Funke FP 04 50kW LO cooling
Funke Funke FP 04 50kW LO cooling — Heat Exchangers, LO cooling.
Inspector Detail
▸
Common issues
- Fouling/scaling on the cooling water side reducing heat transfer efficiency
- Gasket degradation or hardening leading to inter-plate leakage or cross-contamination between oil and water circuits
- Plate corrosion or pitting, particularly with untreated or brackish cooling water
- Reduced LO outlet temperature control from partial flow channel blockage
- Temperature control (bypass/three-way) valve malfunction causing unstable LO temperature
- Fatigue cracking of the plate pack under repeated thermal cycling
Inspection checklist
- Monitor LO inlet/outlet temperature differential and compare against baseline
- Check for external leakage at the plate pack frame and connections
- Trend pressure drop across the exchanger (rising differential indicates fouling)
- Inspect gaskets for hardening, extrusion, or visible damage at overhaul
- Open and mechanically/chemically clean plates per maker schedule
- Verify tie-bolt torque on the plate pack frame
- Check temperature control valve function
- Sample for cross-contamination (oil in cooling water or vice versa)
Service intervals
| External leak/visual inspection | monthly |
| Performance trend review (temperature differential, pressure drop) | monthly |
| Plate pack opening and cleaning | annually, or when performance drop indicates fouling, per maker schedule |
| Gasket renewal | at each plate pack opening or per maker recommendation, typically every 3-5 years |
| Tie-bolt torque check | at each plate pack reassembly |
Typical wear limits
| Heat transfer performance drop before cleaning | typically flagged at roughly 10-15% below the commissioning baseline temperature differential - confirm against the maker's design data |
| Pressure drop increase before cleaning | typically flagged when differential pressure exceeds design value by roughly 20-30% - confirm against the maker's design data |
Ranges are typical for this design class. Always confirm against the manufacturer documentation for your serial number.
Critical spares
- Full gasket set for the plate pack
- Spare plates (a maker-recommended percentage of the pack)
- Tie-bolt set
- Temperature control valve repair kit
Safety
- Hot lube oil circuit - burn risk when opening the plate pack shortly after operation
- Incorrect tie-bolt torque during reassembly can cause plate pack leakage or gasket blow-out under pressure
- Pressurized system - isolate and depressurize/drain before opening
- Check for oil sheen in the cooling water discharge as an indicator of gasket failure/cross-contamination
Class survey
Class surveys typically check for external leakage, review pressure/temperature trend records where logged, and for exchangers serving essential systems (e.g. main engine LO cooling) confirm the arrangement matches the approved cooling system diagram.
Components & Design
Component data being added…
Technical Data
🤖 Ask about this model
One free question — answered like a marine engineer. No account needed.
Suppliers & Spare Parts
Direct links to manufacturer, datasheet, spare-parts portal and dealers — request access below.
📄 Request sourcing links & documentsCases, daily reports, timesheets and AI troubleshooting in the OceanSphere Marine app — free for 14 days.
Start free trial →Find manufacturers, repair shops and spare-part dealers in the Maritime Network — our global company directory.
Maritime Network →