Tyco (Johnson Controls) AquaMist ULF AM11 — Ultra Low Flow (Low-pressure) closed (automatic) nozzle for Class A fire suppression in engineered water mist systems.

Specifications

Technical data.reference — unverified

Do you have the manufacturer datasheet for this model? Send it with the enquiry form — we check it and name the source.

Betriebsdruck7-12 bar (101.5-174.0 psi)
DatenpunktTFP2211
Inspection

Inspector Detail

Common issues

  • Nozzle orifice or upstream strainer blockage from pipe scale or debris, reducing discharge performance
  • Thermal (glass bulb) release element painted over or contaminated, delaying or preventing activation
  • Incorrect temperature-rated bulb fitted after a nozzle replacement
  • Corrosion or pitting of stainless steel/brass nozzle bodies in an aggressive engine room atmosphere
  • Missing or damaged protective dust cap allowing pre-activation blockage of the orifice
  • Zone/section valve failing to open fully on test, reducing pressure delivered at the nozzle

Inspection checklist

  • Visual check of every nozzle for missing/painted bulb, dust cap in place, and no physical damage
  • Verify nozzle orientation and spacing have not been altered by adjacent pipework or equipment changes
  • Check pipework and strainers for internal corrosion or scale during periodic flushing
  • Functional test of the pump unit and zone/section valves to design pressure per the approved test procedure
  • Verify pressure gauge readings at test points fall within the design range for this nozzle type
  • Check nozzle count and layout against the approved fire control drawing for the protected space
  • Confirm automatic and manual release, plus alarm functions, operate correctly
  • Inspect the pump skid, accumulator and associated piping for leaks

Service intervals

Visual inspection of all nozzles (bulb, cap, orientation)every 12 months
Pressure/flow functional test of pump unit and zone valvesevery 12 months, per the approved maintenance schedule
Strainer cleaning/inspectionevery 12 months or per maker instructions
Full system discharge test (representative section)per class/flag requirement, commonly at 5-year survey intervals

Typical intervals for this design class, not the manufacturer’s figures for your model. The manufacturer’s manual is binding.

Typical wear limits

Nozzle/system operating pressuredesigned for 7-12 bar (101.5-174.0 psi) at the nozzle per the maker's data - confirm the actual figure against the vessel-specific approved hydraulic calculation, not this range alone

Ranges are typical for this design class. Always confirm against the manufacturer documentation for your serial number.

Critical spares

  • Replacement nozzles of the correct type and thermal rating (closed automatic, ultra-low-flow)
  • Spare glass bulb release elements of the matching temperature rating
  • Nozzle dust caps
  • Strainer elements
  • Zone/section valve seals and actuator components

Safety

  • System piping operates at 7-12 bar - isolate and depressurize before maintenance
  • An incorrect bulb temperature rating can cause nuisance activation or fail to activate in a real fire
  • Nozzles are tested devices - fitting a non-approved substitute invalidates the Class A fire test basis for the protected space
  • Residual pressure/water hammer risk when reopening an isolated section

Class survey

Water mist (Hi-Fog type) systems are Continuous Survey Machinery items on classed vessels; surveyors typically review maintenance records for periodic pump/valve function tests and nozzle visual condition, and check that any replacement nozzles carry the same type approval as the original installation.

Need this part?

Request a quote for this model.

Free of charge — send us your request for Tyco / Johnson Controls equipment. Our team checks it and replies by e-mail.

For marine equipment hardly any maker or authorised dealer will name a price while the vessel is unknown. With the vessel details, availability and price can be settled faster; without them we may have to ask first, which costs a few days. If you are not allowed to name the vessel, a photo of the rating plate is enough — attach it below or send it as a reply to our confirmation e-mail.

Your contact details are not published. No account required.
Related models

Also in Water Mist System (Hi-Fog).

Other models of the same equipment type, Tyco / Johnson Controls first.

By manufacturer MarioffTycoMarioff Hi-FogDanfoss SemcoUltra FogAquasys / TycoHanla IMSVid Fire-Kill ApSAutronicaDanfoss SEM-SAFEBSMI / Shanghai BaolongG W SPRINKLERViking Life-Saving EquipmentYamato Protec CorporationFikeAll manufacturersSpare parts by equipmentNew here? Create a free account Can't read the plate? Try the nameplate scanner All Tyco / Johnson Controls models More like AquaMist ULF AM11
More than the data sheet shows

We answer by e-mail, never with an automatic reply.

Tell us what you need for this Tyco / Johnson Controls AquaMist ULF AM11 — a part, a service call, a second opinion. Are you Tyco / Johnson Controls? Claim this brand page.

Service engineer? Write the day report for this AquaMist ULF AM11 in OceanSphere Work — photos, hours and parts, as a PDF for the owner. Try it free for 14 days →

Frequently asked

Questions that come up with this equipment.

Is this model's data free?

Yes. Specifications, documents and service notes for this model are readable without an account. An account adds saved searches and requests, nothing is taken away.

Can you find a part for this exact model?

Yes. Tell us the manufacturer, the model and what you need — a person reads every request and replies by e-mail.

The specifications look wrong — what now?

Send us the nameplate or the correct value. We check it against the manufacturer datasheet or class-society record and update the page.