The accommodation sprinkler system is an automatic, pressurised network that opens sprinkler heads by heat alone and starts extinguishing before the crew reaches the space, the one part of the ship's fire fighting outfit that acts without anyone touching a valve.

Tyco / Johnson Controls
Knowledge

What to check on a Sprinkler System (Accommodation).

2 models from Tyco / Johnson Controls in Sprinkler System (Accommodation). Below: the full model list.

What makes this type

Unlike the fire main and hydrants, which need a crew member to run out a hose, the accommodation sprinkler system is automatic: each head contains a heat-sensitive element that releases at a set temperature, opening only that head and the ones near it rather than flooding the whole system. It is required specifically for accommodation, service and control spaces because these are the areas most likely to be occupied and least likely to have someone standing by with a hose when a fire starts, typically at night.

Accommodation sprinkler system, flow diagram
Flow diagram of an accommodation sprinkler system showing the sprinkler pump filling the pressure tank, the distribution main through a section valve with flow switch to the sprinkler heads, and the flow switch signal to the fire alarm panel.

Legend

  1. Fire alarm panel
  2. distribution main to accommodation
  3. pressure tank
  4. section valve & flow switch
  5. Sprinkler pump
  6. sprinkler heads (heat-sensitive bulb)

Main components

Pressure tank

A charged tank, part air and part fresh water, that gives instant pressure to the first head that opens before the pump has time to start.

Sprinkler pump

Automatically starts on a pressure drop in the system to sustain flow once the tank's stored pressure is used up, and must be capable of running the system at its designed simultaneous head count.

Read the full guide

Sprinkler heads

Glass bulb or fusible link elements rated to open at a set temperature, chosen higher in spaces like galleys where ambient heat is naturally elevated so the head does not open on cooking heat alone.

Section valves and alarm panel

Each section of piping has an isolating valve and a flow switch that triggers an alarm at the bridge and a local indicator showing which section has activated, so the crew knows where to go without searching the ship.

Piping network

A dedicated, always-charged pipe run separate from the general fire main, sized so pressure and flow are maintained even with several heads open simultaneously in one section.

Selection / sizing

  • Number of sections and the largest number of heads expected to open together in one section sets pump capacity.
  • Head temperature rating matched to the space: standard rating for cabins and public rooms, higher rating for galleys and machinery adjacent spaces.
  • Pressure tank capacity, sized to bridge the gap before the pump reaches full pressure.
  • Corrosion-resistant piping given the system stands charged with water permanently, unlike a dry system.

Regulations / Class

SOLAS Ch. II-2 requires automatic sprinkler, fire detection and fire alarm systems in accommodation, service spaces and control stations on passenger ships and is applied to many cargo ship accommodation blocks as an alternative means of protection. The system must give an audible and visual alarm at a continuously manned station identifying the section, and class rules require periodic testing of pump start, pressure tank charge and section valve operation, verified at annual and renewal survey.

Typical faults

FaultCauseConsequence
Pressure tank low on chargeSlow air leak, not topped up at roundsDelay before pump starts, weak initial discharge
Section valve left shut after maintenanceNot reopened and logged after work on a branchWhole section unprotected without any alarm indication
Head painted overDeck maintenance painting overspray onto sprinkler headsHeat-sensitive element insulated, may fail to open
Pump fails to auto-startPressure switch fault or breaker left openSystem relies on tank pressure only, exhausted within minutes

What to look for in a supplier

  • Heads and valves with current type approval certificates matching the flag and class requirements, not just a generic fire sprinkler product.
  • Documented hydraulic calculation showing the pump and tank meet the simultaneous operation requirement for the largest section.
  • Spare heads held in the correct temperature ratings for each space category, not a single rating for the whole ship.

Never paint a sprinkler head during accommodation maintenance, and check the section valve log every time work is done on a branch line. An unlogged shut valve is the most common reason a sprinkler system fails to respond when it is actually needed.

Models

Models in this type.

The best-documented model of each manufacturer first, then the next — 2 of 2 models in Sprinkler System (Accommodation). Every row links to full specifications, documents and service notes.

Showing only Tyco / Johnson Controls. Show all manufacturers
By manufacturer

Manufacturers.

All 10 manufacturers with models of Sprinkler System (Accommodation). Names with a manufacturer page open it; the others open a search across the full library.

All manufacturers in the library
More than the data sheet shows

Write to us about this model — the answer comes by e-mail.

Name the make and the model and what the job is: a spare, a service call, a second opinion on a data sheet. We answer by e-mail.

No details at hand? A photo of the rating plate or the part is enough — simply attach it to the request.

Frequently asked

Questions that come up with this equipment.

Is Sprinkler System (Accommodation) data free?

Yes. Every model page, every guide and every datasheet for this type is readable without an account. An account adds saved searches and requests, nothing is taken away.

My model is missing — what now?

Send us the nameplate. We identify it by hand, add it to the library, and if you need a part or a service, the request is already on our desk.

Can you source a Sprinkler System (Accommodation) part?

Yes. Tell us the manufacturer, the model and what you need — a person reads every request and replies by e-mail.