Emergency Switchboard
The emergency switchboard carries only the loads SOLAS requires after a blackout - steering gear, emergency lighting, fire pumps and communications - and is fed exclusively by the emergency generator or the emergency battery, never in parallel with the main switchboard.
Read more — Emergency Switchboard explained ▾
What makes the emergency switchboard different
The emergency switchboard is not a smaller copy of the main switchboard. It is a physically separate panel, normally located above the bulkhead deck outside the machinery space, that stays energised only from the emergency generator or the transitional battery source. Under normal sea conditions it is fed from the main switchboard through a bus-tie breaker, but that link is the one connection that must never allow the two sources to run in parallel, because an out-of-phase closure between main and emergency supply can damage both switchboards in a single event. On loss of main power the bus-tie opens automatically and the emergency generator, or the battery bank while the generator starts, picks up the connected loads.
Main components
Incoming feeders
Two incoming breakers: one from the emergency generator, one from the main switchboard through the bus-tie. Only one can be closed at a time, enforced by mechanical or electrical interlock, never by procedure alone.
Transitional source
A battery bank, or a UPS in newer installations, that carries emergency lighting, navigation lights, the general alarm and internal communication for the period between blackout and the generator reaching full voltage and frequency.
Outgoing feeders
Dedicated circuits for the emergency fire pump, steering gear, emergency lighting circuits, navigation lights, watertight door indication, general alarm, VDR and the radio installation. Each circuit is sized and protected independently so a fault on one does not pull down the others.
Protection and monitoring
Voltmeter, frequency meter, insulation monitoring device and protective relays for the incoming feeders. Insulation monitoring matters more here than on the main board because the emergency switchboard often sits in a damp, unheated space, and a slow insulation fault can go unnoticed until the one moment the board is needed.
Sizing and load selection
The starting point is the SOLAS emergency load list: every consumer that must run after a blackout, for how long, and whether it needs the transitional source or can wait for the generator. Cargo ships are generally expected to sustain the emergency load for a minimum period in the order of 36 hours, with the emergency generator required to pick up automatically within about 45 seconds of a blackout. The transitional battery source has to bridge that gap for lighting, alarms and communications without any manual switching. Sizing the switchboard means totalling the connected emergency load with a margin for future additions, then choosing bus bar rating, breaker interrupting capacity and cable cross-sections to match, not the other way round.
Regulations and class
SOLAS Chapter II-1 sets out the requirements for the emergency source of electrical power, the transitional source, and the loads that must be connected. Class societies add their own survey items: functional tests of automatic start and changeover, periodic load tests of the emergency generator under the emergency switchboard, and insulation resistance checks. Surveyors will specifically ask to see the bus-tie interlock demonstrated, not just described on a drawing.
Typical faults
| Fault | Consequence |
|---|---|
| Bus-tie interlock defeated or bypassed | Main and emergency source can be closed in parallel out of phase, risking a short circuit that damages both switchboards |
| Battery charger failed or battery bank sulphated | Transitional source cannot bridge the gap before the generator picks up; lighting and alarms drop out at blackout |
| Emergency load list grown without recalculation | Generator and switchboard undersized for actual connected load, tripping on overload during a real blackout test |
| Insulation resistance degraded from a damp generator room | Nuisance earth fault alarms, and in the worst case a fault that only shows up when the board is loaded |
What to look for in a supplier
- Type-approved switchgear with class certification for the specific vessel type, not a generic industrial panel relabelled for marine use
- A documented, interlocked changeover scheme with drawings that match what is actually installed, not just the original design intent
- IP rating and corrosion protection suited to an emergency generator room, which is rarely climate controlled
- Spare breaker ways and bus bar capacity for load growth over the vessel's life, since retrofitting a full emergency switchboard later is far more disruptive than sizing it correctly once
Testing the generator start proves only half the system; ask when the transitional battery source was last load tested under an actual blackout simulation, because a flat battery bank behind a perfectly running generator still leaves the ship dark for the first thirty to forty-five seconds.
Typical Manufacturers
2 manufacturers · 2 models
ABB Marine
1
Kongsberg
1
- Generatorwicklung-Isolationsdegradation
- AVR Spannungsregler-Fehlfunktion
- Kupplung Schwingungsdämpfer Verschleiß
- Gleichstrommaschine Bürstenverschleiß
- Integrated protection and monitoring functions reduce wiring complexity
- Modular design allows easy expansion or reconfiguration on board
- High reliability with proven Kongsberg components and DNV approval
- Compact footprint suitable for space‑constrained vessels
- Standardized interfaces simplify integration with existing Kongsberg automation systems
- Limited to low‑voltage applications (≤690 V), not suitable for high‑power main distribution
- Higher initial capital cost compared with generic OEM switchboards
- Spare parts and service are tied to Kongsberg’s global support network, which may affect lead times in remote regions
- Requires specific training for optimal operation and maintenance