Medium-voltage main switchboards, typically 3.3 kV, 6.6 kV or 11 kV, use vacuum or SF6 circuit breakers instead of the air-break contactors found on low-voltage boards, because fault energy at these voltages will destroy standard LV gear and can injure anyone standing in front of it.
The 1 models with the most complete data of 1 in Main Switchboard (MV). Every row links to full specifications, documents and service notes.
All 1 manufacturers with models of Main Switchboard (MV). Names with a manufacturer page open it; the others open a search across the full library.
All manufacturersThe other equipment types in this category.
Low-voltage boards at 400-690 V handle most auxiliary loads on a ship, but once installed generator output climbs past roughly 3-4 MW per set, cable cross-sections and transformer counts at LV become impractical. Cruise ships, LNG carriers, large offshore vessels and some ice-class ships generate and distribute at medium voltage instead, then step down locally to 440 V or 690 V near the consumers. The switchgear itself is a different class of equipment: breakers interrupt fault currents in a vacuum bottle or SF6 chamber rather than in open air, compartments…
Low-voltage boards at 400-690 V handle most auxiliary loads on a ship, but once installed generator output climbs past roughly 3-4 MW per set, cable cross-sections and transformer counts at LV become impractical. Cruise ships, LNG carriers, large offshore vessels and some ice-class ships generate and distribute at medium voltage instead, then step down locally to 440 V or 690 V near the consumers. The switchgear itself is a different class of equipment: breakers interrupt fault currents in a vacuum bottle or SF6 chamber rather than in open air, compartments are segregated to contain an internal arc, and every operation is mechanically interlocked because a mistake at these voltages is rarely survivable for the person making it.
Withdrawable vacuum or SF6 breakers mounted on a truck that racks in and out of the cubicle. Vacuum is the dominant technology on new tonnage; SF6 is still found on older or offshore-derived designs.
Copper or aluminium busbars run the length of the board, split into a port and starboard half joined by a bus-tie breaker so the board can be operated as two independent sections.
Numerical relays handle overcurrent, earth fault, differential and, on generator incomers, reverse power and loss-of-excitation protection, tripping the associated breaker within a coordinated time grading scheme.
Current and voltage transformers feed both the protection relays and the metering/SCADA system; their ratio must match the relay settings exactly or protection becomes unreliable.
Mechanical and electrical interlocks stop a breaker being withdrawn while closed, prevent the compartment door opening while live, and allow a maintenance earthing switch to be applied only once the breaker is isolated.
SOLAS Ch II-1 requires that the main source of electrical power be arranged so that essential services remain available after a single fault, which on MV ships is normally met by splitting the board into two sections with a bus-tie breaker rather than running it as one continuous bus. Class societies require type test certificates for the exact voltage and short-circuit rating supplied, generally referencing IEC 62271-200 for metal-enclosed switchgear, and verify protection relay settings during survey rather than just the physical condition of the cubicles. Internal arc containment is demonstrated through arc fault type testing so that, if an arc does occur, the pressure and hot gas vent to a safe direction instead of into the switchroom.
| Fault | Cause | Consequence |
|---|---|---|
| Breaker fails to close or trip | Spring charging motor failure or a stuck racking mechanism | Loss of a generator or an unplanned blackout of the affected section |
| Insulation breakdown | Moisture and condensation in an unheated or poorly ventilated switchroom | Earth fault trip, in the worst case an internal arc |
| Protection maloperation | Relay settings not updated after a generator or CT change | Nuisance tripping, or failure to clear a real fault in time |
| Busbar hot spot | Loose bolted joint or corroded contact surface | Localised overheating that can progress to an arc fault |
A bus-tie breaker left closed for operational convenience turns two independent half-boards into one single point of failure — treat it as a switch to be operated deliberately, not a permanent bridge.
Tell us the manufacturer, the model and what you need — a part, a service call, a second opinion. Our desk asks the right suppliers from a network of over 114,000 companies and comes back with a quote or a sourcing plan, not a search page.
Yes. Every model page, every guide and every datasheet for this type is readable without an account. An account adds saved searches and requests, nothing is taken away.
Send us the nameplate. We identify it by hand, add it to the library, and if you need a part or a service, the request is already on our desk.
Yes. Tell us the manufacturer, the model and what you need — our desk asks the right suppliers from a network of over 114,000 companies and comes back with a quote or a sourcing plan.