EWWH-VZ
Daikin EWWH-VZ — Water-cooled inverter screw chiller with ultra-low GWP refrigerant for comfort, process and marine applications..
Components & Design
Component data being added…
Technical Data
🤖 Ask about this model
One free question — answered like a marine engineer. No account needed.
Common failures & inspection points
Inspect seawater/condenser water inlet strainer and heat exchanger tube bundle for biofouling, scale, and corrosion; clean per manufacturer interval
Check refrigerant charge, look for oil contamination, and verify absence of leaks at fittings, valve stems, and brazed joints using electronic leak detector
Verify operation of oil separator, oil reservoir level (critical for pitch/roll marine version), and oil heater function before startup
Inspect and test accelerometers (marine VZ units) that trigger EEXV control during vessel pitch/roll; confirm correct alarm and control response
Check evaporator and condenser water flow rates, inlet/outlet temperatures, and pressure drops against design values; clean strainers
Test safety and control devices: high/low refrigerant pressure cutouts, chilled water flow switch, motor overload relays, and anti-freeze protection
Inspect structural mounts, anti-vibration isolators, and pipe flexible connections for corrosion and mechanical integrity in the marine environment
Verify electrical panel condition: check terminal tightness, insulation resistance, inverter/VFD drive status and fault logs, and confirm earthing/bonding to ship's structure
Type-general inspection and maintenance points for this equipment category — not model-specific.