Skip to content
OceanSphereENGINES
Library› Engine Room› Compressors› AC Compressor (for HVAC)
Compressors

AC Compressor (for HVAC)

An AC compressor for the accommodation HVAC system moves refrigerant, not air — it compresses refrigerant gas so the condenser can reject heat overboard, which makes it a completely different machine from the ship's air-start or service air compressors despite the shared name.

Daikin Marine
Knowledge

What to check on an AC Compressor (for HVAC).

1 models from Daikin Marine in AC Compressor (for HVAC). Below: the full model list.

What sets an HVAC compressor apart from other shipboard compressors

Starting air and service air compressors compress atmospheric air for pneumatic use. An HVAC compressor is a refrigeration compressor: it compresses a refrigerant gas (commonly R-134a or R-407C on older tonnage, R-513A or R-1234ze on newer installations moving away from higher-GWP refrigerants) as part of a closed vapour-compression cycle serving the accommodation air handling units. It never handles atmospheric air directly and runs in a sealed circuit with an evaporator, condenser and expansion device.

HVAC AC compressor refrigeration cycle
Refrigeration cycle of an HVAC AC compressor: the compressor sends hot refrigerant gas to the condenser, the expansion valve drops pressure into the evaporator, and cold suction gas returns to the compressor.

Legend

  1. condenser
  2. expansion valve
  3. liquid line
  4. cold refrigerant
  5. hot gas discharge
  6. suction line
  7. evaporator
  8. compressor

Main components

Compressor types in service

Reciprocating semi-hermetic compressors remain common on mid-size vessels for their serviceability — cylinder heads can be opened for valve work without breaking the refrigerant circuit at the crankcase. Scroll compressors appear on smaller accommodation plants for their lower vibration and fewer moving parts, but are fully hermetic and cannot be internally repaired on board; a failed scroll unit is replaced whole.

Crankcase heater and oil management

A crankcase heater keeps refrigerant from migrating into the oil during standstill, since refrigerant dissolved in oil on start-up causes violent foaming and can strip bearing lubrication in seconds. Oil separators downstream of the discharge return entrained oil to the crankcase rather than letting it circulate and coat the condenser and evaporator surfaces.

Read the full guide

Controls and safety cut-outs

High- and low-pressure switches, an oil differential pressure switch on larger units, and discharge temperature protection together stop the compressor before a fault develops into a burnout. These are not optional extras — a compressor running without working pressure protection is one blocked condenser away from a locked rotor.

Selection / sizing

  • Cooling load of the accommodation spaces served, in kW, against the compressor's rated capacity at the design condensing and evaporating temperatures.
  • Refrigerant type, driven by what is already in use on the vessel and by phase-down schedules for higher-GWP refrigerants that flag states are progressively adopting under the Montreal Protocol framework.
  • Semi-hermetic versus fully hermetic, weighed against the crew's ability to carry out valve or bearing work at sea versus simply carrying a spare unit.
  • Electrical supply — voltage, phase and starting current against the vessel's switchboard capacity, particularly for direct-on-line starts on larger units.

Regulations and class

MARPOL Annex VI and the Montreal Protocol/Kigali Amendment framework govern which refrigerants can be used and how leaks must be logged; vessels carrying more than a threshold refrigerant charge need a refrigerant management plan and log book entries for every top-up. Class rules require periodic survey of the HVAC system's pressure vessels and safety devices, and accommodation ventilation capacity itself is checked against SOLAS habitability requirements at build, though the compressor itself is not separately class-approved equipment in most cases.

Typical faults

FaultConsequence
Crankcase heater failed or left switched off during layupRefrigerant migrates into oil, causing violent foaming and bearing damage on the next start
Condenser sea water side fouled with marine growthHigh discharge pressure trips the compressor repeatedly or drives up power consumption
Refrigerant undercharge from a slow leakLow suction pressure causes short-cycling and eventual loss of cooling capacity
Moisture ingress after an open repair without proper evacuationAcid formation in the refrigerant circuit that attacks windings and can cause a burnout

What to look for in a supplier

  • Confirmed refrigerant compatibility with what is already charged in the system, since retrofitting a different refrigerant is a full re-commissioning job, not a drop-in swap.
  • Availability of spare valve plates and gaskets for semi-hermetic units, since a full replacement compressor is a significant spare part to carry.
  • Documentation for the vessel's refrigerant management plan and leak log, matched to flag state reporting requirements.
  • Electrical characteristics matched exactly to the existing starter and switchboard protection, not just the nameplate kW.

Never open a refrigerant circuit without recovering the charge into a certified cylinder first — venting refrigerant to atmosphere during a compressor swap is both an environmental discharge that must be logged and, on vapour-compression systems, an easy way to introduce moisture that ruins the repair.

Models

Models in this type.

The best-documented model of each manufacturer first, then the next — 1 of 1 models in AC Compressor (for HVAC). Every row links to full specifications, documents and service notes.

Showing only Daikin Marine. Show all manufacturers
By manufacturer

Manufacturers.

All 3 manufacturers with models of AC Compressor (for HVAC). Names with a manufacturer page open it; the others open a search across the full library.

All manufacturers in the library
More than the data sheet shows

Write to us about this model — the answer comes by e-mail.

Name the make and the model and what the job is: a spare, a service call, a second opinion on a data sheet. We answer by e-mail.

No details at hand? A photo of the rating plate or the part is enough — simply attach it to the request.

Frequently asked

Questions that come up with this equipment.

Is AC Compressor (for HVAC) data free?

Yes. Every model page, every guide and every datasheet for this type is readable without an account. An account adds saved searches and requests, nothing is taken away.

My model is missing — what now?

Send us the nameplate. We identify it by hand, add it to the library, and if you need a part or a service, the request is already on our desk.

Can you source a AC Compressor (for HVAC) part?

Yes. Tell us the manufacturer, the model and what you need — a person reads every request and replies by e-mail.