Dräger Flame 2300 — UV/IR dual-sensor flame detection for hydrocarbon fires.

Components & Design

Component data being added…

Technical Data

Sensor Type Dual UV/IR flame detector
Fire Types Hydrocarbon-based fires
Reliability High immunity to false alarms
Output Modes Multiple output configurations
Approvals Explosion-proof rated
Application Oil and Gas Industry

🤖 Ask about this model

One free question — answered like a marine engineer. No account needed.

Common failures & inspection points

Optical window contamination (dust, oil, moisture, soot)

Visually inspect optical window for debris; perform automatic built-in test (BIT) for window contamination; clean with lint-free cloth and isopropyl alcohol if contamination detected; even minor contamination can reduce sensitivity by up to 50% per NFPA 72

Sensor sensitivity drift or degradation

Perform sensitivity testing using manufacturer-approved test methods (e.g., Dräger FS-5000 flame simulator for Flame detectors); test within 1 year of installation and every 2 years thereafter; sensors outside rated range must be cleaned, recalibrated, or replaced

Mechanical obstructions blocking field of view

Verify unobstructed field of view per specifications; check for dust, condensation, or physical objects blocking detector line of sight; confirm mounting position and alignment; use visual technology (Flame 5000) or bore-sight tools to verify clear optical path

Electrical and communication failures (loss of signal, intermittent faults)

Verify 18-32 VDC power supply and correct polarity; test HART/Modbus communication if equipped; check 4-20 mA signal output (normal ~4 mA, warning ~16 mA, alarm 20 mA); perform monthly functional tests; verify LED indicator status (green=normal, yellow=fault, red=radiation detected)

Environmental stress (temperature extremes, harsh conditions, salt spray)

Confirm detector rated for actual operating environment (-60°C to +85°C range for Flame 5000; ATEX/IECEx for hazardous areas); inspect for corrosion of stainless steel or aluminum housing; in offshore/dusty environments increase cleaning frequency to quarterly or monthly vs. annual minimum

Type-general inspection and maintenance points for this equipment category — not model-specific.

Suppliers & Spare Parts

Direct links to manufacturer, datasheet, spare-parts portal and dealers — request access below.

📄 Request sourcing links & documents
🛠 Manage this equipment in your fleet