automatic round fire damper type HCF
automatic round fire damper type HCF by Nanjing Hengxinda. DNV MED certificate 4244902 Lux.
Inspector Detail
▸
Common issues
- Damper blade fails to seat fully closed due to corrosion or paint buildup on seat/frame
- Actuator linkage seizes from lack of lubrication, so the damper does not respond to the CO2 release signal
- Limit switch / position indicator misaligned, giving a false open or closed status at the fire panel
- Gasket/seal deterioration allowing smoke or CO2 leakage past a nominally closed damper
- Manual override handle rusted or missing, preventing local operation during a drill
- Frame corrosion from engine room heat/humidity cycling, especially where routed near exhaust trunking
- Fusible link or spring-return mechanism (if fitted) contaminated with oil mist, delaying closure
Inspection checklist
- Confirm the damper closes fully under gravity/spring or actuator with no manual assistance, blade seating evenly
- Check that position indication at the local damper and at the fire control/CO2 release panel agree
- Verify the manual local closing handle operates smoothly and the damper can be reset without forcing
- Inspect gasket/seal around the blade perimeter for hardening, cracking or missing sections
- Check hinge pins and linkage for corrosion and free movement without binding
- Verify damper identification and location match the fire control plan and CO2 zone drawing
- Function test coordinated with the CO2 system drill, confirming the damper responds within the required time
- Check duct penetration fire-stopping/sealing around the damper frame is intact
Service intervals
| Function/close test | at each CO2 system drill, at least annually |
| Lubrication of hinge/linkage | per PMS, typically every 3-6 months |
| Gasket/seal inspection | annually |
| Position indicator/limit switch check | annually |
| Corrosion touch-up/painting | as needed, typically at drydock or when found |
Critical spares
- Blade seal/gasket set
- Actuator return spring or fusible link (if fitted)
- Hinge pins and bushings
- Position indicator microswitch
- Manual reset/override handle assembly
Safety
- A damper that fails to close leaves an open path for smoke or fire and lets CO2 vent uncontrolled from the protected space, reducing extinguishing concentration
- CO2 release into an occupied space is an asphyxiation hazard - damper closure must never be wedged open or defeated
- Sharp blade edges and spring-loaded mechanisms can cause hand injury during manual testing
- Working near ducting at height during inspection requires standard fall protection
Class survey
Fire dampers forming part of a fixed CO2 system are covered under the CO2 system's fire-fighting equipment survey. Surveyors typically want a witnessed or logged functional closing test, confirmation that the damper matches the approved fire control plan, and PMS records of drill/test dates. The type-approval certificate should be verified against the physical nameplate at survey.
Components & Design
Component data being added…
Technical Data
🤖 Ask about this model
One free question — answered like a marine engineer. No account needed.
Suppliers & Spare Parts
Direct links to manufacturer, datasheet, spare-parts portal and dealers — request access below.
📄 Request sourcing links & documentsCases, daily reports, timesheets and AI troubleshooting in the OceanSphere Marine app — free for 14 days.
Start free trial →Find manufacturers, repair shops and spare-part dealers in the Maritime Network — our global company directory.
Maritime Network →DNV type approval
Verified against the DNV Approval Finder — the certificate below is issued by DNV, not by us.
- Certificate
- 4244902 Lux
- Approved as
- Fire protection
- Certificate holder
- Nanjing Hengxinda (China)
- Valid until
- 2030-01-01