Library Electrical Motor Control Direct Online Starter (DOL)
Motor Control

Direct Online Starter (DOL)

A direct online starter connects a motor straight to full supply voltage in one step, giving full starting torque immediately but drawing five to eight times full-load current, which is why it is only used where the supply and the driven load can absorb that inrush.

111models 4manufacturers
Models

Models in this type.

The 100 models with the most complete data of 111 in Direct Online Starter (DOL). Every row links to full specifications, documents and service notes.

ABB MarineDOL AF09 0.37kW 400V Marine ABB MarineDOL AF09 0.37kW 440V Marine ABB MarineDOL AF09 0.37kW 690V Marine ABB MarineDOL AF09 0.75kW 400V Marine ABB MarineDOL AF09 0.75kW 440V Marine ABB MarineDOL AF09 0.75kW 690V Marine ABB MarineDOL AF16 1.5kW 400V Marine ABB MarineDOL AF16 1.5kW 440V Marine ABB MarineDOL AF16 1.5kW 690V Marine ABB MarineDOL AF16 2.2kW 400V Marine ABB MarineDOL AF16 2.2kW 440V Marine ABB MarineDOL AF16 2.2kW 690V Marine ABB MarineDOL AF26 4kW 400V Marine ABB MarineDOL AF26 4kW 440V Marine ABB MarineDOL AF26 4kW 690V Marine ABB MarineDOL AF26 5.5kW 400V Marine ABB MarineDOL AF26 5.5kW 440V Marine ABB MarineDOL AF26 5.5kW 690V Marine ABB MarineDOL AF40 11kW 400V Marine ABB MarineDOL AF40 11kW 440V Marine ABB MarineDOL AF40 11kW 690V Marine ABB MarineDOL AF40 7.5kW 400V Marine ABB MarineDOL AF40 7.5kW 440V Marine ABB MarineDOL AF40 7.5kW 690V Marine ABB MarineDOL AF65 15kW 400V Marine ABB MarineDOL AF65 15kW 440V Marine ABB MarineDOL AF65 15kW 690V Marine ABB MarineDOL AF65 22kW 400V Marine ABB MarineDOL AF65 22kW 440V Marine ABB MarineDOL AF65 22kW 690V Marine MitsubishiFR-A800 0.4kW Marine 400V Marine MitsubishiFR-A800 0.4kW Marine 440V Marine MitsubishiFR-A800 0.4kW Marine 690V Marine MitsubishiFR-A800 0.75kW Marine 400V Marine MitsubishiFR-A800 0.75kW Marine 440V Marine MitsubishiFR-A800 0.75kW Marine 690V Marine MitsubishiFR-A800 1.5kW Marine 400V Marine MitsubishiFR-A800 1.5kW Marine 440V Marine MitsubishiFR-A800 1.5kW Marine 690V Marine MitsubishiFR-A800 11kW Marine 400V Marine MitsubishiFR-A800 11kW Marine 440V Marine MitsubishiFR-A800 11kW Marine 690V Marine MitsubishiFR-A800 15kW Marine 400V Marine MitsubishiFR-A800 15kW Marine 440V Marine MitsubishiFR-A800 15kW Marine 690V Marine MitsubishiFR-A800 2.2kW Marine 400V Marine MitsubishiFR-A800 2.2kW Marine 440V Marine MitsubishiFR-A800 2.2kW Marine 690V Marine MitsubishiFR-A800 3.7kW Marine 400V Marine MitsubishiFR-A800 3.7kW Marine 440V Marine MitsubishiFR-A800 3.7kW Marine 690V Marine MitsubishiFR-A800 5.5kW Marine 400V Marine MitsubishiFR-A800 5.5kW Marine 440V Marine MitsubishiFR-A800 5.5kW Marine 690V Marine MitsubishiFR-A800 7.5kW Marine 400V Marine MitsubishiFR-A800 7.5kW Marine 440V Marine MitsubishiFR-A800 7.5kW Marine 690V Marine Rockwell/AB MarinePowerFlex 40P 11kW 400V Marine Rockwell/AB MarinePowerFlex 40P 11kW 440V Marine Rockwell/AB MarinePowerFlex 40P 11kW 690V Marine Rockwell/AB MarinePowerFlex 40P 15kW 400V Marine Rockwell/AB MarinePowerFlex 40P 15kW 440V Marine Rockwell/AB MarinePowerFlex 40P 15kW 690V Marine Rockwell/AB MarinePowerFlex 40P 4kW 400V Marine Rockwell/AB MarinePowerFlex 40P 4kW 440V Marine Rockwell/AB MarinePowerFlex 40P 4kW 690V Marine Rockwell/AB MarinePowerFlex 40P 5.5kW 400V Marine Rockwell/AB MarinePowerFlex 40P 5.5kW 440V Marine Rockwell/AB MarinePowerFlex 40P 5.5kW 690V Marine Rockwell/AB MarinePowerFlex 40P 7.5kW 400V Marine Rockwell/AB MarinePowerFlex 40P 7.5kW 440V Marine Rockwell/AB MarinePowerFlex 40P 7.5kW 690V Marine Rockwell/AB MarinePowerFlex 4M 0.4kW 400V Marine Rockwell/AB MarinePowerFlex 4M 0.4kW 440V Marine Rockwell/AB MarinePowerFlex 4M 0.4kW 690V Marine Rockwell/AB MarinePowerFlex 4M 0.75kW 400V Marine Rockwell/AB MarinePowerFlex 4M 0.75kW 440V Marine Rockwell/AB MarinePowerFlex 4M 0.75kW 690V Marine Rockwell/AB MarinePowerFlex 4M 1.5kW 400V Marine Rockwell/AB MarinePowerFlex 4M 1.5kW 440V Marine Rockwell/AB MarinePowerFlex 4M 1.5kW 690V Marine Rockwell/AB MarinePowerFlex 4M 2.2kW 400V Marine Rockwell/AB MarinePowerFlex 4M 2.2kW 440V Marine Rockwell/AB MarinePowerFlex 4M 2.2kW 690V Marine Siemens MarineDOL 0.37kW 400V Marine Siemens MarineDOL 0.37kW 440V Marine Siemens MarineDOL 0.37kW 690V Marine Siemens MarineDOL 0.75kW 400V Marine Siemens MarineDOL 0.75kW 440V Marine Siemens MarineDOL 0.75kW 690V Marine Siemens MarineDOL 1.5kW 400V Marine Siemens MarineDOL 1.5kW 440V Marine Siemens MarineDOL 1.5kW 690V Marine Siemens MarineDOL 11kW 400V Marine Siemens MarineDOL 11kW 440V Marine Siemens MarineDOL 11kW 690V Marine Siemens MarineDOL 15kW 400V Marine Siemens MarineDOL 15kW 440V Marine Siemens MarineDOL 15kW 690V Marine Siemens MarineDOL 2.2kW 400V Marine
By manufacturer

Manufacturers.

All 4 manufacturers with models of Direct Online Starter (DOL). Every name opens a search across the full library.

Related types

Also in Motor Control.

The other equipment types in this category.

Frequency Converter / VFDMotor Protection SwitchMotor Starter / ContactorSoft Starter
Knowledge

What to check on a Direct Online Starter (DOL).

A DOL starter is the simplest motor control arrangement on the ship: a contactor and overload relay, nothing more. Close the contactor and the motor sees full line voltage immediately, developing full starting torque from the first instant, which suits loads that need torque right away such as small pumps and fans. The cost of that simplicity is the inrush current, typically five to eight times the motor's rated current for a second or two, which stresses the supply switchboard and can cause a visible voltage dip that affects other…

What Sets Direct Online Starting Apart

A DOL starter is the simplest motor control arrangement on the ship: a contactor and overload relay, nothing more. Close the contactor and the motor sees full line voltage immediately, developing full starting torque from the first instant, which suits loads that need torque right away such as small pumps and fans. The cost of that simplicity is the inrush current, typically five to eight times the motor's rated current for a second or two, which stresses the supply switchboard and can cause a visible voltage dip that affects other equipment on the same bus. Star-delta and soft starters exist precisely to avoid that inrush; DOL is chosen instead when the motor is small enough, relative to the generator capacity, that the dip is acceptable, or when the driven load genuinely needs full torque at zero speed.

Direct online starter, control schema
One-line schema of a direct online starter: three-phase supply through a circuit breaker and a three-pole contactor with thermal overload relay to the motor, and the control circuit with stop, start and hold-in contacts operating the contactor coil.

Main Components

Main Contactor

An electromagnetically operated switch that connects the three motor phases to the supply, sized by current rating and utilization category for motor duty.

Thermal Overload Relay

A protective device that trips the contactor if motor current stays above the set threshold for longer than its time-current curve allows, protecting the winding from a stalled rotor or prolonged overload.

Short-Circuit Protection

A fuse or motor circuit breaker upstream of the contactor that clears a fault current far faster than the overload relay is designed to.

Control Circuit

Start and stop pushbuttons, a holding contact that latches the contactor closed after the start button is released, and any interlocks from the process, such as a low-level cutout on a pump.

Selection and Sizing

  • Motor full-load current and starting current, which set both the contactor rating and the overload relay range.
  • Generator or switchboard capacity to absorb the starting inrush without an unacceptable voltage dip to other loads.
  • Duty cycle of the driven equipment, since frequent starts shorten contactor contact life faster than continuous running would suggest.
  • Coordination between the overload relay curve and the upstream short-circuit protection, so the two devices do not both try to clear the same fault.

Regulations and Class

Motor starters for essential services fall under class electrical installation rules covering protection coordination, short-circuit withstand and the requirement for independent overload and short-circuit protection on each motor circuit. Where the motor drives an essential auxiliary, class rules typically require the starter circuit to be arranged so a fault on one motor circuit does not disable protection on others sharing the same switchboard section. There is no IMO instrument specific to starter type; the governing requirements come through the classification society's electrical installation rules.

Typical Faults

FaultCauseConsequence
Contactor contact weldingRepeated starts under high inrush, or attempting to interrupt a fault currentMotor cannot be stopped from the control circuit, contactor must be replaced
Nuisance overload trippingOverload relay set below actual full-load current, or a genuinely tight bearingUnplanned stoppage of the driven pump or fan
Failure to trip on locked rotorOverload relay incorrectly sized or bypassedWinding burnout on a stalled motor
Chattering contactorLow control voltage or a loose control circuit connectionContact erosion and eventual failure to hold the motor running

What to Look for in a Supplier

  • Contactor utilization category rated for motor starting duty, not a general-purpose switching category.
  • Overload relay range that actually covers the motor's full-load current with margin, confirmed against the motor nameplate, not the starter's default range.
  • Enclosure rating matched to the installation location, since engine room and deck locations have different ingress protection needs.
  • Spare contactor and overload relay availability, since these are the components most likely to need replacement over the equipment's life.

Before blaming the motor for a trip, check whether the overload relay is actually set to the motor's nameplate current; a mismatched relay setting causes more nuisance trips than any winding fault.

Search by manufacturer AFRISOWISKASwagelokAlfa Laval S.p.A.MAN Energy SolutionsWärtsiläEndress+HauserABB MarineAlfa LavalMacGregorNovenco MarineCarrier MarineSiemens MarineHeinen & HopmanDaikin Marine
Would you like to know more?

One request. A person answers within 24 hours on working days.

Tell us the manufacturer, the model and what you need — a part, a service call, a second opinion. Our desk asks the right suppliers from a network of over 114,000 companies and comes back with a quote or a sourcing plan, not a search page.

Frequently asked

Three things people ask first.

Is Direct Online Starter (DOL) data free?

Yes. Every model page, every guide and every datasheet for this type is readable without an account. An account adds saved searches and requests, nothing is taken away.

My model is missing — what now?

Send us the nameplate. We identify it by hand, add it to the library, and if you need a part or a service, the request is already on our desk.

Can you source a Direct Online Starter (DOL) part?

Yes. Tell us the manufacturer, the model and what you need — our desk asks the right suppliers from a network of over 114,000 companies and comes back with a quote or a sourcing plan.