OceanSphereENGINES
Bibliothek› HVAC› Klimaanlagen› Kaltwassersatz› J&E Hall International HallScrew Semi-hermetic Air-Cooled Ammonia Chiller
J&E Hall International

HallScrew Semi-hermetic Air-Cooled Ammonia Chiller

Kaltwassersatz · Klimaanlagen

Technische Daten aus Hersteller- oder Klassequellen · noch nicht von Hand geprüft​‍‌‌​‍‌‍‌‌‌‌‍​‍​‌‍‍​

J&E Hall International HallScrew Semi-hermetic Air-Cooled Ammonia Chiller — Low-charge air-cooled ammonia chiller using HallScrew semi-hermetic single-screw compressors. Designed for cold store cooling, process cooling, and comfort cooling. Available in single or dual compressor configuration. Suitable for industrial and marine refrigeration applications.

Technische Daten

Technische Daten.

Haben Sie das Herstellerdatenblatt zu diesem Modell? Schicken Sie es mit dem Anfrageformular — wir prüfen es und nennen die Quelle.

Referenzwerte — nicht geprüft
Cooling capacity kw high temp350–960
Cooling capacity kw medium temp195–550
Cooling capacity kw low temp100–260
Temperature range cold store-18°C to +15°C
Temperature range process-25°C to +7°C

Quelle: coolingpost.com · nicht mit einem Herstellerdatenblatt abgeglichen

Inspektion

Inspektor-Detail

Häufige Probleme

  • Ammonia leakage at the compressor shaft seal, valves, or pipe joints
  • Screw compressor slide valve/capacity control sticking
  • Oil separator or oil return system fouling causing oil carryover from the compressor
  • Condenser fan motor or fan blade failure reducing head pressure control
  • Gasket or fitting degradation causing low-level ammonia odor/leaks
  • Compressor motor overheating from low refrigerant charge or a fouled condenser
  • Suction or discharge valve leakage reducing compressor capacity

Prüfliste

  • Check for ammonia odor or leaks with an appropriate detector at joints, valves, and seals
  • Inspect the condenser coil/fins for fouling and clean as needed
  • Check oil level and oil pressure differential across the compressor
  • Verify high/low pressure and oil safety cutouts trip correctly
  • Check slide valve operation and capacity control response
  • Check refrigerant charge level via sight glass or level indicator
  • Inspect suction line insulation for condensation or ice buildup
  • Test the ammonia detection/alarm system
  • Check condenser fan motors for vibration or bearing noise

Wartungsintervalle

Oil change/analysistypically 4000-8000 hours or annually, per maker's schedule
Safety cutout (HP/LP/oil) testingper class requirement, typically annually
Condenser coil cleaningquarterly or per fouling condition
Ammonia detection system calibrationper maker/class schedule, typically annually

Typische Intervalle für diese Bauart, keine Herstellerangabe für Ihr Modell. Verbindlich ist das Handbuch des Herstellers.

Typische Verschleißgrenzen

Oil moisture/acid levelmonitor via oil analysis trend against the maker's limits rather than a fixed onboard reading
Refrigerant charge levelmaintain per the sight glass/level indicator range specified by the maker - do not top up without first tracing and repairing any leak

Die Bereiche sind für diese Bauklasse typisch. Maßgeblich sind stets die Herstellerunterlagen zur jeweiligen Seriennummer.

Kritische Ersatzteile

  • Shaft seal kit for the screw compressor
  • Solenoid/expansion valve
  • Oil filter element
  • Refrigerant filter-drier
  • High/low pressure safety switch
  • Condenser fan motor
  • Refrigerant joint gasket/O-ring set

Sicherheit

  • Ammonia is toxic and, in certain concentrations, flammable - full PPE (gas-tight goggles, gloves, escape breathing apparatus) is required for any refrigerant work
  • Confirm the ammonia detection and alarm system is operational before entering the compressor/chiller space
  • Refrigerant piping and vessels are under pressure - isolate and recover charge before opening
  • Screw compressor rotating parts and drive coupling guards must be fitted
  • Ensure adequate ventilation of the machinery space per class requirements for ammonia systems

Klassenbesichtigung

Ammonia refrigeration plant is subject to class rules specific to toxic/flammable refrigerants (detection, ventilation, machinery space arrangement) in addition to standard refrigeration machinery survey. Class checks leak detection function, pressure vessel/piping certification, and relief discharge arrangements at survey.

Dieses Teil gesucht?

Angebot für dieses Modell anfragen.

Kostenlos — senden Sie uns Ihre Anfrage zu J&E Hall International-Ausrüstung. Unser Team prüft sie und antwortet per E-Mail.

Für Schiffsausrüstung nennt kaum ein Hersteller oder Vertragshändler einen Preis, solange das Schiff unbekannt ist. Mit Schiffsangaben lässt sich Verfügbarkeit und Preis schneller klären; fehlen sie, müssen wir unter Umständen zuerst nachfragen, was einige Tage kostet. Dürfen Sie das Schiff nicht nennen, reicht ein Foto des Typenschilds — hängen Sie es unten an oder schicken Sie es als Antwort auf unsere Bestätigungsmail.

Ihre Kontaktdaten werden nicht veröffentlicht. Kein Konto nötig.
Verwandte Modelle

Auch in Kaltwassersatz.

Weitere Modelle desselben Ausrüstungstyps, zuerst J&E Hall International.

Nach Hersteller CarrierDaikinHeinen & HopmanTraneYork/JohnsonNovenco MarineBronswerk MarineMcQuay MarineCruisairWebastoDometicFrigomarVeco SpA / ClimmaFrascoldOilonAlle HerstellerErsatzteile nach AusrüstungNeu hier? Kostenloses Konto anlegen Typenschild unleserlich? Probieren Sie den Typenschild-Scanner Ähnliche wie HallScrew Semi-hermetic Air-Cooled Ammonia Chiller
Mehr als das Datenblatt zeigt

Wir antworten per E-Mail, nie mit einer Automatik.

Sagen Sie uns, was Sie für diesen J&E Hall International HallScrew Semi-hermetic Air-Cooled Ammonia Chiller benötigen — ein Ersatzteil, einen Serviceeinsatz, eine zweite Meinung. Sind Sie J&E Hall International? Diese Herstellerseite beanspruchen.

Servicetechniker? Schreiben Sie den Tagesbericht für diesen HallScrew Semi-hermetic Air-Cooled Ammonia Chiller in OceanSphere Work — Fotos, Stunden und Teile, als PDF für den Reeder. 14 Tage kostenlos testen →

Häufig gefragt

Fragen, die bei dieser Ausrüstung aufkommen.

Sind die Daten dieses Modells kostenfrei?

Ja. Technische Daten, Dokumente und Servicehinweise zu diesem Modell sind ohne Konto lesbar. Ein Konto bringt gespeicherte Suchen und Anfragen dazu, es nimmt nichts weg.

Können Sie ein Teil genau für dieses Modell finden?

Ja. Nennen Sie uns Hersteller, Modell und Bedarf — ein Mensch liest jede Anfrage und antwortet per E-Mail.

Die Angaben scheinen falsch zu sein — was jetzt?

Schicken Sie uns das Typenschild oder den richtigen Wert. Wir prüfen ihn gegen das Herstellerdatenblatt oder den Klassifikationsdatensatz und aktualisieren die Seite.