Library› Electrical› Battery & UPS Systems› Lithium-Ion Battery System (ESS)
Battery & UPS Systems

Lithium-Ion Battery System (ESS)

A lithium-ion ESS differs from a UPS in scale and purpose: a UPS bridges seconds of gap for critical loads, while an ESS can carry hotel load, peak-shave generators, or drive electric propulsion for extended periods.

Saft
Knowledge

What to check on a Lithium-Ion Battery System (ESS).

100 models from Saft in Lithium-Ion Battery System (ESS). Below: the full model list.

What Defines a Lithium-Ion Battery System

A marine lithium-ion energy storage system (ESS) is a battery installation built to supply or absorb significant electrical power over minutes to hours, not just the few seconds a conventional UPS bridges. It sits on the ship's power network through a power conversion system and is managed by a battery management system (BMS) that constantly tracks cell voltage, temperature and state of charge. What separates it from a simple UPS battery bank is scale and integration: an ESS can peak-shave generator load, provide spinning reserve for a diesel-electric plant, or in hybrid and full-electric vessels, drive propulsion directly, whereas a UPS exists purely to hold critical control and navigation circuits alive during a mains gap.

Lithium-ion battery system arrangement
Front view of a lithium-ion battery energy storage cabinet showing stacked battery modules, the battery management system, the main contactor, cooling air supply and the output connection to the switchboard or inverter.

Legend

  1. battery cabinet
  2. cooling air
  3. battery management system
  4. battery module
  5. main contactor
  6. to switchboard / inverter

Main components

Battery modules and racks

Lithium-ion cells, commonly NMC or LFP chemistry, grouped into modules and stacked in racks inside a dedicated, fire-rated battery room or containerised enclosure, each rack fitted with its own fusing and disconnect.

Battery management system

Monitors every cell or cell group for voltage, temperature and current, balances charge between cells, and can isolate a faulted module before a problem propagates through the rack.

Read the full guide

Power conversion system

Bidirectional inverters that convert the battery's DC to the ship's AC network and back, matching voltage and frequency during charge and discharge.

Thermal management and fire suppression

Air or liquid cooling keeps cells within their operating temperature band, and a dedicated fire detection and suppression system, often with gas venting to prevent an explosive atmosphere, protects against thermal runaway.

Selection and sizing

  • Usable energy capacity in kWh, sized for the intended duty: peak shaving, spinning reserve, zero-emission port stays, or propulsion
  • Power rating in kW of the power conversion system, which can be the limiting factor even when energy capacity is ample
  • Cell chemistry trade-off: LFP cells tolerate abuse and thermal stress better, NMC cells pack more energy into less volume and weight
  • Cycle life and expected degradation curve over the system's design life, since capacity fades with charge cycles
  • Space, weight and required fire-rated compartment volume, which on smaller vessels can be the deciding constraint

Class and regulatory requirements

Classification societies issue dedicated battery installation notations covering cell safety testing, battery room fire protection, ventilation to prevent gas accumulation, and segregation from other spaces. IMO interim guidelines for ships using lithium-ion battery technology, together with SOLAS Chapter II-2 fire safety provisions, shape the required fire detection, suppression and ventilation arrangements. Surveys include periodic BMS function checks, insulation resistance testing of the battery circuit, and inspection of the battery room's fire suppression and ventilation systems; class rules on many notations also require periodic capacity testing to confirm the system still meets its rated duty as it ages.

Typical faults

FaultCauseConsequence
Thermal runawayCell damage, internal short circuit, or cooling system failureRapid heat and gas release, risk of fire propagating cell to cell
Cell imbalanceBMS balancing circuit fault or aged, mismatched cellsReduced usable capacity, premature end-of-life on affected modules
Capacity fadeNormal cycling aging, accelerated by high temperature or deep dischargeSystem no longer meets its original duty, needs earlier module replacement
Ventilation or detection faultBlocked vents, disabled gas detectors after maintenanceUndetected gas buildup, explosion risk in a thermal event

What to look for in a supplier

  • Cell-level and system-level type approval from the relevant classification society, not just component certification
  • A documented thermal runaway propagation test for the specific rack design
  • Remote monitoring and diagnostic support, since early cell degradation is easier for the maker's software to catch than a crew visual check
  • Clear module replacement strategy and availability, since batteries are a wear item with a finite cycle life unlike most other electrical plant

Treat a single BMS module-isolation alarm as an event to log and investigate, not reset and forget; the BMS isolated that module because a cell parameter left its safe window, and the same trigger recurring days later on a different module often signals a rack-wide problem developing.

Models

Models in this type.

The best-documented model of each manufacturer first, then the next — 100 of 100 models in Lithium-Ion Battery System (ESS). Every row links to full specifications, documents and service notes.

Showing only Saft. Show all manufacturers
SaftFlex'ion 100 Marine LFP SaftFlex'ion 100 Marine NMC SaftFlex'ion 250 Marine NMC SaftFlex'ion 500 Marine LFP SaftFlex'ion 500 Marine NMC SaftSeanergy 1000 LFP SaftSeanergy 1000 NMC SaftSeanergy 1000kWh LFP 1000V SaftSeanergy 1000kWh LFP 400V SaftSeanergy 1000kWh LFP 700V SaftSeanergy 1000kWh NMC 1000V SaftSeanergy 1000kWh NMC 400V SaftSeanergy 1000kWh NMC 700V SaftSeanergy 100kWh LFP 1000V SaftSeanergy 100kWh LFP 400V SaftSeanergy 100kWh LFP 700V SaftSeanergy 100kWh NMC 1000V SaftSeanergy 100kWh NMC 400V SaftSeanergy 100kWh NMC 700V SaftSeanergy 1500kWh LFP 1000V SaftSeanergy 1500kWh LFP 400V SaftSeanergy 1500kWh LFP 700V SaftSeanergy 1500kWh NMC 1000V SaftSeanergy 1500kWh NMC 400V SaftSeanergy 1500kWh NMC 700V SaftSeanergy 150kWh LFP 1000V SaftSeanergy 150kWh LFP 400V SaftSeanergy 150kWh LFP 700V SaftSeanergy 150kWh NMC 1000V SaftSeanergy 150kWh NMC 400V SaftSeanergy 150kWh NMC 700V SaftSeanergy 200 LFP SaftSeanergy 200 NMC SaftSeanergy 2000 LFP SaftSeanergy 2000 NMC SaftSeanergy 2000kWh LFP 1000V SaftSeanergy 2000kWh LFP 400V SaftSeanergy 2000kWh LFP 700V SaftSeanergy 2000kWh NMC 1000V SaftSeanergy 2000kWh NMC 400V SaftSeanergy 2000kWh NMC 700V SaftSeanergy 200kWh LFP 1000V SaftSeanergy 200kWh LFP 400V SaftSeanergy 200kWh LFP 700V SaftSeanergy 200kWh NMC 1000V SaftSeanergy 200kWh NMC 400V SaftSeanergy 200kWh NMC 700V SaftSeanergy 3000kWh LFP 1000V SaftSeanergy 3000kWh LFP 400V SaftSeanergy 3000kWh LFP 700V SaftSeanergy 3000kWh NMC 1000V SaftSeanergy 3000kWh NMC 400V SaftSeanergy 3000kWh NMC 700V SaftSeanergy 300kWh LFP 1000V SaftSeanergy 300kWh LFP 400V SaftSeanergy 300kWh LFP 700V SaftSeanergy 300kWh NMC 1000V SaftSeanergy 300kWh NMC 400V SaftSeanergy 300kWh NMC 700V SaftSeanergy 400kWh LFP 1000V SaftSeanergy 400kWh LFP 400V SaftSeanergy 400kWh LFP 700V SaftSeanergy 400kWh NMC 1000V SaftSeanergy 400kWh NMC 400V SaftSeanergy 400kWh NMC 700V SaftSeanergy 500 LFP SaftSeanergy 500 NMC SaftSeanergy 5000 LFP SaftSeanergy 5000kWh LFP 1000V SaftSeanergy 5000kWh LFP 400V SaftSeanergy 5000kWh LFP 700V SaftSeanergy 5000kWh NMC 1000V SaftSeanergy 5000kWh NMC 400V SaftSeanergy 5000kWh NMC 700V SaftSeanergy 500kWh LFP 1000V SaftSeanergy 500kWh LFP 400V SaftSeanergy 500kWh LFP 700V SaftSeanergy 500kWh NMC 1000V SaftSeanergy 500kWh NMC 400V SaftSeanergy 500kWh NMC 700V SaftSeanergy 50kWh LFP 1000V SaftSeanergy 50kWh LFP 400V SaftSeanergy 50kWh LFP 700V SaftSeanergy 50kWh NMC 1000V SaftSeanergy 50kWh NMC 400V SaftSeanergy 50kWh NMC 700V SaftSeanergy 750kWh LFP 1000V SaftSeanergy 750kWh LFP 400V SaftSeanergy 750kWh LFP 700V SaftSeanergy 750kWh NMC 1000V SaftSeanergy 750kWh NMC 400V SaftSeanergy 750kWh NMC 700V SaftSeanergy 75kWh LFP 1000V SaftSeanergy 75kWh LFP 400V SaftSeanergy 75kWh LFP 700V SaftSeanergy 75kWh NMC 1000V SaftSeanergy 75kWh NMC 400V SaftSeanergy 75kWh NMC 700V SaftFlex'ion 250 Marine LFP SaftSeanergy 5000 NMC
100 models
Related types

Also in Battery & UPS Systems.

The other equipment types in this category.

Battery Management System (BMS)Battery/UPSLead-Acid Battery BankMarine Energy Storage SystemMarine UPSMarine UPS System
More than the data sheet shows

Write to us about this model — the answer comes by e-mail.

Name the make and the model and what the job is: a spare, a service call, a second opinion on a data sheet. We answer by e-mail.

No details at hand? A photo of the rating plate or the part is enough — simply attach it to the request.

Frequently asked

Questions that come up with this equipment.

Is Lithium-Ion Battery System (ESS) data free?

Yes. Every model page, every guide and every datasheet for this type is readable without an account. An account adds saved searches and requests, nothing is taken away.

My model is missing — what now?

Send us the nameplate. We identify it by hand, add it to the library, and if you need a part or a service, the request is already on our desk.

Can you source a Lithium-Ion Battery System (ESS) part?

Yes. Tell us the manufacturer, the model and what you need — a person reads every request and replies by e-mail.