An online UPS keeps navigation and communication loads on inverter power at all times, so a mains failure or generator changeover produces no switching gap at all, unlike the standby designs used elsewhere in the distribution system.
The 0 models with the most complete data of 0 in UPS (Uninterruptible Power Supply). Every row links to full specifications, documents and service notes.
The other equipment types in this category.
Everywhere else in the switchboard the ship accepts that power can be interrupted for the second or two it takes a breaker to trip and a standby source to pick up. A UPS exists precisely because a handful of loads cannot accept even that gap: gyrocompass, radar, ECDIS, GMDSS equipment and the alarm and monitoring system need continuous, filtered power through any switching event, blackout or generator changeover. An online UPS achieves this by keeping the load permanently on an inverter fed from a rectified and battery-buffered DC bus, so…
Everywhere else in the switchboard the ship accepts that power can be interrupted for the second or two it takes a breaker to trip and a standby source to pick up. A UPS exists precisely because a handful of loads cannot accept even that gap: gyrocompass, radar, ECDIS, GMDSS equipment and the alarm and monitoring system need continuous, filtered power through any switching event, blackout or generator changeover. An online UPS achieves this by keeping the load permanently on an inverter fed from a rectified and battery-buffered DC bus, so a mains failure produces no switching transient at all, unlike a standby UPS that only steps in after detecting a fault.
Converts incoming AC to DC, feeds the inverter and keeps the battery charged, normally sized to do both jobs simultaneously without starving the battery.
Sealed lead-acid or, increasingly, lithium iron phosphate cells sized to carry the connected load for a defined autonomy time, typically 30 minutes to a few hours depending on the criticality of what is connected.
Converts the DC bus back to clean AC for the load, continuously in an online design, so the load never sees the raw mains waveform.
An electronic switch that transfers the load directly to mains within a few milliseconds if the inverter itself fails or is overloaded, and is also used to take the UPS out of circuit for maintenance without dropping the load.
SOLAS Ch. II-1 requires navigation and radio equipment to remain in continuous operation through the transitional period of a power failure, which in practice is met with battery-backed supplies, and GMDSS equipment under Ch. IV must be supported by a source able to power it for the periods laid down there. Class rules generally require documented autonomy testing at survey — discharging the battery under load to confirm it still meets its rated backup time — rather than trusting the charger's own status light.
Ask for a load test result, not a float-voltage reading, before accepting that a UPS battery still meets its rated autonomy — a bank can read a perfectly healthy voltage and still collapse in minutes under real load.

Tell us the manufacturer, the model and what you need — a part, a service call, a second opinion. Our desk asks the right suppliers from a network of over 114,000 companies and comes back with a quote or a sourcing plan, not a search page.
Yes. Every model page, every guide and every datasheet for this type is readable without an account. An account adds saved searches and requests, nothing is taken away.
Send us the nameplate. We identify it by hand, add it to the library, and if you need a part or a service, the request is already on our desk.
Yes. Tell us the manufacturer, the model and what you need — our desk asks the right suppliers from a network of over 114,000 companies and comes back with a quote or a sourcing plan.