Marioff Hi-Fog

HI-FOG 3000 Sprinkler

Marioff Hi-Fog HI-FOG 3000 Sprinkler — Marine accommodation, public and service spaces; high-rise building atriums.

Components & Design

Component data being added…

Technical Data

Type New generation closed sprinkler
Standard IMO Res.A800(19) and IMO Res.MSC.265(84) type approved
Ceiling height VdS approved up to 10 meters
Coverage Wider coverage than HI-FOG 2000 series
Performance Faster activation and more efficient suppression

🤖 Ask about this model

One free question — answered like a marine engineer. No account needed.

Common failures & inspection points

Nozzle and spray head obstruction/clogging from water impurities or mineral deposits

Monthly visual inspection for visible blockages; annual cleaning and flushing of nozzles through strainer validation. Check strainer condition (typically 300 µm micron filters). Water quality testing per EN 14972 standards.

System pressure loss or inadequate discharge pressure (target: ~1,050 psi sprinkler, 2,300 psi discharge)

Quarterly pressure testing via pressure gauges. Verify pump discharge pressure (2,300 psi target). Check accumulator pre-charge pressure (nitrogen/compressed air). Validate integrity of high-pressure tubing for micro-cracks or corrosion.

Heat-sensitive bulb degradation, glass micro-cracks, or bulb failure in sprinklers (57°C to 141°C ratings)

Annual visual inspection of bulbs in sample sprinklers from each temperature rating. Replace bulbs showing discoloration, cloudiness, or micro-cracks. Validate bulb response through functional testing per EN 14972. Thermographic scanning of ceiling areas.

Water supply contamination, corrosion of stainless steel components (AISI 316L), or scale buildup in piping

Annual water quality analysis (potable water standard per EN 14972). Visual inspection of interior tubing sections for corrosion via test ports. Flush system at min. 5-year intervals. Inspect stainless steel tubing for surface oxidation or pitting.

Control system, PLC logic, or activation mechanism failure in LPU/EPU/GPU units

Annual functional system activation test (dry discharge test) to verify pump start, pressure rise, and valve actuation. Battery backup verification. Software/firmware version check on PLC controllers. Validate touch-screen interface display on LPU. Simulate fire signal activation.

Type-general inspection and maintenance points for this equipment category — not model-specific.

Suppliers & Spare Parts

Direct links to manufacturer, datasheet, spare-parts portal and dealers — request access below.

📄 Request sourcing links & documents
🛠 Manage this equipment in your fleet

Cases, daily reports, timesheets and AI troubleshooting in the OceanSphere Marine app — free for 14 days.

Start free trial →
🔎 Suppliers & service for this equipment

Find manufacturers, repair shops and spare-part dealers in the Maritime Network — our global company directory.

Maritime Network →
Equipment Model #148697 · ✓ still in production