Hilfsdiesel (Generatorsatz) · Hilfsdiesel
MAN Generator (PrimeServ) 6-L16/24 GenSet — Mechanical, 6 cyl × 160mm bore, 1000 rpm, MGO/HFO, 660 kW.
Haben Sie das Herstellerdatenblatt zu diesem Modell? Schicken Sie es mit dem Anfrageformular — wir prüfen es und nennen die Quelle.
| Daily/Weekly Checks | Visual inspections, log readings, basic operational checks. |
|---|---|
| 1000-2000 hrs | Fuel injector overhaul/exchange. |
| 4000-6000 hrs | Cylinder head overhaul (valves, springs, seats), fuel pump overhaul, turbocharger inspection. |
| 8000-12000 hrs | Piston withdrawal for inspection/ring renewal, connecting rod bearing inspection. |
| 24000-36000 hrs | Major overhaul (crankshaft inspection, main bearings, liner wear measurement, full engine disassembly). |
| Turbocharger Overhaul | 12000-18000 hrs (depending on type and condition, intermediate inspections at 4000-6000 hrs). |
| Cylinder Liner | Max wear (ovality/taper) typically 0.6 - 0.8 mm from new diameter. |
|---|---|
| Piston Ring Gap | Max increase 1.0 - 1.5 mm from new specification (e.g., new 0.4-0.6mm, limit 1.5-2.0mm). |
| Crankshaft Deflection | Max deviation between adjacent webs typically 0.05 - 0.10 mm. |
| Main/Connecting Rod Bearing Clearance | Max increase 0.10 - 0.15 mm from new specification. |
| Exhaust Valve Seat Recession | Max 1.5 - 2.0 mm from cylinder head face. |
| Turbocharger Axial Play | Max 0.15 - 0.20 mm. |
| Turbocharger Radial Play | Max 0.25 - 0.30 mm. |
Die Bereiche sind für diese Bauklasse typisch. Maßgeblich sind stets die Herstellerunterlagen zur jeweiligen Seriennummer.
Class surveyors typically focus on verifying engine running hours and adherence to the Planned Maintenance System (PMS). They will conduct operational tests under load, including emergency stop functionality (local and remote), and confirm the proper operation of all safety devices (overspeed trip, low lube oil pressure trip, high cooling water temperature trip). Inspection of the fuel oil system, especially the MGO/HFO changeover arrangements and leak detection, is critical. The condition of exhaust gas piping, insulation, and expansion bellows will be checked for integrity and fire safety. A generator insulation resistance test will be performed. Surveyors will also inspect engine foundation bolts, anti-vibration mounts, crankcase relief valves, and verify the availability of critical spare parts as per class requirements. Documentation of maintenance, oil analysis reports, and performance logs are crucial.
Geschätzte Lebensdauer: 24,000 - 36,000 hours before major overhaul (bottom-end inspection/renewal), with proper maintenance some units can exceed 40,000 hours.
Kostenlos — senden Sie uns Ihre Anfrage zu MAN Generator (PrimeServ)-Ausrüstung. Unser Team prüft sie und antwortet per E-Mail.
Weitere Modelle desselben Ausrüstungstyps, zuerst MAN Generator (PrimeServ).
Sagen Sie uns, was Sie für diesen MAN Generator (PrimeServ) 6-L16/24 GenSet benötigen — ein Ersatzteil, einen Serviceeinsatz, eine zweite Meinung. Sind Sie MAN Generator (PrimeServ)? Diese Herstellerseite beanspruchen.
Servicetechniker? Schreiben Sie den Tagesbericht für diesen 6-L16/24 GenSet in OceanSphere Work — Fotos, Stunden und Teile, als PDF für den Reeder. 14 Tage kostenlos testen →
Ja. Technische Daten, Dokumente und Servicehinweise zu diesem Modell sind ohne Konto lesbar. Ein Konto bringt gespeicherte Suchen und Anfragen dazu, es nimmt nichts weg.
Ja. Nennen Sie uns Hersteller, Modell und Bedarf — ein Mensch liest jede Anfrage und antwortet per E-Mail.
Schicken Sie uns das Typenschild oder den richtigen Wert. Wir prüfen ihn gegen das Herstellerdatenblatt oder den Klassifikationsdatensatz und aktualisieren die Seite.