Bibliothek› Safety & LSA› Branderkennungssysteme› Adressierbare Brandmeldezentrale› Zhejiang Winner Fire Fighting Equipment Co., Ltd MJPZ9
Zhejiang Winner Fire Fighting Equipment Co., Ltd

MJPZ9

Adressierbare Brandmeldezentrale · Branderkennungssysteme

Klassifizierter Typ (DNV-Register) · technisches Datenblatt noch nicht geprüft​​‍‌‍‍⁠​‍‍‌⁠‍‍​​‌‌⁠​
Beispielbild: Adressierbare Brandmeldezentrale — kein Foto dieses Modells.

MJPZ9 by Zhejiang Winner Fire Fighting Equipment Co., Ltd. DNV MED certificate MEDB00000FN.

Technische Daten

Technische Daten.

Haben Sie das Herstellerdatenblatt zu diesem Modell? Schicken Sie es mit dem Anfrageformular — wir prüfen es und nennen die Quelle.

IMO-zugelassenYes
Inspektion

Inspektor-Detail

Häufige Probleme

  • False/nuisance alarms from dust, steam or cooking fumes reaching smoke detectors in poorly chosen locations
  • Loop or zone faults from cable damage, corroded terminations or moisture ingress at junction boxes in wet spaces
  • Backup battery capacity fade, only found under a proper load test rather than a voltage check alone
  • Detector head contamination (dust, oil mist) reducing sensitivity in machinery spaces
  • Addressable module or isolator failures causing loss of a whole loop segment rather than a single point
  • Panel event log filling or clock drift, making incident review and testing records unreliable if not managed

Prüfliste

  • Functionally test a representative sample of detectors each period using the correct test method (smoke/heat/aerosol per detector type), rotating coverage so all detectors are tested over time
  • Test manual call points
  • Check loop/zone fault indication and confirm no masked or isolated points remain active
  • Load-test the backup battery, not just a voltage/float check
  • Verify changeover to backup power on simulated mains loss
  • Check sounder/visual alarm devices operate and are audible/visible at their designated locations
  • Review panel event log for repeat faults or pre-alarms that indicate a developing sensor problem
  • Confirm cause-and-effect programming (e.g. fire door release, damper closure, ventilation shutdown) still matches the vessel's current fire zone plan

Wartungsintervalle

Full functional test of the systemannually, as required for SOLAS fire detection systems
Backup battery replacementper manufacturer's rated life, typically every 4-5 years for sealed lead-acid types - confirm against this panel's battery data sheet
Detector head cleaning/sensitivity checkannually, or per maker's recommendation for the space's contamination level
Loop wiring insulation/continuity testat each annual survey or on any fault trend

Typische Intervalle für diese Bauart, keine Herstellerangabe für Ihr Modell. Verbindlich ist das Handbuch des Herstellers.

Typische Verschleißgrenzen

Detector sensitivity driftrecalibrate or renew if the panel's self-monitoring flags a sensitivity fault, or per the maker's recommended re-test interval
Backup battery capacityrenew once a load test shows capacity has fallen below the maker's rated minimum for the required standby duration

Die Bereiche sind für diese Bauklasse typisch. Maßgeblich sind stets die Herstellerunterlagen zur jeweiligen Seriennummer.

Kritische Ersatzteile

  • Smoke detector heads (addressable)
  • Heat detector heads (addressable)
  • Addressable loop isolator modules
  • Backup batteries (correct type/capacity for this panel)
  • Sounder/visual alarm devices
  • Manual call points

Sicherheit

  • Never leave a zone or detector isolated after testing without a documented compensating watch - a masked detector cannot alert to a real fire
  • Backup batteries are a chemical hazard if damaged; follow the maker's handling and disposal guidance
  • The panel must remain accessible from the continuously manned station at all times per SOLAS - do not obstruct it during other work
  • Confirm cause-and-effect actions (damper/door release) are tested in a way that does not itself create a hazard during the test

Klassenbesichtigung

SOLAS II-2 fire detection and alarm system - class/flag surveys look for evidence of periodic testing of detectors and call points, a current MED type-approval certificate reference, up-to-date cause-and-effect documentation matching the actual fire zone boundaries, and records of any isolated points being restored.

Geschätzte Lebensdauer: Not expressed in running hours; addressable fire panels are typically supported for 10-15 years, with detector heads commonly recommended for replacement or recalibration around the 10-year mark per manufacturer guidance

Klassifikation

DNV-Typzulassung

Im DNV Approval Finder gelistet, Stand unserer Erfassung. Das Zertifikat stellt DNV aus, nicht wir; den aktuellen Status prüfen Sie bei DNV.

ZertifikatMEDB00000FN
Zertifikat bei DNV öffnen
Dieses Teil gesucht?

Angebot für dieses Modell anfragen.

Kostenlos — senden Sie uns Ihre Anfrage zu Zhejiang Winner Fire Fighting Equipment Co., Ltd-Ausrüstung. Unser Team prüft sie und antwortet per E-Mail.

Für Schiffsausrüstung nennt kaum ein Hersteller oder Vertragshändler einen Preis, solange das Schiff unbekannt ist. Mit Schiffsangaben lässt sich Verfügbarkeit und Preis schneller klären; fehlen sie, müssen wir unter Umständen zuerst nachfragen, was einige Tage kostet. Dürfen Sie das Schiff nicht nennen, reicht ein Foto des Typenschilds — hängen Sie es unten an oder schicken Sie es als Antwort auf unsere Bestätigungsmail.

Ihre Kontaktdaten werden nicht veröffentlicht. Kein Konto nötig.
Verwandte Modelle

Auch in Adressierbare Brandmeldezentrale.

Weitere Modelle desselben Ausrüstungstyps, zuerst Zhejiang Winner Fire Fighting Equipment Co., Ltd.

Nach Hersteller AutronicaConsiliumSiemens Fire SafetyNotifier / HoneywellHochikiEsser / HoneywellApollo MarineThermal Ceramics UKZhejiang Winner Fire Fighting Equipment Co., LtdBIO-EXEkornes ASBrødrene AA ASCBG Systems InternationalDELIUS GmbH & Co. KGGRUPPO MASTROTTO S.p.A.Alle HerstellerErsatzteile nach AusrüstungNeu hier? Kostenloses Konto anlegen Typenschild unleserlich? Probieren Sie den Typenschild-Scanner Ähnliche wie MJPZ9
Mehr als das Datenblatt zeigt

Wir antworten per E-Mail, nie mit einer Automatik.

Sagen Sie uns, was Sie für diesen Zhejiang Winner Fire Fighting Equipment Co., Ltd MJPZ9 benötigen — ein Ersatzteil, einen Serviceeinsatz, eine zweite Meinung. Sind Sie Zhejiang Winner Fire Fighting Equipment Co., Ltd? Diese Herstellerseite beanspruchen.

Servicetechniker? Schreiben Sie den Tagesbericht für diesen MJPZ9 in OceanSphere Work — Fotos, Stunden und Teile, als PDF für den Reeder. 14 Tage kostenlos testen →

Häufig gefragt

Fragen, die bei dieser Ausrüstung aufkommen.

Sind die Daten dieses Modells kostenfrei?

Ja. Technische Daten, Dokumente und Servicehinweise zu diesem Modell sind ohne Konto lesbar. Ein Konto bringt gespeicherte Suchen und Anfragen dazu, es nimmt nichts weg.

Können Sie ein Teil genau für dieses Modell finden?

Ja. Nennen Sie uns Hersteller, Modell und Bedarf — ein Mensch liest jede Anfrage und antwortet per E-Mail.

Die Angaben scheinen falsch zu sein — was jetzt?

Schicken Sie uns das Typenschild oder den richtigen Wert. Wir prüfen ihn gegen das Herstellerdatenblatt oder den Klassifikationsdatensatz und aktualisieren die Seite.