LSM-HF 1,8/3 kV or TEMAR PHFX-A 1,8/3 kV
LSM-HF 1,8/3 kV or TEMAR PHFX-A 1,8/3 kV by Prysmian Group Finland Oy. DNV TA certificate TAE00000SC.
Inspector Detail
▸
Common issues
- Insulation thermal ageing at heavily loaded cable runs, especially near switchboards
- Gland moisture ingress at deck and bulkhead penetrations
- Mechanical damage sustained during cable pulling or later maintenance work nearby
- Screen or armour corrosion in damp trunking or bilge-adjacent routes
- Overheating at poorly torqued terminations rather than the cable itself
- Rodent or mechanical chafe damage inside cable trunking on older vessels
Inspection checklist
- Thermal check (by hand-held thermometer or thermal imaging where available) at terminations and lugs
- Insulation resistance test on the run, logged and trended over time
- Check termination and lug tightness/torque at switchboards and junction boxes
- Visual inspection of the cable route for chafe, crushing, or exposed conductor
- Check cable support spacing has not sagged or allowed chafe against structure
- Confirm cable identification/tagging is legible and matches the single-line/cable schedule
- Check earthing continuity of screen/armour where fitted
Service intervals
| Insulation resistance test | annually, per the vessel's planned maintenance system |
| Thermal check of terminations | annually, or sooner on heavily loaded circuits |
| Visual route inspection | annually |
| Termination torque check | at major overhaul or when a termination is disturbed for any reason |
Critical spares
- Spare cable length of the correct rating and fire/halogen performance
- Cable lugs and terminations matching conductor size
- Heat-shrink termination and jointing kits
- Cable glands rated for the installation location
Safety
- Shock and arc-flash hazard at terminations carrying up to 1.8/3 kV - isolate and prove dead before working
- Fire risk from insulation failure if the wrong cable type or a damaged run has gone unnoticed
- Confined cable routes through trunking where access for inspection is limited
Class survey
Class checks that the DNV type-approved cable actually installed matches the approved cable schedule for this circuit, that halogen-free/low-smoke requirements for the space are met, and wants insulation resistance test records available at survey rather than a one-off check on the day.
Components & Design
Component data being added…
Technical Data
🤖 Ask about this model
One free question — answered like a marine engineer. No account needed.
Suppliers & Spare Parts
Direct links to manufacturer, datasheet, spare-parts portal and dealers — request access below.
📄 Request sourcing links & documentsCases, daily reports, timesheets and AI troubleshooting in the OceanSphere Marine app — free for 14 days.
Start free trial →Find manufacturers, repair shops and spare-part dealers in the Maritime Network — our global company directory.
Maritime Network →DNV type approval
Verified against the DNV Approval Finder — the certificate below is issued by DNV, not by us.
- Certificate
- TAE00000SC
- Approved as
- Electric Power Cable · Electrical Equipment and Systems
- Certificate holder
- Prysmian Group Finland Oy (Finland)
- Valid until
- 2030-06-30