Library› Safety & LSA› Fire Detection Systems› Flame Detector
Fire Detection Systems

Flame Detector

A flame detector senses the ultraviolet or infrared radiation an open flame gives off, reacting within seconds rather than waiting for smoke or heat to build up, which is why it covers engine rooms and cargo areas where a fire can flash before smoke detectors would trigger.

4models
fike
Knowledge

What to check on a Flame Detector.

4 models from fike in Flame Detector. Below: the full model list.

What Makes a Flame Detector Different

A flame detector reacts to the radiation an open flame emits, ultraviolet, infrared, or both, rather than to smoke particles or a rise in ambient temperature. That gives it a response time measured in seconds instead of the minutes a smoke or heat detector can take to accumulate enough signal, and it works in spaces where smoke detectors are unreliable: engine rooms with constant airflow, exhaust and diesel fumes that would swamp a smoke chamber with false alarms, and open cargo areas too large or too ventilated for smoke to build a detectable concentration near any one sensor. The trade-off is that a flame detector only sees flame directly in its line of sight; it cannot detect a smouldering fire that has not yet broken into open flame, so it is normally installed alongside, not instead of, smoke or heat detection.

Flame detector, mounting and field of view
A flame detector housing mounted on a bracket, showing the sensor window facing its field of view toward a flame source, with the cable entry and status indicator on the housing.
Read the full guide

Main Components

Sensing element

UV detectors use a sensor tuned to the deep ultraviolet band flames produce; IR detectors watch one or more infrared wavelength bands, often comparing the flicker frequency, roughly 1-15 Hz, typical of real flame against steady infrared sources to reject false triggers. Combined UV/IR units cross-check both signals before alarming.

Optical window

A sealed, wide-angle lens that must stay clean; oil film, salt deposits or paint overspray on the window is the single most common cause of a detector going blind without anyone noticing.

Signal processing electronics

Filters out non-flame sources such as welding arcs, sunlight, hot machinery surfaces and lightning, using flicker-frequency analysis and, on dual-band units, the ratio between UV and IR signal strength.

Mounting and field of view

Fixed at a height and angle giving unobstructed sightlines over the protected area; detection range depends on flame size and typically extends tens of metres for a UV/IR unit rated for open deck or engine room use.

Selection and Sizing

  • Detection technology matched to the fire risk; hydrocarbon fires suit UV/IR combination units, which reject more false alarm sources than UV alone
  • Field of view and mounting height needed to cover the protected area without blind spots behind machinery or structure
  • Response time and sensitivity setting appropriate to the space, since too sensitive in an engine room invites nuisance trips from hot work
  • Housing rating suited to the environment, including explosion-proof certification where flammable vapours may be present, as in cargo pump rooms on tankers

Regulations and Class

SOLAS Chapter II-2 requires fixed fire detection in machinery spaces and other specified areas, with the detection system type-approved to the applicable performance standard for the technology and space it protects. Class rules require the detection system to report to a continuously manned or monitored central fire alarm panel, with detector function verified at scheduled fire drills and surveys. Detectors on cargo tank decks of tankers or in spaces handling flammable cargo also need to meet the relevant hazardous area (Ex) certification for the zone they are mounted in.

Typical Faults

FaultCauseConsequence
Detector fails to alarm on real fireOptical window fouled with oil film or dustUndetected fire growth, delayed crew response
Frequent false alarmsWelding, hot work or strong sunlight in the field of view without temporary isolationCrew begins ignoring alarms, real events risk being dismissed
No signal reaching the panelCable damage or corroded terminations in a hot, vibrating engine room environmentDetector shows as faulted or simply drops off line unnoticed
Detector triggers on hot machinery, not flameSensitivity or flicker-frequency filtering wrongly configured for the spaceNuisance trips, possible unnecessary fire suppression release

What to Look for in a Supplier

  • Marine type approval certificate valid for the specific area class, open deck, machinery space or hazardous area, the detector will serve
  • Documented false-alarm rejection performance, not just raw sensitivity figures
  • Ex-certified housing where the detector will sit in a zoned hazardous area
  • Self-test or window-fouling indication that flags a blind detector before it is needed rather than after

A flame detector with a dirty window looks identical to a healthy one until the day it matters; window cleaning on the fire round schedule is worth more than any spec sheet number.

Models

Models in this type.

The best-documented model of each manufacturer first, then the next — 4 of 4 models in Flame Detector. Every row links to full specifications, documents and service notes.

Showing only fike. Show all manufacturers
By manufacturer

Manufacturers.

All 23 manufacturers with models of Flame Detector. Names with a manufacturer page open it; the others open a search across the full library.

All manufacturers
Related types

Also in Fire Detection Systems.

The other equipment types in this category.

Addressable Fire Detection PanelConventional Fire Detection PanelFire Alarm Manual Call PointFire Detection Loop Module / IsolatorFire Detector Base / Alarm SounderHeat DetectorManual Call PointSmoke DetectorSmoke Detector (Optical)
Would you like to know more?

One request. A person reads it and replies by e-mail.

Tell us the manufacturer, the model and what you need — a part, a service call, a second opinion. A person reads every request and replies by e-mail.

No details at hand? A photo of the rating plate or the part is enough — simply attach it to the request.

Frequently asked

Three things people ask first.

Is Flame Detector data free?

Yes. Every model page, every guide and every datasheet for this type is readable without an account. An account adds saved searches and requests, nothing is taken away.

My model is missing — what now?

Send us the nameplate. We identify it by hand, add it to the library, and if you need a part or a service, the request is already on our desk.

Can you source a Flame Detector part?

Yes. Tell us the manufacturer, the model and what you need — a person reads every request and replies by e-mail.