The main switchboard is where every generator's output meets every consumer's demand, and the motor control centre extends that same busbar down to individual starters, which is why a fault at either point can black out sections the crew never expected to lose.
11 models from terasaki in Switchboard/MCC. Below: the full model list.
The main switchboard is the busbar and breaker assembly that generators feed into and that distribution boards draw from; the motor control centre (MCC) is a related but distinct assembly, usually downstream of the switchboard, dedicated to housing individual motor starters for pumps, fans and other rotating machinery. Where the switchboard's job is bulk power handling and generator synchronising, the MCC's job is starting, protecting and controlling many individual motors from one compact, centrally wired location rather than scattering starters around the ship next to each motor.
Copper or aluminium bars carrying the full generated current, split into sections by bus-tie breakers so a fault on one section does not necessarily black out the other.
Circuit breakers with synchronising and protection relays that allow generators to be paralleled safely and sections to be tied or split.
Individual breakers feeding distribution boards, large consumers and, in the MCC, each motor starter.
Direct-on-line, star-delta or soft-start units, each with overload protection sized to its motor, housed in individual withdrawable or fixed cubicles within the MCC.
Overcurrent, earth fault, reverse power and under/over voltage protection coordinated across switchboard and MCC so a downstream fault trips the nearest breaker first, not the generator breaker.
SOLAS Ch. II-1 sets requirements for electrical installations including the arrangement of the main switchboard relative to the emergency switchboard and the protection against a single fault disabling both. Class rules require protective device coordination studies (selectivity) to be submitted and verified, and periodic testing of breaker trip settings and insulation resistance is carried out at survey. IACS unified requirements cover short-circuit withstand and type testing of switchgear assemblies.
| Fault | Cause | Consequence |
|---|---|---|
| Protection miscoordination | Relay settings changed locally without updating the selectivity study | Generator breaker trips for a fault that should have been cleared by a feeder breaker, blacking out the whole board |
| Busbar contact overheating | Loose connection or corroded joint | Progressive resistance rise, local burning, risk of fire inside the switchboard |
| Starter overload trip | Motor overload setting too tight or too loose for actual running current | Nuisance trips or, if too loose, undetected motor overheating |
| Insulation degradation | Moisture or dust ingress into an aging cubicle | Reduced insulation resistance, risk of earth fault or flashover |
After any local change to a breaker or overload setting, update and re-check the selectivity study. An unrecorded setting change is the most common reason a small downstream fault takes down the whole switchboard instead of just one feeder.
The best-documented model of each manufacturer first, then the next — 11 of 11 models in Switchboard/MCC. Every row links to full specifications, documents and service notes.
All 6 manufacturers with models of Switchboard/MCC. Names with a manufacturer page open it; the others open a search across the full library.
All manufacturersThe other equipment types in this category.
Tell us the manufacturer, the model and what you need — a part, a service call, a second opinion. A person reads every request and replies by e-mail.
No details at hand? A photo of the rating plate or the part is enough — simply attach it to the request.
Yes. Every model page, every guide and every datasheet for this type is readable without an account. An account adds saved searches and requests, nothing is taken away.
Send us the nameplate. We identify it by hand, add it to the library, and if you need a part or a service, the request is already on our desk.
Yes. Tell us the manufacturer, the model and what you need — a person reads every request and replies by e-mail.