Library› Electrical› Motor Control› Motor Protection Switch
Motor Control

Motor Protection Switch

A motor protection switch combines a manual on/off function with thermal-magnetic overload and short-circuit tripping in one device, sized to the exact full-load current of the motor it protects rather than to the switchboard feeder rating.

5models
terasaki
Knowledge

What to check on a Motor Protection Switch.

5 models from terasaki in Motor Protection Switch. Below: the full model list.

What defines a motor protection switch

A motor protection switch (often called a motor circuit breaker or MPCB) is a manually operated switch and a protective device in one housing, dedicated to a single motor rather than a whole distribution board section. It differs from a plain fuse-switch or an air circuit breaker in that its overload trip curve is set to the motor's actual full-load current, not to the cable's current-carrying capacity, and it trips on an inverse-time thermal curve for overload plus an instantaneous magnetic trip for short-circuit and locked-rotor current. Where a contactor alone switches the motor on and off under normal control-system command, the protection switch is the device that removes power when something has already gone wrong -- overload, phase loss, or a direct fault downstream.

Motor protection switch internals
Schematic of a three-pole motor protection switch showing the ganged handle opening three switch blades, the bimetal overload trip and magnetic short-circuit trip in each pole, the current setting dial and an auxiliary fault contact.
Read the full guide

Main components

Trip unit

A thermal-magnetic trip unit (or, on larger frames, an electronic trip unit) that combines an adjustable overload setting -- usually a dial covering a current range around the motor's rated current -- with a fixed or adjustable short-circuit trip several times higher.

Operating mechanism

A quick-make, quick-break toggle or rotary handle, independent of how fast the operator moves it, so contact welding on a heavy fault current does not delay the trip.

Auxiliary and alarm contacts

Change-over contacts that report the switch position and trip status to the alarm and monitoring system, so a tripped motor shows on the bridge or engine control room panel rather than only being discovered locally.

Phase failure protection

Most marine types include single-phasing protection, since a motor running on two phases after losing one draws sharply higher current in the remaining windings and can burn out within minutes if the thermal trip alone is relied on.

Selection and sizing

  • Full-load current of the motor at its nameplate voltage and duty, not the feeder cable rating.
  • Starting current and starting time, since the trip curve must ride through a normal start without nuisance tripping.
  • Short-circuit breaking capacity at the switchboard fault level, which is higher close to the busbar than at the end of a long feeder.
  • Duty type -- continuous, intermittent, or reversing service such as a winch -- which changes the thermal trip class required.
  • Ambient temperature at the installation point, since switchgear in an engine room runs hotter than an air-conditioned control room and the trip curve needs compensation.

Regulations and class

Class rules require overload and short-circuit protection on every motor circuit above a small rating threshold, plus single-phasing protection on three-phase motors driving essential services. Motors feeding steering gear, fire pumps and other essential services have additional requirements around where the protection is allowed to trip the motor versus only alarm and let it run -- SOLAS Ch. II-1 sets out which essential auxiliaries must not be tripped on overload alone, only alarmed, so that steering is not lost to a nuisance trip in heavy weather. Surveyors check the trip settings against the motor nameplate at commissioning and again at periodic survey, since a setting left at factory default rather than the actual motor current is a common finding.

Typical faults

FaultCauseConsequence
Nuisance tripping on startOverload setting too close to full-load current for a motor with a long or heavy startRepeated failed starts, crew resets the trip without addressing the cause, eventual real overload undetected
Trip unit fails to operate on a genuine overloadContacts welded from a previous fault, or thermal element degraded by age and heat cyclingMotor winding burns out instead of the switch tripping
Single-phasing goes undetectedPhase failure protection not fitted or disabled after a previous nuisance tripMotor continues running on two phases until thermal damage or complete failure
Auxiliary contact signal lostLoose wiring on the remote indication contacts, often after switchboard vibration over years of serviceControl room shows a motor running when it has actually tripped locally

What to look for in a supplier

  • Type test certificate showing short-circuit breaking capacity at the actual switchboard fault level, not just a generic rating.
  • Trip curve documentation the ship's electrician can use to reset and verify the setting after motor replacement.
  • Spares availability for the specific frame size already installed, since protection switches are rarely interchangeable across manufacturers without rewiring the panel.
  • Auxiliary contact configuration matching the existing alarm and monitoring wiring.

When a motor is replaced with one of a different rating, the protection switch setting has to be recalculated and re-set at the same time -- leaving the old setting in place is a routine oversight that turns the switch into a piece of decoration rather than protection.

Models

Models in this type.

The best-documented model of each manufacturer first, then the next — 5 of 5 models in Motor Protection Switch. Every row links to full specifications, documents and service notes.

Showing only terasaki. Show all manufacturers
5 models
By manufacturer

Manufacturers.

All 10 manufacturers with models of Motor Protection Switch. Names with a manufacturer page open it; the others open a search across the full library.

All manufacturers
Related types

Also in Motor Control.

The other equipment types in this category.

Direct Online Starter (DOL)Electric MotorFrequency Converter / VFDMotor Starter / ContactorSoft Starter
Would you like to know more?

One request. A person reads it and replies by e-mail.

Tell us the manufacturer, the model and what you need — a part, a service call, a second opinion. A person reads every request and replies by e-mail.

No details at hand? A photo of the rating plate or the part is enough — simply attach it to the request.

Frequently asked

Three things people ask first.

Is Motor Protection Switch data free?

Yes. Every model page, every guide and every datasheet for this type is readable without an account. An account adds saved searches and requests, nothing is taken away.

My model is missing — what now?

Send us the nameplate. We identify it by hand, add it to the library, and if you need a part or a service, the request is already on our desk.

Can you source a Motor Protection Switch part?

Yes. Tell us the manufacturer, the model and what you need — a person reads every request and replies by e-mail.