Sentryum Rack Marine UPS SMM 20 and UPS SMT 20

The Sentryum Rack Marine UPS (models SMM 20 and SMT 20) provides emergency, uninterruptible power in a compact rack‑mount form, delivering immediate backup to critical shipboard systems during mains failure.

Inspector Detail

Common issues

  • Category/type mismatch: filed under 'Emergency Power / Emergency Generator Set', but the Sentryum Rack Marine UPS (SMM 20 / SMT 20) is an uninterruptible power supply, not a generator - covered here as a UPS
  • Battery capacity degradation over time, reducing backup runtime below the rated duration
  • Battery terminal corrosion or loose connections causing intermittent power loss
  • Ventilation/cooling fan failure causing overheating in the rack enclosure
  • Inverter/charger card faults triggering false alarms or forcing bypass mode
  • Loss of mains/charger input not properly alarmed to the bridge/ECR
  • Battery thermal or charging-control faults depending on battery chemistry fitted

Inspection checklist

  • Check battery voltage, condition and terminal tightness
  • Verify the UPS switches cleanly to battery on a simulated mains-loss test, and back again
  • Confirm backup runtime under rated load meets or exceeds the specified duration
  • Check ventilation/cooling fans and filters for the rack enclosure
  • Verify alarm outputs (mains fail, low battery, fault) report correctly to the monitoring/alarm system
  • Inspect the battery compartment for corrosion, swelling or damage
  • Check output voltage/frequency quality under load
  • Verify earthing/bonding of the rack enclosure

Service intervals

Battery condition check (voltage, visual) monthly
Full battery load/runtime test annually, or per maker interval
Battery replacement typically every 3-5 years for VRLA batteries, per maker recommendation and test results
Ventilation fan/filter check quarterly
Function test (simulated mains failure) per SOLAS/class requirement for the equipment served, commonly monthly to quarterly

Typical wear limits

Battery backup runtime renew the battery set once measured runtime falls to roughly 80% of rated duration or below - confirm against the maker's test procedure
Battery internal resistance/impedance renew once it rises significantly above the as-new baseline recorded at commissioning - trend against that baseline rather than a fixed figure

Ranges are typical for this design class. Always confirm against the manufacturer documentation for your serial number.

Critical spares

  • Replacement battery set (matched, same batch/age)
  • Cooling fan module
  • Charger/inverter card
  • Input/output fuses
  • Battery interconnect cables/terminals

Safety

  • VRLA/lead-acid batteries can vent hydrogen gas - ensure enclosure ventilation is adequate with no ignition sources nearby
  • Stored energy at the battery terminals is a short-circuit risk - use insulated tools and remove jewellery when working on connections
  • The UPS remains live from the battery side even with mains input isolated - treat as energised until proven de-energised
  • Overheated or swollen batteries must be replaced immediately, not returned to service

Class survey

Filed under 'Emergency Power / Emergency Generator Set', but the actual product is an uninterruptible power supply, not a generator set. Where this UPS serves navigation, communication or safety systems required by SOLAS, class verifies battery test records and confirms backup duration meets the requirement for the equipment served - it does not substitute for a required emergency generator.

Estimated lifetime: UPS electronics (charger/inverter) are typically designed for 10+ years of service; the battery is the limiting component and is typically renewed every 3-5 years depending on chemistry, temperature and duty cycle - confirm against the maker's data sheet.

Components & Design

Component data being added…

Technical Data

🤖 Ask about this model

One free question — answered like a marine engineer. No account needed.

Suppliers & Spare Parts

Direct links to manufacturer, datasheet, spare-parts portal and dealers — request access below.

📄 Request sourcing links & documents
🛠 Manage this equipment in your fleet

Cases, daily reports, timesheets and AI troubleshooting in the OceanSphere Marine app — free for 14 days.

Start free trial →
🔎 Suppliers & service for this equipment

Find manufacturers, repair shops and spare-part dealers in the Maritime Network — our global company directory.

Maritime Network →

DNV type approval

Verified against the DNV Approval Finder — the certificate below is issued by DNV, not by us.

Certificate
TAE00004T7
Approved as
UPS · Electrical Equipment and Systems
Certificate holder
RPS S.p.A. (Italy)
Valid until
2028-10-03
Open the certificate at DNV →