Library Electrical Emergency Power Emergency Generator Set
Emergency Power

Emergency Generator Set

The emergency generator is electrically and physically separate from the main gensets by rule, not by convenience — it sits above the bulkhead deck outside the machinery space specifically so a single flooding or fire casualty cannot take out main and emergency power together.

1,274models 433manufacturers
Models

Models in this type.

The 100 models with the most complete data of 1,274 in Emergency Generator Set. Every row links to full specifications, documents and service notes.

Siemens AG GWA3RA21 & 3RA22 Siemens AG GWA3RA6 Siemens AG GWA3RB20 & 3RB21 Siemens AG GWA3RB22, 3RB23 & 3RB29 Siemens AG GWA3RB3.1..., 3RB3.2..., 3RB3.3..., 3RB3.4 Siemens AG GWA3RN20 Siemens AG GWA3RP Siemens AG GWA3RP25 Siemens AG GWA3RQ1 Siemens AG GWA3RR2 Siemens AG GWA3RS2 Temperature Monitoring Relay Siemens AG GWA3RT1, 3RH1 Siemens AG GWA3RT2, 3RA23, 3RA24 & 3RH2 Siemens AG GWA3RU21 Siemens AG GWA3RV1.11 Siemens AG GWA3RV2 Siemens AG GWA3RW40 Siemens AG GWA3RW44 Siemens AG GWA3TF68, -69 Siemens AG GWA3UG4 Siemens AG GWAET 200 SP Siemens AG GWASIMOCODE pro 3UF7 Siemens AG GWASIRIUS 3SK1 Safety Relays Siemens AG GWASIRIUS Act 3SU1... Siemens3RD1000... Siemens3RW50, 3RW52, 3RW55 Siemens3UG5 Series Siemens5SG7... Siemens5SP4 SiemensMain- and Emergency Stop Switches of type 3LD2 as listed in the certificate SiemensNXAIR SiemensNXAIR 50kA SiemensNXPLUS C SiemensS 120 Semiconducter Power Moduls SiemensS 120 Supplementary System Components SiemensSENERGY SWITCHBOARD SiemensSINAMICS DCM DC Converter SiemensSINAMICS G120C, SINAMICS G120, SINAMICS S120 Blocksize SiemensSINAMICS G220 SiemensSINAMICS S120 Chasis Diode Line Modules, Liquid Cooled SiemensSINAMICS S120 Chasis, Liquid Cooled SiemensSION 3AE2..., 3AE5... SiemensSQM4x.36xxxx, SQM4x.38xxxx SiemensEnergy BlueVault SiemensSinamics DCM Control Modules SiemensSinamics G130, G150, S120, S120 Cabinet Modules & S150 SiemensVSGPM WISKA Hoppmann GmbH**SKE(*) (-L)(-**)(-RDE) **(-**) (LT) (MFD**/***(-**/***))(*****) WISKA Hoppmann GmbH**SKV(*) (-L)(-**)(-***) **(-**)(/**) (LT) (EMV-*) WISKA Hoppmann GmbH*SKE/1(S)(-L)-*(-RDE) ** (LT) (MFD**/***(-**/***)) WISKA Hoppmann GmbH*SKV(*)(-L)(-F)(-***) ** (LT) WISKA Hoppmann GmbH2000/E 27, .. /B 22, .., 1017/gR, 1017/gK, 1026, 1027, 1131/CR, 1131/gK, 1131/oS WISKA Hoppmann GmbH4000-.x..-...-.-.-... WISKA Hoppmann GmbH510, 510/2, 510/3, 510/4 WISKA Hoppmann GmbHBraceConduit: BCAB-L-(x)-(y), BraceConduitClip: BCC-(x)-(y), BraceFitting: E(b)BFS(d)-(e)-(f)-(g) WISKA Hoppmann GmbHCertificate MEDD00000J3 WISKA Hoppmann GmbHCertificate MERD00000J3 WISKA Hoppmann GmbHCombi MAR XXXX WISKA Hoppmann GmbHEX-KVM-..-..-.. WISKA Hoppmann GmbHEX-VSM.. WISKA Hoppmann GmbHExplosion Protected Plug and Socket Device 16A 5516/**/**/(******) WISKA Hoppmann GmbHExplosion Protected Switch 14105/*/**/(**)/(******) WISKA Hoppmann GmbHLED Floodlight 5000 WISKA Hoppmann GmbHMulti-purpose luminaire 2010 WISKA Hoppmann GmbHMulti-purpose luminaire 4010 WISKA Hoppmann GmbHPushIn Mobile Splitter with 2 Socket Outlets, PushIn Mobile Extension WISKA Hoppmann GmbHSKS 575 WISKA Hoppmann GmbHSO-32A WISKA Hoppmann GmbHVARITAIN PushIn, PushIn Advance and PushIn Rack WISKA Hoppmann GmbHVARITAIN® OneTouch ECO **/FS/FS/32A/**kA U.I. Lapp GmbHETHERLINE® MARINE FRNC FC CAT.5 2X2XAWG22/7 U.I. Lapp GmbHSKINTOP BS-M U.I. Lapp GmbHSKINTOP CLICK, CLICK R, CLICK BS, CLICK BLK U.I. Lapp GmbHSKINTOP K-M ATEX plus, SKINTOP KR-M ATEX plus U.I. Lapp GmbHSKINTOP MS-M & MS-M-XL, MS-M BRUSH & MS-M BRUSH XL, MSR-M & MSR-M-XL, MS-SC-M & MS-SC-M-XL U.I. Lapp GmbHSKINTOP MS-M ATEX & MS-M-XL ATEX, MS-M ATEX BRUSH, MSR-M ATEX & MSR-M-XL ATEX U.I. Lapp GmbHSKINTOP ST-M & STR-M U.I. Lapp GmbHUNITRONIC DeviceNet THIN Halogen Free UL/CSA (CMG) U.I. Lapp GmbHUNITRONIC DeviceNet Thick Halogen Free UL/CSA (CMG) U.I. Lapp GmbHÖLFLEX HEAT 125 C MC U.I. Lapp GmbHÖLFLEX HEAT 125 MC U.I. Lapp GmbHÖLFLEX HEAT 260 GLS U.I. Lapp GmbHÖLFLEX® CHAIN 90 CP U.I. Lapp GmbHÖLFLEX® CHAIN 90 P U.I. Lapp GmbHÖLFLEX® CLASSIC 110 CH U.I. Lapp GmbHÖLFLEX® CLASSIC 110 H U.I. Lapp GmbHÖLFLEX® CLASSIC 130 H U.I. Lapp GmbHÖLFLEX® CLASSIC 135 CH U.I. Lapp GmbHÖLFLEX® HEAT 125 SC U.I. Lapp GmbHÖLFLEX® PETRO FD 865 CP HD Hyundai Electric Co., Ltd. (Cheongju Power Distribution Campus)HGC115/130/150/185/225/265/300/400/500/630/800 HD Hyundai Electric Co., Ltd. (Cheongju Power Distribution Campus)HGC9/12/18/25/32/40/50/65/75/85/100 HD Hyundai Electric Co., Ltd. (Cheongju Power Distribution Campus)HGM 100 C/R/E/S/H/L, HGM 60 C/R/E/S/H/L, HGM 50 C/R/E/S/H/L, HGM 30 C/R/E/S/H/L HD Hyundai Electric Co., Ltd. (Cheongju Power Distribution Campus)HGM 100E/S/H/L, HGM 60E/S/H/L, HGM 50E/S/H/L, HGM 30E/S/H/L HD Hyundai Electric Co., Ltd. (Cheongju Power Distribution Campus)HGM 125E/S/H/L HD Hyundai Electric Co., Ltd. (Cheongju Power Distribution Campus)HGM 250E/S/H/L, HGM 160E/S/H/L HD Hyundai Electric Co., Ltd. (Cheongju Power Distribution Campus)HGM 400F/N/E/S/H/L HD Hyundai Electric Co., Ltd. (Cheongju Power Distribution Campus)HGM 630F/N/E/S/H/L, HGM 800F/N/E/S/H/L HD Hyundai Electric Co., Ltd. (Cheongju Power Distribution Campus)HGMP Series HD Hyundai Electric Co., Ltd. (Cheongju Power Distribution Campus)HGP 100 F/N/S/H/L/X, HGP 160 F/N/S/H/L/X, HGP 250 F/N/S/H/L/X, HGP 400 F/N/S/H/L/X, HGP 630 F/N/S/H/L/X, HGP 800 F/N/S/H/L/X
By manufacturer

Manufacturers.

All 433 manufacturers with models of Emergency Generator Set. Every name opens a search across the full library.

Knowledge

What to check on a Emergency Generator Set.

An emergency generator set exists to supply a defined list of safety-critical loads — steering gear, navigation lights, fire pumps, emergency lighting, watertight door indication, and communications — automatically, without anyone reaching the space first, whenever the main source of electrical power fails. What separates it from an auxiliary generator is not the engine itself, which is often a similar diesel unit at a smaller rating, but its location and independence: SOLAS requires it above the bulkhead deck, outside the main machinery space, in its own dedicated compartment with its…

What makes this type

An emergency generator set exists to supply a defined list of safety-critical loads — steering gear, navigation lights, fire pumps, emergency lighting, watertight door indication, and communications — automatically, without anyone reaching the space first, whenever the main source of electrical power fails. What separates it from an auxiliary generator is not the engine itself, which is often a similar diesel unit at a smaller rating, but its location and independence: SOLAS requires it above the bulkhead deck, outside the main machinery space, in its own dedicated compartment with its own fuel supply, so that whatever event disabled the main gensets (flooding, fire, blackout) cannot also disable the emergency set. It is sized only to cover the safety load list for a defined duration, not to run the ship — it is not a backup source of full electrical power.

Emergency generator set arrangement
Side schematic of an emergency generator set sited in its own space above the bulkhead deck, separate from the machinery space below, feeding the main switchboard by a dedicated cable.

Main components

Engine and dedicated fuel tank

A self-contained diesel with its own fuel supply, sized for the required autonomy period (commonly 18 to 36 hours depending on ship type), independent of the main fuel service system.

Automatic starting system

Must start automatically on loss of main power and be capable of picking up its rated load within a defined time (typically within 45 seconds under SOLAS for the first, most urgent load step), using a dedicated starting battery bank kept charged independently of the main switchboard.

Emergency switchboard

A physically separate switchboard from the main switchboard, feeding only the emergency load list, with automatic transfer arrangements that connect it when main power is lost and, on some ships, automatic changeover back once main power is restored.

Space heating and ventilation

The emergency generator room needs independent heating (in cold climates, to keep the engine startable) and ventilation, since it cannot rely on systems fed from the main machinery space.

Selection / Sizing

Sizing is a load-list exercise, not a power-headroom exercise: sum the SOLAS-mandated emergency loads (steering, fire pumps, navigation lights, emergency lighting, general alarm, and any other equipment on the required list for the ship type) with appropriate diversity factors, and size the set to cover that with margin, rather than sizing it as a smaller version of the main gensets. Passenger ships and certain offshore vessels have additional load items (evacuation systems, additional fire-fighting capacity) that push emergency set sizing higher than on a simple cargo ship.

Regulations / Class

SOLAS Ch. II-1 sets the core requirements: location above the bulkhead deck outside the machinery space, automatic starting and load pickup within a specified time, independent fuel and starting arrangements, and a defined minimum operating duration. Class surveys the automatic start sequence and load transfer at every periodic survey by a live test — a genset that starts manually but fails to auto-start on simulated blackout is a deficiency, not a pass with a note. MARPOL Annex VI NOx rules apply to the engine same as any diesel, though emergency sets typically run few hours per year so fuel and emissions compliance is rarely the operational concern it is for main and auxiliary engines.

Typical faults

  • Starting battery failure — the most common cause of a failed emergency start, since the batteries sit idle between monthly tests and degrade without load cycling.
  • Fuel system gumming from long inactivity — the dedicated fuel tank is rarely turned over, and stale fuel causes hard starting exactly when reliability matters most.
  • Automatic transfer switch failure — mechanical or control faults that mean the set starts and runs but never actually picks up the emergency switchboard load.
  • Space heater failure in cold trades — a cold engine room can prevent reliable automatic starting even with good batteries and fresh fuel.
  • Load list creep — additional equipment connected to the emergency switchboard over time without re-checking total load against the set's rating.

What to look for in a supplier

  • Certified automatic start and load-acceptance performance matching the specific pickup-time requirement for the ship type (passenger ships have tighter timing than cargo ships).
  • Cold-start capability data if the ship trades in low ambient temperatures, including heater specification for the compartment.
  • A battery and charging system sized and rated for the required number of start attempts without external support.
  • Documentation supporting the class survey's live-test requirement, since an emergency set that cannot be demonstrated starting automatically fails survey regardless of paper specifications.

Test the automatic start monthly by simulating a real blackout, not by pressing the manual start button — a set that starts manually every time can still fail the one test that actually matters.

Search by manufacturer AFRISOWISKASwagelokAlfa Laval S.p.A.MAN Energy SolutionsWärtsiläEndress+HauserABB MarineAlfa LavalMacGregorNovenco MarineCarrier MarineSiemens MarineHeinen & HopmanDaikin Marine
Would you like to know more?

One request. A person answers within 24 hours on working days.

Tell us the manufacturer, the model and what you need — a part, a service call, a second opinion. Our desk asks the right suppliers from a network of over 114,000 companies and comes back with a quote or a sourcing plan, not a search page.

Frequently asked

Three things people ask first.

Is Emergency Generator Set data free?

Yes. Every model page, every guide and every datasheet for this type is readable without an account. An account adds saved searches and requests, nothing is taken away.

My model is missing — what now?

Send us the nameplate. We identify it by hand, add it to the library, and if you need a part or a service, the request is already on our desk.

Can you source a Emergency Generator Set part?

Yes. Tell us the manufacturer, the model and what you need — our desk asks the right suppliers from a network of over 114,000 companies and comes back with a quote or a sourcing plan.