Funke

GPLKS

Funke GPLKS — Doppelwand-Sicherheitsvariante der GPLK-Serie.

Inspector Detail

Common issues

  • Internal plate leakage from thermal fatigue cracking after years of cycling
  • Fouling/scaling on the water side reducing heat transfer, seen as rising approach temperature
  • Leak-detection port on the double-wall safety channel weeping, indicating a breached plate
  • Brazed joint corrosion at connections where dissimilar metals or poor water treatment is present
  • Reduced flow from partial blockage, since a brazed plate pack cannot be mechanically opened for cleaning
  • Copper braze attack from aggressive or high-chloride cooling water

Inspection checklist

  • Check pressure drop and approach temperature against the commissioning baseline to detect fouling
  • Inspect the leak-detection/drainage port on the safety channel for any trace of fluid
  • Verify insulation and connections are free of external corrosion or weeping
  • Confirm operating pressure and temperature remain within the plate rating
  • Review water treatment/dosing records for the cooling circuit
  • Chemically clean (CIP), rather than mechanically open, per manufacturer instructions if fouling is suspected

Service intervals

Performance check (approach temperature, pressure drop) vs baseline 6 months
Leak-detection port inspection at each engine room round, minimum monthly
Chemical (CIP) cleaning if fouling indicated as needed, guided by performance trend
Full external and connection inspection annually or at class survey

Typical wear limits

Maximum rated operating pressure/temperature 30 bar / +200 C as stated by the manufacturer - never exceed, confirm against the nameplate for this specific unit

Ranges are typical for this design class. Always confirm against the manufacturer documentation for your serial number.

Critical spares

  • Complete replacement unit (brazed plate packs are not field-repairable or re-brazable)
  • Gaskets/seals for connection flanges (not the internal brazed joints)
  • Pressure and temperature sensors/gauges fitted to the unit
  • Isolation valves and strainer elements on the connecting pipework

Safety

  • The double-wall design exists specifically to stop the two media mixing if one plate pack leaks - never bypass or blank the drainage/detection port
  • Unit can be hot and under pressure; isolate and depressurise both circuits before any connection work
  • Do not attempt to mechanically open a brazed plate pack - it is not designed to be disassembled

Class survey

Class treats the leak-detection/drain port on double-wall safety heat exchangers as the key survey item - surveyors expect it logged as checked and dry at each round, since it is the main external evidence that the internal barrier between the two media is intact.

Estimated lifetime: No fixed running-hours limit for a brazed unit; service life is governed by fouling/corrosion trend rather than hours, and commonly exceeds 15-20 years in a closed circuit with good water treatment - open or raw-water circuits with poor treatment can fail much sooner.

Components & Design

Component data being added…

Technical Data

Lötmaterial Kupfer
Konstruktion Doppelwand mit Sicherheitsfunktion
Wellprofil V-Wellenprofil
Max. Betriebsdruck 30 bar
Max. Betriebstemperatur +200°C

🤖 Ask about this model

One free question — answered like a marine engineer. No account needed.

Common failures & inspection points

Solder defects and brazing defects

Visual inspection for voids, porosity and predetermined fracture points in solder joints; pressure test (helium-hydrogen test gas mixture: 95% nitrogen + 5% hydrogen) for detection of microscopically small leaks through hydrogen diffusion

Corrosion and erosion of plates

Visual inspection for corrosion scars, surface rust, intergranular corrosion and pitting on plate surfaces and solder lines; surface roughness measurement for early detection of erosion in aggressive media

Thermal fatigue and cracks

Surface crack inspection by penetrant testing (penetrant method) or eddy current testing; thermal load monitoring through pressure and temperature difference measurement; vibration testing during rapid temperature changes

Sealing seat and media leaks

Pressure test (operating pressure + 50%), leak tests with hydrogen gas detectors; inspection for deterioration of seal through swelling or hardening; inspection of leakage gap in double-wall designs (GPLS, SPL)

Pressure drop and contamination

Measurement of current pressure drop and comparison with nominal value; inspection flushing test with test fluid to detect deposits and contamination; cleaning when limit values are exceeded; inspection of filters for degree of contamination

Type-general inspection and maintenance points for this equipment category — not model-specific.

Suppliers & Spare Parts

Direct links to manufacturer, datasheet, spare-parts portal and dealers — request access below.

📄 Request sourcing links & documents
🛠 Manage this equipment in your fleet

Cases, daily reports, timesheets and AI troubleshooting in the OceanSphere Marine app — free for 14 days.

Start free trial →
🔎 Suppliers & service for this equipment

Find manufacturers, repair shops and spare-part dealers in the Maritime Network — our global company directory.

Maritime Network →
Equipment Model #148203 · ✓ still in production