Hochiki SOC-24V — Conventional Photoelectric Smoke Detector.

Components & Design

Component data being added…

Technical Data

Type Photoelectric Smoke
Voltage 24VDC
Certification UL Listed

🤖 Ask about this model

One free question — answered like a marine engineer. No account needed.

Common failures & inspection points

Detector Optical Window Obstruction

Visually inspect detector lens and chamber for dust, insect contamination, or corrosion buildup. Clean or replace detector if optical transmission is compromised (use magnifying glass for small particulates).

Sensitivity Drift and Calibration

Perform semi-annual sensitivity testing using manufacturer-approved calibration tools (e.g., NSTT-C for SIJ-24 series). Verify detector responds within listed sensitivity range (typically 25%-70% obscuration for photoelectric). Replace if sensitivity cannot be recalibrated.

Installation Mounting and Alignment

Verify detectors are properly seated in bases (confirm clockwise twist-lock engagement). For beam detectors, confirm alignment within reflector center using motorized alignment verification. Check mounting hardware security and absence of vibration-induced looseness.

Electrical Continuity and Base Contact

Verify electrical connections at detector base and wiring terminals. Test continuity to control panel. For conventional detectors, confirm 24VDC supply voltage at detector head. For addressable detectors, test SCI loop continuity and polling response.

Environmental Interference and False Alarms

Inspect for sources of nuisance triggers: proximity to HVAC ducts, direct sunlight on beam detectors, steam/condensation sources near smoke detectors, or electromagnetic interference near addressable loops. Reposition detectors or install optical filters as needed per EN54 standards.

Type-general inspection and maintenance points for this equipment category — not model-specific.

Suppliers & Spare Parts

Direct links to manufacturer, datasheet, spare-parts portal and dealers — request access below.

📄 Request sourcing links & documents
🛠 Manage this equipment in your fleet

Cases, daily reports, timesheets and AI troubleshooting in the OceanSphere Marine app — free for 14 days.

Start free trial →
🔎 Suppliers & service for this equipment

Find manufacturers, repair shops and spare-part dealers in the Maritime Network — our global company directory.

Maritime Network →
Equipment Model #148989 · ✓ still in production