
  • Ingress protection rating for exposed deck or engine room locations against a dry accommodation corridor unit.
  • Mounting height and colour, both fixed by class and flag requirements rather than left to preference.

Regulations and class

SOLAS Chapter II-2 and the FSS Code require manual call points at all exits from accommodation, service and control spaces, at each stairway landing, and along escape routes, in addition to automatic detection. They must be red, clearly marked, and positioned so no crew member has to travel far from any point in the space to reach one. Class surveys verify the call points activate the panel correctly and that the alarm reaches both the bridge and the fire control station, and periodic testing of a sample of call points is standard practice at each annual survey.

Typical faults

FaultConsequence
Paint applied over the unit during accommodation refurbishmentFrangible element no longer breaks under normal hand pressure, or the unit is no longer visibly red
Corroded terminal connections in weather-exposed mounting boxesLoop reports intermittent fault or the call point drops off the addressable loop entirely
Cover glass replaced with the wrong element ratingUnit either triggers under vibration alone or requires excessive force to activate
Call point address not updated after panel software changeAlarm shows the wrong location on the mimic, sending the fire team to the wrong deck

What to look for in a supplier

  • Type approval certificate matching the specific fire panel manufacturer and protocol already fitted, not a generic addressable claim.
  • Marine-rated housings (IP66 or better) for external and engine room locations.
  • Spare frangible elements available separately from full replacement units.
  • Documented compatibility with the vessel's existing loop wiring, since some manufacturers' addressable ranges are not backward compatible with older panel generations.

After any accommodation repainting, physically test every call point in the painted area — a coat of paint across the frangible element is one of the most common reasons a call point fails a survey.

Models

Models in this type.

The best-documented model of each manufacturer first, then the next — 45 of 45 models in Manual Call Point. Every row links to full specifications, documents and service notes.

Showing only Apollo Fire Detectors. Show all manufacturers
Apollo Fire Detectors55100-905* Apollo Fire Detectors55100-908* Apollo Fire Detectors58000-975MAR Apollo Fire Detectors58000-976MAR Apollo Fire Detectors58100-905* Apollo Fire Detectors58100-908* Apollo Fire Detectors58100-910* Apollo Fire Detectors58100-927* Apollo Fire Detectors58100-928* Apollo Fire Detectors58100-929* Apollo Fire Detectors58100-930* Apollo Fire Detectors58100-970* Apollo Fire Detectors58100-971* Apollo Fire Detectors58200-975MAR Apollo Fire Detectors58200-976MAR Apollo Fire DetectorsManual Call Point Break-Glass Apollo Fire DetectorsManual Call Point Resettable Apollo Fire DetectorsWeatherproof MCP IP67 Apollo Fire DetectorsMCP1A-X Apollo Fire DetectorsManual Call Point Apollo Fire DetectorsSA55200-940 Apollo Fire DetectorsSA58200-950 Apollo Fire DetectorsSA58200-951 Apollo Fire DetectorsSA58200-953 Apollo Fire DetectorsSA58200-975 Apollo Fire DetectorsSA58200-976 Apollo Fire DetectorsSA5900-011 Apollo Fire DetectorsSA5900-903** Apollo Fire DetectorsSA5900-904** Apollo Fire DetectorsSA5900-905** Apollo Fire DetectorsSA5900-906** Apollo Fire DetectorsSA5900-907** Apollo Fire DetectorsSA5900-908** Apollo Fire DetectorsSA5900-928 Apollo Fire DetectorsSA5900-948 Apollo Fire DetectorsWCP2A-X X Apollo Fire DetectorsXP95 isolated Apollo Fire Detectors58100-926* Apollo Fire Detectors58100-950 Apollo Fire Detectors58100-951 Apollo Fire Detectors58100-953 Apollo Fire Detectors58200-950 Apollo Fire Detectors58200-951 Apollo Fire Detectors58200-953 Apollo Fire DetectorsMCP
45 models
Would you like to know more?

One request. A person reads it and replies by e-mail.

Tell us the manufacturer, the model and what you need — a part, a service call, a second opinion. A person reads every request and replies by e-mail.

No details at hand? A photo of the rating plate or the part is enough — simply attach it to the request.

Frequently asked

Three things people ask first.

Is Manual Call Point data free?

Yes. Every model page, every guide and every datasheet for this type is readable without an account. An account adds saved searches and requests, nothing is taken away.

My model is missing — what now?

Send us the nameplate. We identify it by hand, add it to the library, and if you need a part or a service, the request is already on our desk.

Can you source a Manual Call Point part?

Yes. Tell us the manufacturer, the model and what you need — a person reads every request and replies by e-mail.