The accommodation sprinkler system is an automatic, pressurised network that opens sprinkler heads by heat alone and starts extinguishing before the crew reaches the space, the one part of the ship's fire fighting outfit that acts without anyone touching a valve.
The 3 models with the most complete data of 3 in Sprinkler System (Accommodation). Every row links to full specifications, documents and service notes.
All 2 manufacturers with models of Sprinkler System (Accommodation). Every name opens a search across the full library.
The other equipment types in this category.
Unlike the fire main and hydrants, which need a crew member to run out a hose, the accommodation sprinkler system is automatic: each head contains a heat-sensitive element that releases at a set temperature, opening only that head and the ones near it rather than flooding the whole system. It is required specifically for accommodation, service and control spaces because these are the areas most likely to be occupied and least likely to have someone standing by with a hose when a fire starts, typically at night.
Unlike the fire main and hydrants, which need a crew member to run out a hose, the accommodation sprinkler system is automatic: each head contains a heat-sensitive element that releases at a set temperature, opening only that head and the ones near it rather than flooding the whole system. It is required specifically for accommodation, service and control spaces because these are the areas most likely to be occupied and least likely to have someone standing by with a hose when a fire starts, typically at night.
A charged tank, part air and part fresh water, that gives instant pressure to the first head that opens before the pump has time to start.
Automatically starts on a pressure drop in the system to sustain flow once the tank's stored pressure is used up, and must be capable of running the system at its designed simultaneous head count.
Glass bulb or fusible link elements rated to open at a set temperature, chosen higher in spaces like galleys where ambient heat is naturally elevated so the head does not open on cooking heat alone.
Each section of piping has an isolating valve and a flow switch that triggers an alarm at the bridge and a local indicator showing which section has activated, so the crew knows where to go without searching the ship.
A dedicated, always-charged pipe run separate from the general fire main, sized so pressure and flow are maintained even with several heads open simultaneously in one section.
SOLAS Ch. II-2 requires automatic sprinkler, fire detection and fire alarm systems in accommodation, service spaces and control stations on passenger ships and is applied to many cargo ship accommodation blocks as an alternative means of protection. The system must give an audible and visual alarm at a continuously manned station identifying the section, and class rules require periodic testing of pump start, pressure tank charge and section valve operation, verified at annual and renewal survey.
| Fault | Cause | Consequence |
|---|---|---|
| Pressure tank low on charge | Slow air leak, not topped up at rounds | Delay before pump starts, weak initial discharge |
| Section valve left shut after maintenance | Not reopened and logged after work on a branch | Whole section unprotected without any alarm indication |
| Head painted over | Deck maintenance painting overspray onto sprinkler heads | Heat-sensitive element insulated, may fail to open |
| Pump fails to auto-start | Pressure switch fault or breaker left open | System relies on tank pressure only, exhausted within minutes |
Never paint a sprinkler head during accommodation maintenance, and check the section valve log every time work is done on a branch line. An unlogged shut valve is the most common reason a sprinkler system fails to respond when it is actually needed.
Tell us the manufacturer, the model and what you need — a part, a service call, a second opinion. Our desk asks the right suppliers from a network of over 114,000 companies and comes back with a quote or a sourcing plan, not a search page.
Yes. Every model page, every guide and every datasheet for this type is readable without an account. An account adds saved searches and requests, nothing is taken away.
Send us the nameplate. We identify it by hand, add it to the library, and if you need a part or a service, the request is already on our desk.
Yes. Tell us the manufacturer, the model and what you need — our desk asks the right suppliers from a network of over 114,000 companies and comes back with a quote or a sourcing plan.