Central Cooler (Plate Type) · Heat Exchangers

Class-certified type (DNV register) · technical data sheet not yet verified​​⁠⁠⁠⁠​‌‌‍⁠‌‌‍‌‍‍​​‍

Alfa Laval CB210 copper-brazed plate heat exchanger for marine industrial cooling. Plate count 20-250, max flow rate 155 m3/h, design pressure 33 bar. Part of the CB series for hot water, district heating, marine cooling and HVAC duties.

Specifications

Technical data.

Do you have the manufacturer datasheet for this model? Send it with the enquiry form — we check it and name the source.

Heat Exchanger TypeAlfa Laval Brazed & Fusion-Bonded Plate Heat Exchanger (CB / AlfaNova)
Inspection

Inspector Detail

Common issues

  • Fouling or scaling on the water side reduces heat transfer and widens the approach temperature versus commissioning
  • Copper-brazed plates are not suited to raw seawater duty - confirm the plate material (CB copper-brazed vs AlfaNova fusion-bonded stainless) matches the actual application before use
  • Brazed joint leakage from thermal cycling fatigue after years in service, visible as weeping or staining at the seams
  • Partial blockage from debris or marine growth when the upstream strainer is missing or poorly maintained
  • Reduced efficiency from a reversed or otherwise incorrect flow connection instead of true counter-flow
  • External corrosion at carbon steel connection flanges or piping if coatings are not maintained
  • Freeze damage if the unit is left water-filled and static in cold layup without draining or glycol protection

Inspection checklist

  • Log inlet/outlet temperatures on both sides and compare the approach temperature against the commissioning figure
  • Check pressure drop across the unit against the baseline reading
  • Inspect brazed seams and connection welds for weeping, staining or corrosion products
  • Confirm the plate material certificate on file matches the actual duty (seawater vs closed freshwater/oil circuit)
  • Check the upstream strainer/basket for fouling or damage
  • Inspect mounting brackets and supports for vibration-related cracking
  • Sample both circuits for cross-contamination (oil traces in cooling water or vice versa)
  • Check insulation/lagging condition if fitted for a hot-side duty

Service intervals

Performance check (approach temperature / pressure drop)at each routine engine room round, trended monthly
Upstream strainer cleaningmonthly to quarterly depending on water source cleanliness
Chemical CIP cleaningtypically every 6-24 months depending on water quality - condition based
Visual leak and corrosion inspectionat each planned maintenance or class survey window

Typical intervals for this design class, not the manufacturer’s figures for your model. The manufacturer’s manual is binding.

Typical wear limits

Pressure drop rise above commissioning baselinecommonly used as a cleaning trigger once it rises on the order of 20-40% above the commissioning figure - confirm against the unit's own commissioning data, not a fixed number
Approach temperature rise above designa sustained rise of a few degrees C above the design/commissioning approach temperature is a typical fouling indicator
Plate pack differential pressure baselinerecord the reading at commissioning or last cleaning as the reference point - there is no single generic figure, since it depends on plate count and flow rate for the specific unit

Ranges are typical for this design class. Always confirm against the manufacturer documentation for your serial number.

Critical spares

  • Isolation/shutoff valves for both circuits
  • Pressure and temperature instrumentation for the monitoring loop
  • Upstream strainer basket/mesh elements
  • Gasket sets for the connection flanges
  • Corrosion-resistant mounting hardware
  • A like-for-like replacement unit - CB-series cores are brazed, not gasketed, and cannot be replated in the field, so a badly fouled or leaking unit is normally renewed as a whole

Safety

  • Pressure-retaining part rated to 33 bar design pressure - never pressure test beyond the design rating
  • Hot surfaces on the warm side of the exchanger - guard or insulate against contact burns
  • Trapped pressure and thermal expansion when isolated - vent before breaking any connection
  • Chemical exposure risk during CIP circulation with acid or alkaline cleaning agents - follow the cleaning chemical's own PPE requirements

Class survey

Central coolers are pressure-retaining parts and are typically covered under the general machinery/piping survey rather than as a standalone item; class wants evidence of correct material certification for the duty, pressure test records where renewed, and confirmation the cooling water system meets its rated flow and temperature. Where the unit is critical to a class-essential system, condition evidence may be requested at Continuous Survey Machinery intervals.

Estimated lifetime: Not meaningfully expressed in running hours - brazed plate coolers are normally retired on condition (persistent fouling or leakage) rather than an hours-based schedule; well-maintained units in this class commonly remain in service 15-25 years.

Need this part?

Request a quote for this model.

Free of charge — send us your request for Alfa Laval equipment. Our team checks it and replies by e-mail.

For marine equipment hardly any maker or authorised dealer will name a price while the vessel is unknown. With the vessel details, availability and price can be settled faster; without them we may have to ask first, which costs a few days. If you are not allowed to name the vessel, a photo of the rating plate is enough — attach it below or send it as a reply to our confirmation e-mail.

Your contact details are not published. No account required.
Related models

Also in Central Cooler (Plate Type).

Other models of the same equipment type, Alfa Laval first.

By manufacturer Alfa LavalWärtsiläAPVGEASondexAll manufacturersSpare parts by equipmentNew here? Create a free account Can't read the plate? Try the nameplate scanner All Alfa Laval models More like Alfa Laval CB210
More than the data sheet shows

We answer by e-mail, never with an automatic reply.

Tell us what you need for this Alfa Laval CB210 — a part, a service call, a second opinion. Are you Alfa Laval? Claim this brand page.

Service engineer? Write the day report for this CB210 in OceanSphere Work — photos, hours and parts, as a PDF for the owner. Try it free for 14 days →

Frequently asked

Questions that come up with this equipment.

Is this model's data free?

Yes. Specifications, documents and service notes for this model are readable without an account. An account adds saved searches and requests, nothing is taken away.

Can you find a part for this exact model?

Yes. Tell us the manufacturer, the model and what you need — a person reads every request and replies by e-mail.

The specifications look wrong — what now?

Send us the nameplate or the correct value. We check it against the manufacturer datasheet or class-society record and update the page.