Grasso V 700 800/15
Grasso (GEA) Grasso V 700 800/15 — 15 bar.
Inspector Detail
▸
Common issues
- Valve plate wear or breakage causing reduced capacity and abnormal knocking
- Crankcase oil carryover into the refrigerant circuit, reducing heat exchanger efficiency
- Shaft seal leakage - a known wear item on reciprocating ammonia compressors
- Liquid slugging from a flooded start or poor suction superheat control, damaging valves or pistons
- Capacity control (unloader) malfunction affecting part-load operation
- Bearing wear from inadequate lubrication or oil degradation
- High discharge temperature from low suction superheat, worn valves or a fouled condenser
Inspection checklist
- Check crankcase oil level and condition, including ammonia dilution
- Check discharge and suction valve plates at scheduled opening for wear or breakage
- Check shaft seal for leakage or weeping
- Check capacity control (unloader) function across load steps
- Monitor discharge temperature and pressure trend against baseline
- Check safety/relief valve setting and test date
- Inspect coupling/drive alignment
- Check vibration levels at running speed
- Verify oil separator function and oil return
Service intervals
| Oil change/analysis | commonly every 2,000-4,000 running hours or annually - confirm against maker manual |
| Valve plate inspection | at scheduled opening, typically every 8,000-12,000 h depending on duty |
| Shaft seal renewal | on evidence of leakage beyond the allowable limit, or at major overhaul |
| Safety/relief valve test | annually, per class/flag requirement for pressure vessels and refrigeration systems |
| Ammonia leak detection system check | commonly a monthly function test, per class/statutory requirement |
Typical wear limits
| Shaft seal leakage | any continuous weeping beyond the maker's allowable drip rate calls for seal renewal - confirm against maker limit |
| Valve plate wear | no generic figure - assess against the maker's inspection criteria at each opening |
Ranges are typical for this design class. Always confirm against the manufacturer documentation for your serial number.
Critical spares
- Suction and discharge valve plate sets
- Shaft seal (mechanical seal) kit
- Gasket/O-ring set for cylinder head and crankcase
- Unloader/capacity control components
- Oil filter elements
- Pre-set spare safety relief valve
Safety
- Ammonia (R717) is toxic and flammable in certain concentrations - full PPE including gas-tight suit and breathing apparatus is required for refrigerant-side work
- Confirm the machinery space ammonia detection/alarm is functional before entering the compressor room
- Isolate and pump down high-pressure refrigerant lines before opening any joint
- Electrically isolate and de-energise the crankcase heater before internal work
- Emergency ammonia shower/eyewash and escape routes must be accessible and unobstructed
Class survey
Ammonia refrigeration compressors of this type typically fall within the scope of the vessel's refrigeration plant survey; class wants records of scheduled valve/seal maintenance, current safety/relief valve test certificates, and evidence that ammonia detection and emergency systems are tested per the statutory schedule.
Components & Design
Component data being added…
Technical Data
🤖 Ask about this model
One free question — answered like a marine engineer. No account needed.
Suppliers & Spare Parts
Direct links to manufacturer, datasheet, spare-parts portal and dealers — request access below.
📄 Request sourcing links & documentsCases, daily reports, timesheets and AI troubleshooting in the OceanSphere Marine app — free for 14 days.
Start free trial →Find manufacturers, repair shops and spare-part dealers in the Maritime Network — our global company directory.
Maritime Network →