"> Fixed Gas Detector - Equipment Database

Fixed Gas Detector

medium 16 models total

A fixed gas detector is wired permanently into a monitored space and reports continuously to a control panel, unlike a portable unit a crew member carries to check a space before entry. It is the difference between an ongoing watch and a single point-in-time reading.

Read more — Fixed Gas Detector explained

What sets fixed detection apart

Portable detectors answer one question at a time: is this space safe to enter right now. Fixed gas detection answers a different question continuously: has anything changed in a space that is normally occupied or normally sealed, such as an engine room, a cargo pump room, a battery locker or, on gas carriers, the cargo compressor room and hold spaces around independent tanks. The sensor heads are hard-wired to a central control panel that logs readings, triggers local and bridge alarms, and in many installations interlocks ventilation fans or shuts down electrical equipment automatically once a set threshold is crossed.

Fixed gas detector arrangement
Arrangement of a fixed gas detector showing the sensor head mounted in the monitored space, the cable run to the control panel, the panel with its alarm lamps, the alarm horn and the relay output to a shutdown valve.

Main components

Sensor heads

Catalytic bead sensors detect flammable gas as a percentage of the lower explosive limit; infrared sensors do the same without consuming the target gas, which makes them tolerant of oxygen-deficient atmospheres; electrochemical cells target specific toxic gases such as H2S or CO; separate cells cover oxygen depletion or enrichment.

Control panel and wiring

The panel powers the sensors, processes the signal, drives audible and visual alarms at two thresholds (typically a pre-alarm and a high alarm), and often provides relay outputs to the fire and safety system. Cable runs into hazardous zones must use intrinsically safe barriers or explosion-proof glands.

Calibration points

Each sensor location has an accessible calibration gas port so the head can be bump-tested and calibrated without removal.

Selection and sizing

Sensor placement is driven by the gas properties and the space geometry: lighter-than-air gases are monitored near deckhead level, heavier vapours near the bilge or tank bottom. The number of points depends on space volume, ventilation pattern and the presence of dead pockets where gas could accumulate undetected. Response time (T90), cross-sensitivity to interfering gases, and the certified explosion-proof rating (commonly IIA, IIB or IIC depending on the gas group) all factor into the choice of sensor type for a given hazardous zone.

Regulations and class requirements

SOLAS Chapter II-2 requires fixed gas detection in specific spaces on tankers, including cargo pump rooms, and class rules extend similar requirements to enclosed spaces where flammable or toxic atmospheres are a known risk. Gas carriers under the IGC Code carry additional fixed detection for cargo hold spaces, interbarrier spaces and compressor rooms, monitoring for both flammable cargo vapour and, where relevant, toxicity or refrigerant leakage. Type approval and periodic testing intervals are set by class and flag administration; records of calibration and function tests are checked at survey.

Typical faults

  • Sensor drift over time, giving readings that creep away from true concentration until a routine calibration catches it, or fails to.
  • Expired or depleted calibration gas cylinders, leaving the crew unable to verify sensor response when it matters.
  • Cable or connector faults in the harsh environment of a pump room or engine room, producing intermittent fault signals or a dead channel.
  • Catalytic bead poisoning from silicone vapour or leaded compounds, which silently kills sensitivity while the sensor still appears to respond to bump tests with clean gas.
  • Nuisance alarms from condensation or vibration, which crews sometimes respond to by disabling the point rather than fixing the fault, defeating the whole purpose of the installation.

What to look for in a supplier

  • Explosion-proof certification appropriate to the zone (IECEx or ATEX, matched to the gas group present).
  • Class type approval covering the specific vessel type and application, not a generic industrial certificate.
  • Ready availability of matching replacement sensor cartridges, since panels are often kept in service far longer than any individual sensor.
  • Calibration kits and bump-test gas suited to the exact sensor range fitted, not a close approximation.

A gas detector that has stopped nuisance-alarming is not necessarily fixed; check whether someone disabled the point before assuming the fault cleared itself.

9 manufacturers · 16 models

Dräger

6
Dräger Polytron 8000
Polytron 8000
1 gas per point · Hazardous Gas Detection · electrochemical fixed gas detector
Type
fixed
Output
4-20mA
Solas
ja
Common Failures & Inspection Points
  • Sensor poisoning
  • 4-20mA signal drift
  • Sensor housing corrosion
  • Calibration gas port blockage
Service: Fixed installation in pump rooms, cargo areas. Calibrate every 6 months.
Spare Parts: Dräger: Spezialteile per Hersteller. Lead time: 4-8 Wochen. Gasdetektions-Sensoren an Bord.
Strengths
  • Integrated sensor life monitoring reduces unexpected failures
  • Self‑diagnostic functions alert to sensor poisoning or signal drift early
  • SOLAS‑approved, allowing direct installation in regulated pump rooms and cargo areas
  • 4‑20 mA analog output simplifies wiring to existing alarm panels and control systems
  • Modular design supports multiple gas sensors (e.g., CO, H₂S, O₂) on a single unit
Weaknesses
  • Electrochemical sensors require regular calibration (typically every 6 months)
  • Sensor housing can corrode in highly humid or salty environments if not maintained
  • Analog output only; no native digital (Modbus/Profibus) interface without an external converter
  • Initial purchase price higher than basic single‑gas detectors
  • Port blockage for calibration gas may occur if maintenance is neglected
Typical Vessels: TankerBulk CarrierContainer ShipRo‑Ro / FerryOffshore Supply Vessel
Certifications: IMO SOLAS
Decision Guide: Choose if: you need a reliable, SOLAS‑approved fixed detector with multi‑gas capability and built‑in health monitoring for pump rooms, engine rooms or cargo holds. Avoid if: budget constraints limit the use of higher‑cost electrochemical systems or if a digital communication protocol is required without adding converters.
Use Cases: Installed permanently in shipboard pump rooms to detect CO from diesel exhaust, in engine rooms for H₂S and O₂ deficiency monitoring, and in cargo areas of chemical tankers where toxic vapour detection is mandatory under SOLAS.
PIR 7000
HC detection · Hazardous Gas Detection · NDIR hydrocarbon detector
Type
fixed
Sensor
NDIR
Solas
ja
Common Failures & Inspection Points
  • IR source degradation
  • Window contamination
  • Electronics failure
Service: No sensor poisoning (IR). Extended calibration intervals. Clean window annually.
Spare Parts: Dräger: Spezialteile per Hersteller. Lead time: 4-8 Wochen. Gasdetektions-Sensoren an Bord.
Strengths
  • Non‑poisoning IR sensor provides long life and low maintenance
  • Extended calibration interval (up to 12 months) reduces downtime
  • Self‑diagnostic functions alert to source degradation or window fouling
  • Robust, explosion‑proof housing suitable for harsh marine environments
  • SOLAS approved for mandatory installation on passenger vessels
Weaknesses
  • Only detects IR‑active hydrocarbons; not suitable for gases like CO or H₂S
  • IR source intensity can degrade over time, requiring periodic replacement
  • Optical window must be cleaned annually to maintain accuracy
  • Higher upfront cost compared with basic electrochemical detectors
  • Integration may require specific fieldbus (Profibus/Modbus) infrastructure
Typical Vessels: Oil tankerChemical tankerLPG carrierOffshore supply vesselPassenger ferry / cruise shipContainer ship with cargo‑hold gas monitoring
Certifications: SOLASIMO Type ApprovalDNV GL
Decision Guide: Choose if you need reliable, low‑maintenance hydrocarbon detection in fixed installations and must meet SOLAS requirements. Avoid if multi‑gas detection (e.g., CO, H₂S) is required or budget constraints preclude higher initial cost.
Use Cases: Installed in engine rooms, cargo holds, tank manifolds, offshore platform process areas, and any confined space where hydrocarbon leaks pose fire/explosion risk.
Dräger Polytron 5000 unverified
Equipment Type
fixed_gas_detector
Series
Polytron
Model code
Polytron 5000
Fixed gas detector — fixed point detector
Dräger Polytron 7000 unverified
Equipment Type
fixed_gas_detector
Series
Polytron
Model code
Polytron 7000
Fixed gas detector — fixed transmitter
Dräger Polytron 8000 unverified
Equipment Type
fixed_gas_detector
Series
Polytron
Model code
Polytron 8000
Fixed gas detector — fixed IR
Dräger PIR 7200 unverified
Equipment Type
fixed_gas_detector
Series
PIR
Model code
PIR 7200
Fixed gas detector — open path IR

Honeywell

3
Searchline Excel
0-5 LEL·m · Hazardous Gas Detection · open-path infrared
Type
fixed
Sensor
open_path_IR
Common Failures & Inspection Points
  • Source/detector misalignment
  • Window fouling
  • Electronics aging
Service: Open-path for fence-line and perimeter detection
Spare Parts: Honeywell: Spezialteile per Hersteller. Lead time: 4-8 Wochen. Gasdetektions-Sensoren an Bord.
Strengths
  • Long detection range (up to several hundred metres) without the need for point sensors along the line
  • Self‑diagnosing optics with automatic alignment checks reduces maintenance visits
  • Robust marine‑grade housing (IP66/67) suitable for harsh offshore environments
  • Low power consumption and ability to integrate via HART, Modbus or 4‑20 mA
  • No consumable filters – only periodic window cleaning required
Weaknesses
  • Detects only IR‑absorbing gases (primarily methane/HC); not suitable for CO, H2S, etc.
  • Requires a clear line‑of‑sight; fog, heavy spray or fouled windows can impair performance
  • Initial capital cost higher than point‑type catalytic detectors
  • Electronics aging and window fouling are known failure modes that need scheduled inspections
  • Alignment drift over many years may necessitate recalibration
Typical Vessels: LNG CarrierChemical TankerOil TankerOffshore PlatformMarine Terminal Facility
Certifications: ATEX Zone 0/1IECExDNV GL Classification (equipment for ship installation)
Decision Guide: Choose if you need continuous, long‑range methane detection around a vessel perimeter, tank farm or offshore platform where point sensors would be impractical. Avoid if the application requires multi‑gas detection, operates in persistently foggy or heavily sprayed conditions, or budget constraints preclude higher upfront cost.
Use Cases: Deployed on LNG carrier hulls to monitor vent lines and cargo tank exteriors, on oil and chemical tankers for perimeter leak detection around ballast tanks, on offshore platforms for fence‑line monitoring of gas seeps, and at marine terminals for storage area surveillance.
Honeywell Sensepoint XCL unverified
Equipment Type
fixed_gas_detector
Model code
Sensepoint XCL
Fixed gas detector — fixed point gas transmitter
Honeywell Searchzone Sonik unverified
Equipment Type
fixed_gas_detector
Model code
Searchzone Sonik
Fixed gas detector — ultrasonic leak detector

Crowcon

1
Crowcon Xgard Bright Fixed
Xgard Bright Fixed
1 gas per point · Hazardous Gas Detection · electrochemical sensor fixed detector
Type
fixed
Output
4-20mA
Display
ja
Common Failures & Inspection Points
  • Sensor end-of-life
  • Display failure
  • 4-20mA output drift
Service: UK manufacturer. OLED display shows gas reading at point.
Spare Parts: Crowcon: Spezialteile per Hersteller. Lead time: 4-8 Wochen. Gasdetektions-Sensoren an Bord.
Strengths
  • OLED display gives immediate local readout of gas level
  • Standard 4‑20 mA output allows easy connection to shipboard control and alarm panels
  • ATEX/IECEx certified for use in explosive atmospheres, suitable for marine environments
  • Compact IP66 housing resists moisture, salt spray and vibration
  • Built‑in self‑diagnostics and sensor end‑of‑life warning
Weaknesses
  • Typically limited to a single gas per detector (requires separate units for multiple gases)
  • No native digital protocol (e.g., Modbus) – only analog output is available
  • OLED can be hard to read in very bright sunlight or glare
  • Sensor must be replaced at end‑of‑life, adding maintenance cost
  • Calibration requires external calibrator and periodic manual checks
Typical Vessels: TankerBulk CarrierOffshore Supply VesselContainer Ship (cargo hold monitoring)Passenger Ferry
Certifications: ATEX Zone 1/2 Category 3IECExDNV Class Approved
Decision Guide: Choose if you need a compact, ATEX‑rated detector with local visual readout and simple analog integration for single‑gas monitoring in confined spaces. Avoid if you require multi‑gas detection in one unit or digital networking (e.g., Modbus/TCP) without additional hardware.
Use Cases: Deployed to continuously monitor flammable or toxic gases in cargo tanks, fuel oil tanks, engine rooms, and other enclosed compartments where early leak detection is critical. The OLED display provides crew with on‑site concentration data while the 4‑20 mA output drives ship alarm panels and integrates with integrated monitoring systems.

Det-Tronics

1
Det-Tronics FlexSight LS2000
FlexSight LS2000
0-5 LEL·m · Hazardous Gas Detection · open-path infrared gas detection
Type
fixed
Sensor
open_path_IR
Common Failures & Inspection Points
  • Optical alignment drift
  • Window contamination
  • Heater failure in cold
Service: Open-path detection for large areas. Re-align optics after maintenance.
Spare Parts: Det-Tronics: Spezialteile per Hersteller. Lead time: 4-8 Wochen. Gasdetektions-Sensoren an Bord.
Strengths
  • Long detection range suitable for large cargo or machinery spaces
  • No moving parts or sampling lines, reducing routine maintenance
  • Fast response to gas releases along the optical path
  • Can cover multiple compartments with a single sensor line
Weaknesses
  • Optical alignment can drift over time, requiring periodic re‑alignment
  • Window contamination (dust, oil) degrades accuracy and must be cleaned
  • Heater element may fail in very cold environments, affecting performance
  • Installation requires clear line‑of‑sight; obstructions reduce effectiveness
Typical Vessels: Oil tankerChemical tankerLNG carrierBulk carrierOffshore platform
Decision Guide: Choose if you need continuous monitoring of flammable gases across large, open spaces and can accommodate periodic optical alignment checks. Avoid if the installation area has many obstructions, limited access for regular window cleaning, or operates in extremely cold climates where heater reliability is critical.
Use Cases: Commonly installed along cargo tank walls, engine‑room bulkheads, or deck enclosures to provide early warning of gas leaks in large volumes where point sensors would be impractical.

GfG Instrumentation

1
GfG Instrumentation EC 28 Fixed Transmitter
EC 28 Fixed Transmitter
1 gas per point · Hazardous Gas Detection · intrinsically safe fixed gas transmitter
Type
fixed
Output
4-20mA
Origin
Germany
Common Failures & Inspection Points
  • Sensor depletion
  • 4-20mA signal loss
  • Housing seal failure
Service: German manufacturer. Wide range of toxic gas sensors available.
Spare Parts: GfG Instrumentation: Spezialteile per Hersteller. Lead time: 4-8 Wochen. Gasdetektions-Sensoren an Bord.
Strengths
  • Standard 4‑20 mA output integrates easily with existing ship automation and alarm panels
  • Modular sensor design allows quick change‑over to different gases (e.g., H₂S, CO, NH₃)
  • Robust German‑engineered housing rated for harsh marine environments
  • Built‑in self‑diagnostic functions alert to sensor depletion or wiring faults
Weaknesses
  • Analog‑only output – no native digital protocols (e.g., HART, Modbus) for advanced monitoring
  • Sensor life is limited; periodic replacement adds maintenance cost
  • Signal loss can occur if wiring or the 4‑20 mA loop is compromised
  • Higher initial purchase price compared with basic single‑gas alarms
Typical Vessels: TankerChemical tankerOffshore supply vesselBulk carrier (cargo hold monitoring)Passenger ferry (engine‑room safety)
Decision Guide: Choose if: you need a rugged, intrinsically safe detector with reliable analog output and the flexibility to swap sensors for different gases. Avoid if: your vessel relies on digital communication standards or you have strict budget constraints that favour basic alarms.
Use Cases: Commonly installed in engine rooms for CO and H₂S monitoring, cargo holds of chemical tankers for toxic gas detection, ballast tanks where combustible gases may accumulate, and offshore platforms where explosion‑proof equipment is required.

Honeywell (RAE)

1
FGD-1000 Fixed PID
VOC detection · Hazardous Gas Detection · Photoionization Detector (PID)
Type
fixed
Sensor
PID
Application
chemical_cargo
Common Failures & Inspection Points
  • PID lamp burnout
  • Window contamination
  • Electronics drift
Service: For cargo pump rooms with chemical cargoes. PID lamp replacement.
Spare Parts: Honeywell (RAE): Spezialteile per Hersteller. Lead time: 4-8 Wochen. Gasdetektions-Sensoren an Bord.
Strengths
  • High sensitivity to low‑level VOCs, providing early leak detection
  • Fast response time suitable for rapid alarm activation
  • Robust housing rated for harsh marine pump‑room conditions
  • Lamp replacement is a defined maintenance task with clear intervals
  • Integrated audible/visual alarms and optional remote output
Weaknesses
  • PID lamp has limited life (typically 1–2 years) and must be replaced regularly
  • Optical window can become contaminated by dust or oil, requiring periodic cleaning
  • Electronics may drift over time, necessitating recalibration
  • Not suitable for detecting combustible gases; only VOCs are measured
  • Higher power consumption than catalytic sensors
Typical Vessels: Chemical TankerProduct TankerLNG/LPG Carrier (cargo handling spaces)Offshore Supply Vessel
Decision Guide: Choose if: you need continuous, high‑sensitivity VOC monitoring in cargo pump rooms or other areas where solvent vapors may be present and you can accommodate lamp replacement. Avoid if: the primary hazard is flammable gas detection (use catalytic or infrared sensors instead) or maintenance access to replace PID lamps is limited.
Use Cases: Installed permanently on walls or ceilings of chemical cargo pump rooms, deck machinery spaces handling solvents, and offshore platform process areas to provide early warning of VOC leaks from hoses, valves, or vent systems.

MSA

1
MSA Ultima X5000
Ultima X5000
1 gas per point · Hazardous Gas Detection · Fixed gas detector with HART communication
Type
fixed
Sil
2
Output
4-20mA/HART
Common Failures & Inspection Points
  • Sensor drift
  • Relay failure
  • Display electronics
  • Housing seal degradation
Service: SIL2 rated for safety-critical applications. HART protocol.
Spare Parts: MSA: Spezialteile per Hersteller. Lead time: 4-8 Wochen. Gasdetektions-Sensoren an Bord.
Strengths
  • SIL2 rated, providing high safety integrity for critical areas
  • HART protocol enables remote diagnostics and parameter tuning
  • Standard 4‑20 mA output simplifies integration with ship control systems
  • Fixed installation reduces the need for handheld devices in permanent monitoring points
  • Robust design suitable for harsh marine environments
Weaknesses
  • Sensor drift requires regular calibration to maintain accuracy
  • Relay and display electronics have documented failure modes
  • Housing seal degradation can occur in high‑humidity or salt‑spray conditions
  • Limited to fixed locations; not a substitute for portable detectors
  • Higher upfront cost compared with basic analog gas alarms
Typical Vessels: TankerLPG CarrierChemical TankerOffshore Supply VesselBulk Carrier (fuel oil monitoring)
Decision Guide: Choose if: you need SIL2‑rated fixed gas monitoring with digital HART diagnostics for integration into a vessel’s automation system. Avoid if: the application calls for portable detection, ultra‑low cost alarms, or where seal integrity cannot be guaranteed in extreme exposure.
Use Cases: Deployed to continuously monitor flammable or toxic gases in cargo tanks, fuel oil storage, engine rooms and enclosed spaces on tankers, LPG/chemical carriers and offshore supply vessels, providing early warning and automatic shutdown triggers.

Oldham (3M/Teledyne)

1
OLCT 200 Fixed
1 gas per point · Hazardous Gas Detection · Fixed multi-gas detector
Type
fixed
Output
4-20mA/Modbus
Common Failures & Inspection Points
  • Sensor degradation
  • Communication fault
  • Housing corrosion
Service: Teledyne product. Modbus and 4-20mA output.
Spare Parts: Oldham (3M/Teledyne): Spezialteile per Hersteller. Lead time: 4-8 Wochen. Gasdetektions-Sensoren an Bord.
Strengths
  • Continuous real‑time monitoring of combustible and toxic gases
  • Dual output options (4‑20 mA and Modbus) simplify integration with existing SCADA or alarm panels
  • Robust housing designed for marine environments
  • Teledyne/3M brand support and proven field reliability
  • Straightforward wiring and configuration for fixed installations
Weaknesses
  • Sensor drift requires scheduled calibration and replacement
  • Housing can corrode if not properly maintained in salty atmospheres
  • Communication faults (Modbus) may interrupt data transmission
  • Only suitable for fixed mounting – no portable capability
  • May need a dedicated power supply separate from ship’s main distribution
Typical Vessels: TankerBulk CarrierContainer ShipOffshore Supply VesselCruise Ship
Decision Guide: Choose if: you need reliable, continuous gas monitoring on a vessel with existing analog or Modbus instrumentation and can commit to regular sensor calibration and housing maintenance. Avoid if: you require portable detectors, have strict certification requirements not verified for this model, or cannot guarantee corrosion‑preventive upkeep.
Use Cases: Installed in engine rooms, cargo holds, fuel tanks, and accommodation spaces to detect flammable gases (e.g., methane, LPG) and toxic gases (e.g., CO, H2S), providing early warning and interfacing with integrated safety and alarm systems.

Simtronics

1
GD10P
HC detection · Hazardous Gas Detection · fixed infrared point detector
Type
fixed
Sensor
point_IR
Common Failures & Inspection Points
  • IR optics contamination
  • Heater element failure
  • Signal drift
Service: Autronica/Simtronics product. Common on offshore platforms.
Spare Parts: Simtronics: Spezialteile per Hersteller. Lead time: 4-8 Wochen. Gasdetektions-Sensoren an Bord.
Strengths
  • Fast, reliable detection of methane and other hydrocarbons using IR absorption
  • Robust housing rated for harsh offshore conditions (water‑tight, corrosion‑resistant)
  • Built‑in self‑diagnostics and heater control to minimise drift and false alarms
  • Easy integration with Autronica/Simtronics control panels via HART or Modbus
  • Low power consumption suitable for remote installations
Weaknesses
  • Limited to hydrocarbon gases; not suitable for toxic or oxygen‑deficient atmospheres
  • Optical window can become contaminated, requiring periodic cleaning
  • Heater element failure can cause loss of sensitivity and requires replacement
  • Higher upfront cost compared with basic electrochemical sensors
  • Requires line‑of‑sight installation to the gas plume
Typical Vessels: Offshore platformFPSOLNG carrierChemical tankerOffshore supply vessel
Certifications: IECExATEX
Decision Guide: Choose the GD10P when continuous, high‑reliability detection of hydrocarbon leaks is required on offshore or hazardous‑area installations and integration with existing Simtronics/Autronica systems is desired. Avoid it if you need multi‑gas toxic monitoring, have strict budget constraints, or cannot provide regular optical‑window maintenance.
Use Cases: Deployed in flare stacks, cargo tanks, pump rooms, and process areas on offshore platforms and vessels to detect methane or other hydrocarbon releases, trigger alarms, and feed data to integrated safety management systems.