Central AC Plant (Chiller)
A central chilled water plant produces cold water at one or two central chillers and pumps it through insulated pipework to air handling units throughout the accommodation, giving one set of compressors to maintain instead of dozens of small split units scattered through the ship.
Read more — Central AC Plant (Chiller) explained ▾
What sets a central plant apart from split units
Where a split air conditioning system places a compressor at or near each served space, a central chiller plant concentrates all refrigeration in one or two machinery spaces and distributes cooling as chilled water, typically at 6-7°C supply, through insulated piping to air handling units around the ship. This means only one refrigerant circuit to survey and leak-test instead of many, and it lets the plant run on partial load with one chiller and one on standby, but it also means a single chiller failure with no redundancy can lose cooling to the entire accommodation at once.
Main components
Compressor and refrigerant circuit
Screw or scroll compressors circulate refrigerant through an evaporator, where it absorbs heat from the chilled water loop, and a condenser, where that heat is rejected to seawater or to a fresh water intermediate circuit.
Chilled water circuit
Pumps circulate chilled water from the evaporator to air handling units and fan coil units throughout the accommodation and control spaces, returning warmed water to the chiller for re-cooling.
Air handling units
AHUs mix fresh and recirculated air, pass it over a chilled water coil, and distribute it through ductwork with dampers controlling the balance per zone or space.
Condenser cooling
Heat rejection uses either seawater cooling directly on the condenser or an intermediate fresh water circuit cooled by the ship's central cooling system, keeping raw seawater away from the refrigerant condenser itself.
Selection and sizing
Cooling load is calculated from accommodation area, occupancy, solar and equipment heat gain, and the design ambient conditions the ship is expected to operate in.
- Total cooling load in kW, typically split across two or more chillers for redundancy.
- Design ambient seawater and air temperature, since Gulf or tropical routes push chillers much harder than North Sea trades.
- Refrigerant type and its regulatory status (HFC phase-down schedules affect long-term availability of some refrigerants).
- Redundancy philosophy: N+1 chillers versus a single oversized unit.
Regulations and class requirements
Class rules require accommodation, wheelhouse and control spaces to be maintained within defined temperature and humidity ranges, and set minimum ventilation and air conditioning capacity for the vessel's intended trading area. Refrigerant handling falls under MARPOL Annex VI provisions on ozone-depleting substances and, depending on flag and refrigerant type, under regional F-gas type regulation for leak checking and logging of refrigerant top-ups. Periodic survey includes pressure testing of the refrigerant circuit and verification of leak detection arrangements in the machinery space.
Typical faults
| Fault | Cause | Consequence |
|---|---|---|
| Refrigerant leak | Vibration fatigue at pipe joints, corroded fittings | Falling cooling capacity, compressor short-cycling, environmental reporting obligation |
| Fouled condenser | Marine growth or scaling on seawater-cooled tubes | Rising condensing pressure, reduced efficiency, high-pressure trip |
| Low chilled water flow | Air locked pump, partially closed valve, fouled strainer | Uneven cooling, freeze-up risk at the evaporator |
| Compressor trip on high pressure | Loss of condenser cooling water flow | Loss of that chiller, plant falls back on standby unit if fitted |
What to look for in a supplier
- Confirmed capacity at the vessel's actual design seawater and ambient air temperature, not a standard test condition.
- Refrigerant choice with a clear long-term availability outlook given phase-down schedules.
- Redundancy and standby arrangements matching the ship's operating profile and accommodation size.
- Local service support or a training package, since chiller electronics and controls vary significantly between makers.
A slow, unexplained rise in condensing pressure over weeks is almost always condenser fouling, not a refrigerant fault, and it is cheaper to clean than to chase with refrigerant top-ups.
Typical Manufacturers
6 manufacturers · 21 models
Daikin Marine
7Carrier Marine
6Heinen & Hopman
5JETS VACUUM
1- Component wear due to operating hours and environmental conditions
- Corrosion due to seawater/salt air exposure
- Electronics/control failure due to moisture or vibration
- Service interval overrun causes premature failure
Victor Marine
1
- Component wear due to operating hours and environmental conditions
- Corrosion due to seawater/salt air exposure
- Electronics/control failure due to moisture or vibration
- Service interval overrun causes premature failure