"> KSB Etanorm-Fire
⚓ Working on this equipment?
Ask the AI troubleshooter, log your hours on board and turn them into invoice-ready service reports — for this exact model.
Start free — 14 days →
No credit card required
KSB

Etanorm-Fire

KSB Etanorm-Fire — DIN-Standard-Variante für SOLAS-Hauptfeuerlöschpumpen auf europäischen Newbuilds.

30-1000 m³/h
Capacity
Sea water
Medium

Components & Design

Component data being added…

Technical Data

pump type End-suction centrifugal fire pump
variant count approx 80
period start year 1990
drive type Electric
construction DIN/EN 733, bronze impeller option

🤖 Ask about this model

One free question — answered like a marine engineer. No account needed.

Common failures & inspection points

Mechanical seal: leakage, wear of sealing surfaces, surface damage

Visual inspection of seal housing and shaft for drip traces or moisture; pressure testing with manometer to detect pressure drops; soap solution for bubble formation and leak location; control of scavenge system for blockages (overheating causes premature wear). Monitor leak rate: mechanical seal normal <0.006 l/h

Bearing: wear, temperature rise, faulty lubrication (oil/grease)

Measure bearing temperature and compare with manufacturer specifications; check vibration and smooth running of pump and motor; check lubricant supply and exchange intervals; inspect elastic transmission elements (coupling bolts, discs, packages) for wear; control coupling alignment. Coupling replacement recommended in case of wear

Impeller/wear rings: wear on running and suction side, contamination damage, surface corrosion

Visual-mechanical inspection for wear of sealing rings and impeller wear protection; check for wear of shaft keyways and bearing seats; clearance inspection (<1 µm normal value for seals); check wear ring material (hard-chromed or nitrided for abrasive media >800-1000 HV surface hardness). Replace damaged or worn parts with genuine spare parts

Cavitation: pressure drop below vapor pressure, bubble implosion, material erosion on housing and impeller

Compare NPSH value of system (NPSHA) against required pump NPSH (NPSHR) from data sheet; NPSHA must be >= NPSHR over entire operating range; monitor pump smooth running and operating noise (cavitation noise = rough operating noise); perform pressure test bench tests to simulate cavitation conditions; check suction conditions and system design; visually inspect housing and impeller for pitting and surface erosion

Systemkomponenten: Rohrleitungen, Armaturen, Schaltfunktion, elektronische Überwachung, Korrosion

Inspect piping and fittings for wear, corrosion and functionality; test pump control and switching function; check electronic monitoring systems; inspect general housing corrosion and bearing contamination traces; perform surface cleaning (DO NOT flush, instead apply protective grease); document all inspection results

Type-general inspection and maintenance points for this equipment category — not model-specific.

Service & Maintenance

DIN standard.

Suppliers & Spare Parts

Direct links to manufacturer, datasheet, spare-parts portal and dealers — request access below.

📄 Request sourcing links & documents
🛠 Manage this equipment in your fleet

Cases, daily reports, timesheets and AI troubleshooting in the OceanSphere Marine app — free for 14 days.

Start free trial →
🔎 Suppliers & service for this equipment

Find manufacturers, repair shops and spare-part dealers in the Maritime Network — our global company directory.

Maritime Network →

Replacement Parts

KSB MarineCare global.
Equipment Model #37638 · ✓ still in production