"> Emergency Switchboard - Equipment Database

Emergency Switchboard

critical IMO Required 2 models total

The emergency switchboard carries only the loads SOLAS requires after a blackout - steering gear, emergency lighting, fire pumps and communications - and is fed exclusively by the emergency generator or the emergency battery, never in parallel with the main switchboard.

Read more — Emergency Switchboard explained

What makes the emergency switchboard different

The emergency switchboard is not a smaller copy of the main switchboard. It is a physically separate panel, normally located above the bulkhead deck outside the machinery space, that stays energised only from the emergency generator or the transitional battery source. Under normal sea conditions it is fed from the main switchboard through a bus-tie breaker, but that link is the one connection that must never allow the two sources to run in parallel, because an out-of-phase closure between main and emergency supply can damage both switchboards in a single event. On loss of main power the bus-tie opens automatically and the emergency generator, or the battery bank while the generator starts, picks up the connected loads.

Emergency switchboard, single-line diagram
Single-line diagram of the emergency switchboard fed by the emergency generator or emergency battery through a bus-tie to the main switchboard, feeding steering gear, emergency lighting, the fire pump and radio equipment.

Main components

Incoming feeders

Two incoming breakers: one from the emergency generator, one from the main switchboard through the bus-tie. Only one can be closed at a time, enforced by mechanical or electrical interlock, never by procedure alone.

Transitional source

A battery bank, or a UPS in newer installations, that carries emergency lighting, navigation lights, the general alarm and internal communication for the period between blackout and the generator reaching full voltage and frequency.

Outgoing feeders

Dedicated circuits for the emergency fire pump, steering gear, emergency lighting circuits, navigation lights, watertight door indication, general alarm, VDR and the radio installation. Each circuit is sized and protected independently so a fault on one does not pull down the others.

Protection and monitoring

Voltmeter, frequency meter, insulation monitoring device and protective relays for the incoming feeders. Insulation monitoring matters more here than on the main board because the emergency switchboard often sits in a damp, unheated space, and a slow insulation fault can go unnoticed until the one moment the board is needed.

Sizing and load selection

The starting point is the SOLAS emergency load list: every consumer that must run after a blackout, for how long, and whether it needs the transitional source or can wait for the generator. Cargo ships are generally expected to sustain the emergency load for a minimum period in the order of 36 hours, with the emergency generator required to pick up automatically within about 45 seconds of a blackout. The transitional battery source has to bridge that gap for lighting, alarms and communications without any manual switching. Sizing the switchboard means totalling the connected emergency load with a margin for future additions, then choosing bus bar rating, breaker interrupting capacity and cable cross-sections to match, not the other way round.

Regulations and class

SOLAS Chapter II-1 sets out the requirements for the emergency source of electrical power, the transitional source, and the loads that must be connected. Class societies add their own survey items: functional tests of automatic start and changeover, periodic load tests of the emergency generator under the emergency switchboard, and insulation resistance checks. Surveyors will specifically ask to see the bus-tie interlock demonstrated, not just described on a drawing.

Typical faults

FaultConsequence
Bus-tie interlock defeated or bypassedMain and emergency source can be closed in parallel out of phase, risking a short circuit that damages both switchboards
Battery charger failed or battery bank sulphatedTransitional source cannot bridge the gap before the generator picks up; lighting and alarms drop out at blackout
Emergency load list grown without recalculationGenerator and switchboard undersized for actual connected load, tripping on overload during a real blackout test
Insulation resistance degraded from a damp generator roomNuisance earth fault alarms, and in the worst case a fault that only shows up when the board is loaded

What to look for in a supplier

  • Type-approved switchgear with class certification for the specific vessel type, not a generic industrial panel relabelled for marine use
  • A documented, interlocked changeover scheme with drawings that match what is actually installed, not just the original design intent
  • IP rating and corrosion protection suited to an emergency generator room, which is rarely climate controlled
  • Spare breaker ways and bus bar capacity for load growth over the vessel's life, since retrofitting a full emergency switchboard later is far more disruptive than sizing it correctly once

Testing the generator start proves only half the system; ask when the transitional battery source was last load tested under an actual blackout simulation, because a flat battery bank behind a perfectly running generator still leaves the ship dark for the first thirty to forty-five seconds.

5 yr
Class Survey
30 yr
Typical Lifetime

Typical Manufacturers

ABB Siemens Schneider Electric

2 manufacturers · 2 models

ABB Marine

1
ABB Marine Emergency Switchboard
Emergency Switchboard
Standard Compliance
SOLAS II-1/41, IEC 60092-302
Auto-Changeover Time
<45 s
Voltage
230 / 440 V AC
Supply Sources
Emergency genset + battery
Loads
Steering, nav lights, comms, fire pumps

Kongsberg

1
Kongsberg Maritime AS Kongsberg Low Voltage Switchboard 800X
Kongsberg Low Voltage Switchboard 800X
Per ship electrical load analysis · Electrical Power Generation · Low-voltage emergency power distribution switchboard
Common Failures & Inspection Points
  • Generatorwicklung-Isolationsdegradation
  • AVR Spannungsregler-Fehlfunktion
  • Kupplung Schwingungsdämpfer Verschleiß
  • Gleichstrommaschine Bürstenverschleiß
Service: Generator-Isolationstest jährlich. AVR-Kalibrierung jährlich. Kupplung-Inspektion alle 5 Jahre. Ölwechsel per Herstellerangabe.
Spare Parts: Ersatzteile über Kongsberg Maritime AS oder zugelassene Vertriebspartner. Lead time: 2-6 Wochen.
Strengths
  • Integrated protection and monitoring functions reduce wiring complexity
  • Modular design allows easy expansion or reconfiguration on board
  • High reliability with proven Kongsberg components and DNV approval
  • Compact footprint suitable for space‑constrained vessels
  • Standardized interfaces simplify integration with existing Kongsberg automation systems
Weaknesses
  • Limited to low‑voltage applications (≤690 V), not suitable for high‑power main distribution
  • Higher initial capital cost compared with generic OEM switchboards
  • Spare parts and service are tied to Kongsberg’s global support network, which may affect lead times in remote regions
  • Requires specific training for optimal operation and maintenance
Typical Vessels: Offshore supply vesselPlatform supply vesselFerryCruise shipNaval auxiliary
Certifications: DNV
Decision Guide: Choose if you need a reliable, compact emergency power distribution system with built‑in monitoring and you already use Kongsberg automation or value DNV‑approved equipment. Avoid if your vessel operates on a tight budget, requires high‑voltage main distribution, or you prefer a vendor‑agnostic solution with broader aftermarket support.
Use Cases: The 800X is typically installed to feed essential ship services such as navigation equipment, fire‑pump systems, emergency lighting and communication gear from standby generators, ensuring compliance with SOLAS emergency power requirements.