A motor starter is the switching and protection package that closes the circuit to a motor on command and opens it again the instant an overcurrent, undervoltage or single-phasing condition appears, while a contactor by itself is only the switching element with no built-in protection.

4models
Vetus
Knowledge

What to check on a Motor Starter / Contactor.

4 models from Vetus in Motor Starter / Contactor. Below: the full model list.

What makes a starter different from a bare contactor

A contactor is an electrically operated switch: a coil pulls in a set of main contacts to make or break a three-phase circuit, nothing more. A motor starter combines that contactor with protection, most commonly a thermal overload relay wired in series with the motor's current path, plus the control wiring for start/stop pushbuttons, interlocks, and status feedback to the switchboard or automation system. Direct-on-line, star-delta and soft starters are all built around this same contactor-plus-protection core; what changes between them is how much inrush current and torque the motor sees at the moment of starting.

Motor starter and contactor circuit
Schematic of a direct-on-line motor starter showing the three-phase supply through the contactor main contacts and overload relay to the motor, with the control circuit coil, start and stop stations and the holding contact.
Read the full guide

Main components

Contactor

Sized by rated operational current (AC-3 duty for motor loads) and by pole count, with an auxiliary contact block usually added for interlocking and remote indication.

Overload relay

Thermal or electronic, set to the motor's full load current and service factor; it trips on a sustained overcurrent that a fuse or breaker would be too slow, or not sensitive enough, to catch.

Short-circuit protection

A motor circuit breaker or fuses upstream of the contactor clear a true short circuit far faster than the thermal overload can react, and the two are sized to coordinate rather than duplicate each other.

Star-delta or soft-start components

Where fitted, a second and third contactor (star-delta) or a solid-state voltage ramp module (soft starter) reduce starting current, at the cost of reduced starting torque, for larger motors where a direct-on-line start would sag the switchboard bus.

Selection and sizing

The starter must be matched to the motor's full load current, starting current multiple, duty class (continuous, intermittent, or frequent reversing), and the switchboard's fault level for the short-circuit device. AC-3 utilisation category current rating is the figure to check against the motor nameplate, not the contactor's resistive AC-1 rating, which is always higher and misleading if used for sizing.

Regulations and class

  • Class rules require motor circuits to carry both overload and short-circuit protection, and essential service motors to have specific alarm and, where required, automatic restart arrangements after a blackout.
  • SOLAS Ch. II-1 requirements for essential auxiliaries (steering gear, fire pumps, emergency equipment) drive which starters need duplicated supplies or automatic changeover rather than manual restart only.
  • Periodic testing of overload relay trip settings and protection relay function is checked at survey, typically confirmed by primary or secondary injection testing during major surveys.

Typical faults

FaultConsequence
Contactor main contacts pitted or welded from repeated interruption of starting currentMotor fails to stop on command, or one phase fails to make, causing single-phasing
Overload relay set above actual motor full load currentProtection no longer trips before winding damage on a developing fault, defeating the purpose of the relay
Coil burnt from undervoltage chatter during a switchboard disturbanceStarter drops out and will not re-energise until the coil is replaced, taking an essential auxiliary offline
Star-delta timer misadjustedTransition happens too early (high current transient) or too late (unnecessary time at reduced torque), stressing both motor and starter

What to look for in a supplier

  • Contactor and overload relay rated for the actual AC-3 duty current, with a documented coordination table against the upstream breaker or fuses.
  • Spares availability for the exact overload relay type fitted, since electronic overload modules are rarely interchangeable across manufacturers.
  • Type-tested motor control centre assemblies where required by class, rather than field-built panels with no assembly-level test certificate.
  • Clear marking of AC-3 versus AC-1 ratings on the datasheet, since this figure is the most common source of undersized replacement starters.

When replacing a starter after a trip, check the overload relay setting against the motor nameplate before re-energising; a starter swapped in a hurry with the previous relay setting left unchanged is a common cause of a repeat winding failure weeks later.

Models

Models in this type.

The best-documented model of each manufacturer first, then the next — 4 of 4 models in Motor Starter / Contactor. Every row links to full specifications, documents and service notes.

Showing only Vetus. Show all manufacturers
4 models
By manufacturer

Manufacturers.

All 28 manufacturers with models of Motor Starter / Contactor. Names with a manufacturer page open it; the others open a search across the full library.

All manufacturers
Related types

Also in Motor Control.

The other equipment types in this category.

Direct Online Starter (DOL)Electric MotorFrequency Converter / VFDMotor Protection SwitchSoft Starter
Would you like to know more?

One request. A person reads it and replies by e-mail.

Tell us the manufacturer, the model and what you need — a part, a service call, a second opinion. A person reads every request and replies by e-mail.

No details at hand? A photo of the rating plate or the part is enough — simply attach it to the request.

Frequently asked

Three things people ask first.

Is Motor Starter / Contactor data free?

Yes. Every model page, every guide and every datasheet for this type is readable without an account. An account adds saved searches and requests, nothing is taken away.

My model is missing — what now?

Send us the nameplate. We identify it by hand, add it to the library, and if you need a part or a service, the request is already on our desk.

Can you source a Motor Starter / Contactor part?

Yes. Tell us the manufacturer, the model and what you need — a person reads every request and replies by e-mail.