Process temperature100 °C (212 °F)
Process temperatures up to:100 °C (212 °F)
Measuring range> 0.7 g/cm³ (optionally available: > 0.5 g/cm³
>20 V>20 V
0.5a0.5A
Ambient temperature:+25 °C (+77 °F)
Process pressure:1 bar (14.5 psi)
Medium temperature:25 °C (77 °F)
Density setting:> 0.7 g/cm³
Switching time delay:Standard (0.5 s, 1 s)
Switch point (with orientation: vertical from above)13 mm (0.51 in) ± 1 mm
Hysteresismax. 3 mm (0.12 in)
Non-repeatability±1 mm (0.04 in)
Influence of medium temperature–25 µm (984 µin)/°C
Influence of medium pressure–20 µm (787 µin)/bar
Switching delay• 0.5 s when tuning fork is covered
Measuring frequencyapprox. 1 100 Hz in air
Measured errorIn event of device change: ±2 mm (0.08 in)
Switch point~10.5(0.4) ~13 (0.5) ~30 (1.2) mm (in)
Ambient temperature range–40 to +70 °C (–40 to +158 °F)
Imax:200 mA (DC-PNP), 250 mA (AC/DC)
Process temperature range–40 to +100 °C (–40 to +212 °F)
Process pressure rangeMax. –1 to +40 bar (–14.5 to +580 psi)
Density> 0.7 g/cm³ (optionally available: > 0.5 g/cm³ )
Viscosity1 to 10,000 mPa · s dynamic viscosity
Solids contentsø < 5 mm (0.2 in)
Lateral loading capacitymax. 200 N
Dimensions mm (in)40 (1.6)
IP ratingIP65/67
Dimensions136.6 (5.38)"
Pressure and temperature (maximum)+40 bar (+580 psi) at +150 °C (+302 °F)
Material316L
Pressure and temperature (maximum):+40 bar (+580 psi) at +150 °C (+302 °F)
WeightApprox. 140 g (4.938 oz)
Surface roughness Metallic surface in contact with process:Ra ≤3.2 µm (126 µin)
Supply voltage10 to 30 V DC
Power consumption< 975 mW
Current consumption< 15 mA
Residual rippleDC-PNP: 5 Vss 0 to 400 Hz
AC/DC: —
ConnectionM12 plug
Current0.5A
Voltage>20 V
Cable connectionM12 connector
Reference operating conditionsAmbient temperature: +25 °C (+77 °F)
ConnectorValve plug M16, NPT ½" for housing cover: PPSU plastic
Tuning fork Dimensions mm (in)ø17.1 (0.67)
Material:316L
Cable cross-sectionmax. 1.5 mm2 (AWG 16)
Cable diameter3.5 to 8 mm (0.14 to 0.26 in)
Reference operating Ambient temperature+25 °C (+77 °F)
Process pressure1 bar (14.5 psi)
Medium temperature25 °C (77 °F)
Density setting> 0.7 g/cm³
Switching time delayStandard (0.5 s, 1 s)
Imax200 mA (DC-PNP), 250 mA (AC/DC)
Materials not in contact with processHousing cover with M12 connector (IP65/67), Housing cover with valve plug (IP65)
Surface roughnessRa ≤3.2 µm (126 µin)
Prozesstemperatur100 °C (212 °F)
Versorgungsspannung0.5A
Material316L (1.4404/1.4435)
Druck und Temperatur (maximal)+40 bar (+580 psi) bei 150 °C (302 °F)
Dimensions136.6 (5.38)**
Schaltvermögen (3-Leiter DC-PNP)200 mA
Schaltvermögen (IO-Link)105 mA/200 mA
Versorgungsspannung (SIO Modus)10 … 30 V DC
Versorgungsspannung (IO-Link Modus)18 … 30 V DC
Leistungsaufnahme< 1 W (bei max. Last: 200 mA)
StromaufnahmeDC-PNP
< 15 mA
AC/DC
< 3,8 mA
Referenzbedingungen Umgebungstemperatur+25 °C (+77 °F)
Prozessdruck1 bar (14,5 psi)
Messstofftemperatur25 °C (77 °F)
Dichteeinstellung> 0,7 g/cm³
SchaltzeitverzögerungStandard (0,5 s, 1 s)
Schaltpunkt13 mm (0,51 in)
Hysteresemax. 3 mm (0,12 in)
Nichtwiederholbarkeit±1 mm (0,04 in) nach DIN 61298-2
Einfluss der Messstofftempe- ratur–25 µm (984 µin)/°C
Einfluss des Messstoffdru- ckes–20 µm (787 µin)/bar
Schaltverzögerung• 0,5 s bei Bedecken der Schwinggabel
• 1,0 s bei
Messfrequenzca. 1 100 Hz in Luft
UnsicherheitBei Gerätewechsel: ±2 mm (0,08 in) nach DIN 61298-2
Umgebungstemperaturbereich–40…+70 °C (–40…+158 °F)
Imax (DC-PNP)200 mA
Imax (AC/DC)250 mA
Prozesstemperaturbereich–40…+100 °C (–40…+212 °F)
Prozessdruckbereichmax. –1…+40 bar (–14,5…+580 psi)
Viskosität1...10 000 mPa · s dynamische Viskosität
Feststoffanteilø < 5 mm (0,2 in)
Seitliche Belastbarkeitmax. 200 N
Druck und Temperatur (maximal):+40 bar (+580 psi) bei +150 °C (+302 °F)
Weightca. 140 g (4,938 oz)
Operating InstructionsLiquiphant FTL31 IO-Link
Point level switch for liquids71417213
Electrical connectionM12 plug
Housing (sensor design)150 °C (302 °F)
Installation nozzleno less than the minimum diameter of 50 mm (2.0 in) mm (in)
Temperature of the electronics housing and assemblies80 °C
Installation nozzle diameter50 mm
Minimum installation nozzle diameter2.0 in
L163.9 mm (2.52 in) mm (in)
L238.0 mm (1.5 in) mm (in)
PlugM12
MAX output0.5A
MIN output0.5A
Storage temperature–40 to +85 °C (–40 to +185 °F)
Operating altitudeUp to 2 000 m (6 600 ft) above sea level
Shock resistancea = 300 m/s2 = 30 g, 3 axes x 2 directions x 3 shocks x 18 ms
Vibration resistancea(RMS) = 50 m/s2, ASD = 1.25 (m/s2)2/Hz, f = 5 to 2 000 Hz, t = 3 x 2 h
Measuring range> 0,7 g/cm³ (optional bestellbar: > 0,5 g/cm³)
RestwelligkeitDC-PNP
5 Vss 0 … 400 Hz
AC/DC
—
Electrical connection500 mA träge
KabeleinführungVentilstecker (M16x1,5; NPT ½"; QUICKON)
Leitungsquerschnittmax. 1,5 mm2 (AWG 16)
SteckerM12
P/S Nennleistung1,3 … 6 VA [W] / [VA]
Kontaktstrom0.5A
Betriebsspannung>20 V
Referenzbedingungen Prozessdruck1 bar (14,5 psi)
Referenzbedingungen Messstofftemperatur25 °C (77 °F)
Referenzbedingungen Dichteeinstellung> 0,7 g/cm³
Referenzbedingungen SchaltzeitverzögerungStandard (0,5 s, 1 s)
Einfluss der Messstofftemperatur–25 µm (984 µin)/°C
Einfluss des Messstoffdruckes–20 µm (787 µin)/bar
KlimaklasseDIN EN 60068-2-38/IEC 68-2-38: Prüf
SchutzartIP65/67 NEMA Type 4X Enclosure (Stecker M12)
Stoßfestigkeita = 300 m/s² = 30 g, 3 Achsen x 2 Richtungen x 3 Stösse x 18 ms
Schwingungsfestigkeita(RMS) = 50 m/s², ASD = 1,25 (m/s²)²/Hz, f = 5 ... 2000 Hz, t = 3 x 2 h
CertificationsprEN 60068-2-27:2007
Messstoffdichte> 0,7 g/cm³ (optional bestellbar: > 0,5 g/cm³)
Prozesstemperaturen bis100 °C (212 °F)
Betriebsart MAX>20 V
Betriebsart MIN>20 V
Current0.5A
Schaltpunkt (bei Einbaulage vertikal von oben)13 mm (0,51 in) ± 1 mm
Einfluss des Messstoffdrucks–20 µm (787 µin)/bar
Gewicht Kompaktversion mit Prozessadapter G ½" und Ventilstecker für Prozesstemperatur bis 100 °C (212 °F)ca. 140 g (4,938 oz)
Gewicht Kurzrohrversion mit Prozessadapter G ½" und Ventilstecker für Prozesstemperatur bis 150 °C (302 °F)ca. 169 g (5,961 oz)
ConnectionStecker M12
3-Leiter DC-PNPStecker M12
Kabelspezifikation - Leitungsquerschnittmax. 1,5 mm2 (AWG 16)
Kabelspezifikation - Ø3,5…8 mm (0,14…0,26 in)
Derating-kurve100 °C (212 °F)
Gehäuse (Sensordesign)100 °C (212 °F)
Ø31.5(1.24)
Ausgangsleistung0.5A
Voltage>20 V
Einfluss der Messstofftempe-ratur–25 µm (984 µin)/°C
Einfluss des Messstoffdru- ckes–20 µm (787 µin)/bar
Prozesstemperaturen bis:100 °C (212 °F)
Schaltpunkt A~13 (0.5), ~30 (1.2), ~10.5 (0.4) mm (in)
K externe Last0.5A
Maximalstrom0.5 A
Relais Betriebspannung24 V
Relais Nennleistung0,7 … 6 W
Kabel15 m
EinsatzhöheBis 2 000 m
Kurzschlussschutz3-Leiter DC-PNP: Überlastschutz/Kurzschlussschutz bei I > 250 mA; der Sensor wir
Sensor Design2 max. 100°C Prozesstemp., 3 max. 150°C Prozesstemp.
Zulassung:010 AA Ex-freier Bereich, CA, CSA General Purpose
Elektronik; Ausgang:20-253VAC/DC; 2-Leiter, 4 10-30VDC; 3-Leiter PNP
Sensor Design:2 max. 100°C Prozesstemp., 3 max. 150°C Prozesstemp.
Temperatur-40 bis +150 °C
Druck-1 bis +40 bar
Oberflächenrauigkeit3,2 μm
Umgebungs-temperatur-40…+70 °C
Sensormaterial316L
Rauhigkeit< 3,2 µm μm
Climate classDIN EN 60068-2-38/IEC 68-2-38: test Z/AD
AltitudeUp to 2 000 m (6 600 ft) above sea level
Degree of protection• IP65/67 NEMA Type 4X Enclosure (M12 connector)
Switch-on delaymax. 3 s
Einschaltverzögerungmax. 3 s
Gewinde metrischG 1"
Switching capacity (3-wire DC-PNP)200 mA
Supply voltage (SIO mode)10 to 30 VDC
Supply voltage (IO-Link mode)18 to 30 VDC