Zhejiang Winner Fire Fighting Equipment Co., Ltd

MJPZ9

MJPZ9 by Zhejiang Winner Fire Fighting Equipment Co., Ltd. DNV MED certificate MEDB00000FN.

Inspector Detail

Common issues

  • False/nuisance alarms from dust, steam or cooking fumes reaching smoke detectors in poorly chosen locations
  • Loop or zone faults from cable damage, corroded terminations or moisture ingress at junction boxes in wet spaces
  • Backup battery capacity fade, only found under a proper load test rather than a voltage check alone
  • Detector head contamination (dust, oil mist) reducing sensitivity in machinery spaces
  • Addressable module or isolator failures causing loss of a whole loop segment rather than a single point
  • Panel event log filling or clock drift, making incident review and testing records unreliable if not managed

Inspection checklist

  • Functionally test a representative sample of detectors each period using the correct test method (smoke/heat/aerosol per detector type), rotating coverage so all detectors are tested over time
  • Test manual call points
  • Check loop/zone fault indication and confirm no masked or isolated points remain active
  • Load-test the backup battery, not just a voltage/float check
  • Verify changeover to backup power on simulated mains loss
  • Check sounder/visual alarm devices operate and are audible/visible at their designated locations
  • Review panel event log for repeat faults or pre-alarms that indicate a developing sensor problem
  • Confirm cause-and-effect programming (e.g. fire door release, damper closure, ventilation shutdown) still matches the vessel's current fire zone plan

Service intervals

Full functional test of the system annually, as required for SOLAS fire detection systems
Backup battery replacement per manufacturer's rated life, typically every 4-5 years for sealed lead-acid types - confirm against this panel's battery data sheet
Detector head cleaning/sensitivity check annually, or per maker's recommendation for the space's contamination level
Loop wiring insulation/continuity test at each annual survey or on any fault trend

Typical wear limits

Detector sensitivity drift recalibrate or renew if the panel's self-monitoring flags a sensitivity fault, or per the maker's recommended re-test interval
Backup battery capacity renew once a load test shows capacity has fallen below the maker's rated minimum for the required standby duration

Ranges are typical for this design class. Always confirm against the manufacturer documentation for your serial number.

Critical spares

  • Smoke detector heads (addressable)
  • Heat detector heads (addressable)
  • Addressable loop isolator modules
  • Backup batteries (correct type/capacity for this panel)
  • Sounder/visual alarm devices
  • Manual call points

Safety

  • Never leave a zone or detector isolated after testing without a documented compensating watch - a masked detector cannot alert to a real fire
  • Backup batteries are a chemical hazard if damaged; follow the maker's handling and disposal guidance
  • The panel must remain accessible from the continuously manned station at all times per SOLAS - do not obstruct it during other work
  • Confirm cause-and-effect actions (damper/door release) are tested in a way that does not itself create a hazard during the test

Class survey

SOLAS II-2 fire detection and alarm system - class/flag surveys look for evidence of periodic testing of detectors and call points, a current MED type-approval certificate reference, up-to-date cause-and-effect documentation matching the actual fire zone boundaries, and records of any isolated points being restored.

Estimated lifetime: Not expressed in running hours; addressable fire panels are typically supported for 10-15 years, with detector heads commonly recommended for replacement or recalibration around the 10-year mark per manufacturer guidance

Components & Design

Component data being added…

Technical Data

imo approved True

🤖 Ask about this model

One free question — answered like a marine engineer. No account needed.

Suppliers & Spare Parts

Direct links to manufacturer, datasheet, spare-parts portal and dealers — request access below.

📄 Request sourcing links & documents
🛠 Manage this equipment in your fleet

Cases, daily reports, timesheets and AI troubleshooting in the OceanSphere Marine app — free for 14 days.

Start free trial →
🔎 Suppliers & service for this equipment

Find manufacturers, repair shops and spare-part dealers in the Maritime Network — our global company directory.

Maritime Network →

DNV type approval

Verified against the DNV Approval Finder — the certificate below is issued by DNV, not by us.

Certificate
MEDB00000FN
Open the certificate at DNV →