Kelvion GBE-GKE Series — Hydronics, hot water systems, regenerative applications, decentralized systems.

Components & Design

Component data being added…

Technical Data

Max Pressure 30-35 bar (435-507 psi)
Max Temperature Up to 200°C
Brazing Material Copper
Design Modular construction
Special Features High efficiency, low investment costs, ConBraze design available, economical solution

🤖 Ask about this model

One free question — answered like a marine engineer. No account needed.

Common failures & inspection points

Pressure and Temperature Fluctuations

Regularly monitor gauge readings for abnormal pressure and temperature variations; ensure they remain within design specifications; check for erratic behavior indicating potential internal degradation or blockage

External Leakage Detection

Visual inspection of plate pack exterior, especially at gaps and interfaces between plates; check for moisture, drips, or residue indicating micro-leaks; perform dye testing at 0.6 times design pressure for 30 minutes with one side pressurized and other unpressurized; use hydrogen/nitrogen mixture leak tracking for material fatigue detection

Plate Fouling and Deposit Buildup

Inspect plates visually for debris, sediment, or scale deposits; assess flow passages for blockage; perform hydro-blasting or chemical CIP cleaning if fouling detected; verify plate cleanliness meets design specifications to maintain heat transfer efficiency

Fastening Bolt Integrity

Check all fastening bolts for looseness, corrosion, or degradation; verify proper torque specifications are maintained; inspect for vibration-induced loosening; replace corroded bolts with specifications matching original design requirements

Brazing Material Integrity (Copper/Nickel/VacInox)

Visually inspect brazing joints for cracks, voids, or separation; perform dye penetrant testing if cracks suspected; check for color change or corrosion in brazed areas; verify no signs of hydrogen embrittlement or stress corrosion in high-pressure models; use ultrasonic or helium leak detection for structural integrity assessment

Type-general inspection and maintenance points for this equipment category — not model-specific.

Suppliers & Spare Parts

Direct links to manufacturer, datasheet, spare-parts portal and dealers — request access below.

📄 Request sourcing links & documents
🛠 Manage this equipment in your fleet

Cases, daily reports, timesheets and AI troubleshooting in the OceanSphere Marine app — free for 14 days.

Start free trial →
🔎 Suppliers & service for this equipment

Find manufacturers, repair shops and spare-part dealers in the Maritime Network — our global company directory.

Maritime Network →
Equipment Model #148222 · ✓ still in production