Grasso V 1100 Series
Grasso (GEA) Grasso V 1100 Series — Compressors.
Inspector Detail
▸
Common issues
- Crankcase oil carry-over from poor oil separation causing low oil pressure trips
- Suction/discharge valve plate wear leading to reduced capacity and elevated discharge temperature
- Shaft seal leakage causing slow refrigerant and oil loss
- Capacity control mechanism (slide valve or cylinder unloader) sticking
- High discharge temperature from low suction superheat setting or leaking valves
- Vibration or knocking from worn connecting rod bearings or piston rings
- Refrigerant leakage at gaskets/glands - safety-critical if the system uses ammonia
Inspection checklist
- Check crankcase oil level and condition; sample for moisture/acid content on ammonia systems
- Inspect suction/discharge valve plates for wear or pitting at overhaul
- Measure discharge temperature and compare against the safe operating limit
- Check shaft seal for leakage or weeping
- Test low/high pressure and low oil pressure safety cutouts
- Inspect capacity control mechanism for correct, smooth operation
- Check vibration levels and foundation/mounting bolt tightness
- Verify refrigerant charge and leak-test with an approved detector
Service intervals
| Oil change | commonly every 2,000-4,000 running hours or annually, whichever comes first - confirm against GEA's maker manual |
| Oil filter replacement | commonly every 500-1,000 running hours |
| Safety cutout (pressure/oil) function test | annually, as part of periodical survey |
| Valve plate inspection | at major overhaul, commonly in the 8,000-12,000 hour range but strongly duty-dependent |
Typical wear limits
| Shaft seal leakage | should stay within the maker's specified drip/weep allowance; continuous leakage is not acceptable - confirm the exact figure against GEA's manual |
| Valve plate condition | renew when sealing surfaces show visible pitting or when capacity loss exceeds roughly 10% of rated output - confirm against GEA's overhaul criteria rather than a fixed clearance number, which is not confidently known for this specific series |
Ranges are typical for this design class. Always confirm against the manufacturer documentation for your serial number.
Critical spares
- Suction/discharge valve plate set
- Shaft seal kit
- Piston rings
- Oil filter elements
- Cylinder head/valve plate gasket set
- Refrigerant-side safety relief valve
Safety
- If the system uses ammonia (NH3): toxic and flammable gas - work in a ventilated space, keep breathing apparatus available, no naked flames nearby
- High-pressure refrigerant release risk during valve plate or gasket work - fully isolate and depressurise first
- Hot surfaces at the compressor head and discharge line
- Confirm gas-free/ventilated status before entering an enclosed machinery space after any suspected leak
Class survey
Where the refrigeration plant serves an essential service (reefer cargo, crew provisions), the compressor typically falls within Continuous Survey Machinery scope. Class wants safety cutout test records, and - on ammonia systems - a gas detection log and evidence of periodic oil/refrigerant condition checks.
Components & Design
Component data being added…
Technical Data
🤖 Ask about this model
One free question — answered like a marine engineer. No account needed.
Suppliers & Spare Parts
Direct links to manufacturer, datasheet, spare-parts portal and dealers — request access below.
📄 Request sourcing links & documentsCases, daily reports, timesheets and AI troubleshooting in the OceanSphere Marine app — free for 14 days.
Start free trial →Find manufacturers, repair shops and spare-part dealers in the Maritime Network — our global company directory.
Maritime Network →