"> Kelvion GB-DW Series
⚓ Working on this equipment?
Ask the AI troubleshooter, log your hours on board and turn them into invoice-ready service reports — for this exact model.
Start free — 14 days →
No credit card required
🔧 3 verified suppliers & service companies for Kelvion in the Maritime Network Find suppliers →
Kelvion

GB-DW Series

Kelvion GB-DW Series — Applications requiring media separation and safety.

Components & Design

Component data being added…

Technical Data

Max Pressure 45 bar (653 psi)
Max Temperature -196 to +200°C
Brazing Material Copper
Design Double-wall safety construction
Special Features Reliable medium separation, space-saving, safe for sensitive applications

🤖 Ask about this model

One free question — answered like a marine engineer. No account needed.

Common failures & inspection points

Pressure and Temperature Fluctuations

Regularly monitor gauge readings for abnormal pressure and temperature variations; ensure they remain within design specifications; check for erratic behavior indicating potential internal degradation or blockage

External Leakage Detection

Visual inspection of plate pack exterior, especially at gaps and interfaces between plates; check for moisture, drips, or residue indicating micro-leaks; perform dye testing at 0.6 times design pressure for 30 minutes with one side pressurized and other unpressurized; use hydrogen/nitrogen mixture leak tracking for material fatigue detection

Plate Fouling and Deposit Buildup

Inspect plates visually for debris, sediment, or scale deposits; assess flow passages for blockage; perform hydro-blasting or chemical CIP cleaning if fouling detected; verify plate cleanliness meets design specifications to maintain heat transfer efficiency

Fastening Bolt Integrity

Check all fastening bolts for looseness, corrosion, or degradation; verify proper torque specifications are maintained; inspect for vibration-induced loosening; replace corroded bolts with specifications matching original design requirements

Brazing Material Integrity (Copper/Nickel/VacInox)

Visually inspect brazing joints for cracks, voids, or separation; perform dye penetrant testing if cracks suspected; check for color change or corrosion in brazed areas; verify no signs of hydrogen embrittlement or stress corrosion in high-pressure models; use ultrasonic or helium leak detection for structural integrity assessment

Type-general inspection and maintenance points for this equipment category — not model-specific.

Suppliers & Spare Parts

Direct links to manufacturer, datasheet, spare-parts portal and dealers — request access below.

📄 Request sourcing links & documents
🛠 Manage this equipment in your fleet

Cases, daily reports, timesheets and AI troubleshooting in the OceanSphere Marine app — free for 14 days.

Start free trial →
🔎 Suppliers & service for this equipment

Find manufacturers, repair shops and spare-part dealers in the Maritime Network — our global company directory.

Maritime Network →
Equipment Model #148223 · ✓ still in production