Power Generation

Generator Set

A generator set pairs a diesel engine with an AC alternator on one common bed to make the ship's electrical power independently of propulsion, unlike a shaft generator that only produces power while the main engine is turning.

10models
Vetus
Knowledge

What to check on a Generator Set.

10 models from Vetus in Generator Set. Below: the full model list.

What Makes a Generator Set Different

A generator set, or genset, is a diesel engine and a synchronous alternator built on one common bed, driven at a fixed speed and delivering three-phase AC power at the ship's supply voltage and frequency. It is self-contained and can be started, loaded and stopped independently of the propulsion plant. That sets it apart from a shaft generator, coupled to the main engine's reduction gear and only able to hold frequency while the vessel is under way at sufficient speed, and from the emergency generator, a dedicated, separately located unit sized only to cover safety loads after a blackout.

Generator set arrangement
Side view of a generator set showing the diesel engine and alternator joined by a flexible coupling on one common bedplate, with the terminal box, exhaust outlet, cooling water connections and anti-vibration mounts.

Most ships carry two to four gensets so load can be shared, one unit can be taken out for overhaul without losing redundancy, and sets can be run in parallel when peak load from cargo pumps, bow thruster or mooring winches exceeds what one machine can carry alone.

Read the full guide

Main Components

Prime mover

A medium-speed, four-stroke diesel engine, typically running 720-1000 rpm on a 50 Hz ship or 900-1200 rpm on 60 Hz, with rated speed chosen to divide evenly into the required frequency by the alternator's pole count.

Alternator

A brushless synchronous alternator with an automatic voltage regulator (AVR) that holds output voltage constant as load changes and supplies the excitation needed for parallel operation.

Governor

Controls fuel rack position to hold speed, and therefore frequency, within class limits under sudden load changes. Most newer installations use electronic governors integrated with the power management system rather than the older mechanical-hydraulic type.

Control and protection panel

Houses synchronizing equipment, protection relays for reverse power, overcurrent, earth fault and over/under frequency, and the interface to the ship's power management system (PMS).

Cooling, starting and exhaust

Jacket water and charge air cooling circuits, a compressed-air or electric starting system, and an exhaust line with silencer and, on newer tonnage, selective catalytic reduction (SCR) or exhaust gas recirculation (EGR) for NOx control.

Selection and Sizing

  • Rated output in kW at a stated power factor, usually 0.8, since alternators are rated in kVA
  • Voltage and frequency: 440 V / 60 Hz is common on many trading vessels, 690 V on ships with large electric propulsion or thruster loads
  • Number of sets versus redundancy required, balancing capital cost against the ability to lose one set and still cover essential load
  • Fuel flexibility: MDO/MGO only, dual-fuel capability, or heavy fuel oil capable with the necessary treatment plant

Regulations and Class

NOx emissions fall under MARPOL Annex VI and are certified per engine through an EIAPP certificate confirming compliance with the applicable Tier limit for the ship's construction date and operating area. Classification societies require that gensets can be paralleled safely, that load-sharing and load-shedding logic is proven, and that the vessel can recover from a full blackout within a defined time. Periodic survey covers governor response, protection relay testing and insulation resistance of the windings.

Typical Faults

FaultCauseConsequence
Wet stackingProlonged running at low load, common when oversized sets cover light harbour loadUnburnt fuel and carbon foul the turbocharger, exhaust and injectors
Failed synchronizing or reverse power tripGovernor droop mismatch or AVR fault between paralleled setsSet trips offline, remaining sets can overload, risk of blackout
High jacket water temperature alarmCooler fouling or seawater pump failureAutomatic load reduction or shutdown to prevent engine damage
Falling insulation resistanceMoisture or oil vapour ingress into alternator windingsEarth fault trip, risk of winding failure if not dried out and corrected

What to Look for in a Supplier

  • Engine and alternator already offered as a matched, type-tested package rather than assembled from unrelated components
  • Valid EIAPP certification for the NOx tier the ship needs, with documentation the flag state will accept
  • A service and spares network reaching the vessel's actual trading area, not just the country of manufacture
  • Published noise and vibration data compatible with the engine room's resilient mounting arrangement
  • A control system that integrates cleanly with the vessel's existing power management system

A genset that spends most of its life lightly loaded in port will foul faster than one working near its rated output; rotating duty between sets and avoiding permanent light-load running on one machine saves far more maintenance than any oil additive.

Models

Models in this type.

The best-documented model of each manufacturer first, then the next — 10 of 10 models in Generator Set. Every row links to full specifications, documents and service notes.

Showing only Vetus. Show all manufacturers
By manufacturer

Manufacturers.

All 52 manufacturers with models of Generator Set. Names with a manufacturer page open it; the others open a search across the full library.

All manufacturers
Show all 52 manufacturers
Related types

Also in Power Generation.

The other equipment types in this category.

Automatic Voltage Regulator (AVR)Emergency SwitchboardGas TurbineGas Turbine Enclosure / Control SystemGenset Controller / SynchronizerMarine Generator / AlternatorShaft Generator / PTOShore Connection BoxSteam Turbine
Would you like to know more?

One request. A person reads it and replies by e-mail.

Tell us the manufacturer, the model and what you need — a part, a service call, a second opinion. A person reads every request and replies by e-mail.

No details at hand? A photo of the rating plate or the part is enough — simply attach it to the request.

Frequently asked

Three things people ask first.

Is Generator Set data free?

Yes. Every model page, every guide and every datasheet for this type is readable without an account. An account adds saved searches and requests, nothing is taken away.

My model is missing — what now?

Send us the nameplate. We identify it by hand, add it to the library, and if you need a part or a service, the request is already on our desk.

Can you source a Generator Set part?

Yes. Tell us the manufacturer, the model and what you need — a person reads every request and replies by e-mail.