Power Distribution

Main Switchboard (MV)

Medium-voltage main switchboards, typically 3.3 kV, 6.6 kV or 11 kV, use vacuum or SF6 circuit breakers instead of the air-break contactors found on low-voltage boards, because fault energy at these voltages will destroy standard LV gear and can injure anyone standing in front of it.

ABB
Knowledge

What to check on a Main Switchboard (MV).

1 models from ABB in Main Switchboard (MV). Below: the full model list.

What sets MV switchgear apart

Low-voltage boards at 400-690 V handle most auxiliary loads on a ship, but once installed generator output climbs past roughly 3-4 MW per set, cable cross-sections and transformer counts at LV become impractical. Cruise ships, LNG carriers, large offshore vessels and some ice-class ships generate and distribute at medium voltage instead, then step down locally to 440 V or 690 V near the consumers. The switchgear itself is a different class of equipment: breakers interrupt fault currents in a vacuum bottle or SF6 chamber rather than in open air, compartments are segregated to contain an internal arc, and every operation is mechanically interlocked because a mistake at these voltages is rarely survivable for the person making it.

Medium-voltage main switchboard
Front schematic of a medium-voltage main switchboard: busbar along the top feeding an incoming generator cubicle, a bus-tie and outgoing feeder cubicles, each with a vacuum circuit breaker, with CT/VT and protection relay on the incoming panel.

Legend

  1. busbar (MV copper bar)
  2. vacuum circuit breaker
  3. CT / VT
  4. protection relay
  5. incoming feeder (generator)
  6. bus-tie breaker
  7. outgoing feeder
  8. outgoing feeder

Main components

Circuit breakers

Withdrawable vacuum or SF6 breakers mounted on a truck that racks in and out of the cubicle. Vacuum is the dominant technology on new tonnage; SF6 is still found on older or offshore-derived designs.

Busbar system

Copper or aluminium busbars run the length of the board, split into a port and starboard half joined by a bus-tie breaker so the board can be operated as two independent sections.

Read the full guide

Protection relays

Numerical relays handle overcurrent, earth fault, differential and, on generator incomers, reverse power and loss-of-excitation protection, tripping the associated breaker within a coordinated time grading scheme.

Instrument transformers

Current and voltage transformers feed both the protection relays and the metering/SCADA system; their ratio must match the relay settings exactly or protection becomes unreliable.

Interlocks and earthing

Mechanical and electrical interlocks stop a breaker being withdrawn while closed, prevent the compartment door opening while live, and allow a maintenance earthing switch to be applied only once the breaker is isolated.

Selection and sizing

  • Rated voltage must match the generator voltage class exactly, not just be higher than it
  • Rated short-circuit breaking current, typically 25-40 kA for marine MV boards, sized against the fault level the generators and any shore or shaft-generator connection can deliver
  • Busbar continuous current rating with margin for future feeders
  • Internal arc classification and accessibility type, which decides how venting is routed away from operating positions
  • Physical footprint and cable entry direction against the switchroom layout

Regulations and class

SOLAS Ch II-1 requires that the main source of electrical power be arranged so that essential services remain available after a single fault, which on MV ships is normally met by splitting the board into two sections with a bus-tie breaker rather than running it as one continuous bus. Class societies require type test certificates for the exact voltage and short-circuit rating supplied, generally referencing IEC 62271-200 for metal-enclosed switchgear, and verify protection relay settings during survey rather than just the physical condition of the cubicles. Internal arc containment is demonstrated through arc fault type testing so that, if an arc does occur, the pressure and hot gas vent to a safe direction instead of into the switchroom.

Typical faults

FaultCauseConsequence
Breaker fails to close or tripSpring charging motor failure or a stuck racking mechanismLoss of a generator or an unplanned blackout of the affected section
Insulation breakdownMoisture and condensation in an unheated or poorly ventilated switchroomEarth fault trip, in the worst case an internal arc
Protection maloperationRelay settings not updated after a generator or CT changeNuisance tripping, or failure to clear a real fault in time
Busbar hot spotLoose bolted joint or corroded contact surfaceLocalised overheating that can progress to an arc fault

What to look for in a supplier

  • Type test certificates to IEC 62271-200 that match the exact voltage class and short-circuit rating ordered, not a similar sibling model
  • An internal arc test report for the enclosure size actually being supplied
  • A relay settings package the ship's own electrical engineers can read, back up and edit, not one locked to the maker's service technician
  • Availability of spare trip coils, closing coils and spring mechanisms as discrete parts, not only complete breaker exchange units

A bus-tie breaker left closed for operational convenience turns two independent half-boards into one single point of failure — treat it as a switch to be operated deliberately, not a permanent bridge.

Models

Models in this type.

The best-documented model of each manufacturer first, then the next — 1 of 1 models in Main Switchboard (MV). Every row links to full specifications, documents and service notes.

Showing only ABB. Show all manufacturers
By manufacturer

Manufacturers.

All 2 manufacturers with models of Main Switchboard (MV). Names with a manufacturer page open it; the others open a search across the full library.

All manufacturers in the library
More than the data sheet shows

Write to us about your machine — the answer comes by e-mail.

Name the make and the model and what the job is: a spare, a service call, a second opinion on a data sheet. We answer by e-mail.

No details at hand? A photo of the rating plate or the part is enough — simply attach it to the request.

Frequently asked

Questions that come up with this equipment.

Is Main Switchboard (MV) data free?

Yes. Every model page, every guide and every datasheet for this type is readable without an account. An account adds saved searches and requests, nothing is taken away.

My model is missing — what now?

Send us the nameplate. We identify it by hand, add it to the library, and if you need a part or a service, the request is already on our desk.

Can you source a Main Switchboard (MV) part?

Yes. Tell us the manufacturer, the model and what you need — a person reads every request and replies by e-mail.